Summary
PRCOM20120634
Building Permit - Commercial
Final Completion
DACUR INVESTMENT COMPANY INC
ALTERATION COMMERCIAL
TEMPORARY PRE-SALE AREA
04/02/2012
04/03/2012
04/23/2012
Locations
Contacts
MIKE HAGEN ELECTRIC CO, Address:8820 NE 108TH ST, Phone:(816) 734-5100  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
DARLAND CONSTRUCTION CO, Address:4115 S 133RD ST, Phone:(402) 827-8202  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 04/12/2012 04/12/2012
Jim Eden
Misc
Corrective Action Required
04/11/2012

IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1. Exit signs are not required in rooms or areas that require only one exit or exit access. 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official. 3. Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3. 4. Exit signs are not required in sleeping areas in occupancies in Group I-3. 5. In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency. Verified at inspection. Provide over two exits.
Misc
Corrective Action Required
04/11/2012

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Verified at inspection.
Misc
Corrective Action Required
04/11/2012

Panic hardware on existing doors shalll be in working condition. Any locks on push/pull doors shall be thumb latched. Verified at inspection.
Misc
Corrective Action Required
04/11/2012

This review is for the temporary sales area only.
Portable fire extinguishers - general
Corrective Action Required
04/11/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of 2, 2A:10B:C fire extinguishers in the space. Verified at inspection.
Internal Plan Review (Res) Approved 04/12/2012 04/03/2012
Mike Weisenborn
True
Building Plan Review Approved 04/12/2012 04/03/2012
Mike Weisenborn
Bldg - Exit signage - Where required
Corrective Action Required
04/03/2012

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - To be verified on inspection.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
04/03/2012

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - To be verified on inspection.
License Tax Codes Approved 04/12/2012 04/02/2012
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $32.99 $32.99 Paid 04/03/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 4/13/2012 at 12:00 AM 04/13/2012
Misc
Partial Correction
04/13/2012
PHASE 1 AREA: NO SAFETY ISSUES FOUND ABOVE CEILING AT ACT CEILING AREA -- OK TO COVER WHEN READY; NO SYSTEMS ROUGH-IN ISSUES FOUND EXPOSED OR BELOW CEILING
Final Inspection - Commercial Partial 4/18/2012 4/18/2012 at 12:00 AM 04/18/2012
Misc
Partial Correction
04/18/2012
CONTINGENT ON LS FIRE DEPT APPROVAL, OK TO USE & OCCUPY PHASE ONE AREA (TEMPORARY USE IN ANTICIPATION OF SUBSEQUENT PHASES)
Occupancy Inspection - Fire Temporary C of O 4/18/2012 at 12:00 AM 04/18/2012
All Rough Inspection - Commercial Passed 4/13/2012 at 12:00 AM 04/22/2012
Misc
Resolved
04/22/2012
PHASE 1 AREA: NO SAFETY ISSUES FOUND ABOVE CEILING AT ACT CEILING AREA -- OK TO COVER WHEN READY; NO SYSTEMS ROUGH-IN ISSUES FOUND EXPOSED OR BELOW CEILING
Occupancy Inspection - Fire Passed 4/18/2012 at 12:00 AM 04/23/2012
Final Inspection - Commercial Passed 4/23/2012 at 12:00 AM 04/23/2012
Misc
Resolved
04/22/2012
CONTINGENT ON LS FIRE DEPT APPROVAL, OK TO USE & OCCUPY PHASE ONE AREA (TEMPORARY USE IN ANTICIPATION OF SUBSEQUENT PHASES)
Documents & Images
Date Uploaded File Type Document Name
04/03/2012 Letter Building Permit
04/03/2012 Letter Plan Review Conditions
04/13/2012 Letter Inspection Summary
04/18/2012 Letter Inspection Summary
04/18/2012 Letter Fire Loss Reduction Form
04/23/2012 Letter Inspection Summary
04/23/2012 Letter Inspection Summary
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter Final Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home