Permit Application Status

PRCOM20120225


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20120225
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
FINISH SPACE FOR BANQUET FACILITY
02/13/2012
03/12/2012
10/15/2014
05/14/2012
Locations
Contacts
INTEGRAL CONSTRUCTION SERVICES, INC, Address:303 SW MARKET ST, Phone:(816) 246-5655  
GREEN FIELD ENERGY GROUP INC, Address:5 SW 4TH ST, Phone:(816) 524-5616  
CROSS ELECTRIC INC, Address:18705 E HIGHLAND DR, Phone:(816) 540-2452  
CL HOWERTON ENTERPRISES LLC, Address:224 NW AA HWY, Phone:(816) 237-6338  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/11/2012
Jim Eden
Installation acceptance testing
Corrective Action Required
04/10/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Misc
Corrective Action Required
04/10/2012

Duct detection shall send supervisory signals only to the FACP. Activation shall cause a supervisory alarm only without activation of interior horn/strobes.
Construction documents - Fire protection systems
Corrective Action Required
04/11/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans recieved 4/2/2012. Engineer stamp on building permit set.
Sprinkler Plan Review Released for Construction 04/11/2012
Jim Eden
Misc
Corrective Action Required
03/19/2012

Plans released per plan revisions and letter from H.D. Doshi P.E. dated March 14, 2012.
Installation acceptance testing
Corrective Action Required
03/19/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/19/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of a current annual inspection. Verified at inspection.
Internal Plan Review (Res) Approved 03/13/2012 03/09/2012
Tracy Deister
WITH ATTACHED CONDITIONS. TRACY DEISTER 03/09/2012 4:39 PM
Building Plan Review Approved 03/13/2012 03/09/2012
Tracy Deister
Accessibility - Water closet - Grab bars
Resolved
03/09/2012

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - Add the required vertical grab bar to the plans.
Misc
Resolved
03/09/2012

The door and fram schedule is not complete. Door hardware information is not provided. Action required - Door hardware information, such as closers and latch, is needed to determine clear floor space requirements. Add additional information.
Accessibility - Maneuvering Clearance at Doors.
Resolved
03/09/2012

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the pull side of doors 02 and 04. Make needed corrections.
Misc
Resolved
03/09/2012

Not all new walls are provided with construction notes. Action required - Provide construction notes for all new walls.
Plumb - Urinal partitions
Resolved
03/09/2012

2006 IPC 310.5 - Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater. Action required - A partition is required between the urinal and the lavatory. Make needed corrections.
Bldg - Toilet rooms - Walls
Resolved
03/09/2012

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - If paint is to be used in these areas it must be an epoxy based paint. Make needed corrections.
Plumb - Water closet general clearance
Resolved
03/09/2012

2006 IPC 405.3.1 - Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition, vanity or other obstruction, or closer than 30 inches center-to-center between adjacent fixtures. There shall be at least a 21-inch clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches wide and 60 inches deep. Action required - The two non-accessible water closets in the womens restroom do not meet this requirement. Make needed corrections.
Mech - Outdoor air required
Resolved
03/09/2012

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - I am unable to locate the calculations for this. Please provide additional information.
Misc
Resolved
03/09/2012

Exhaust fans are to be sized based on the number of water closets/urinals located in the space. The plans show the same size fan in each of the restrooms and each restroom has a different number of fixtures and is being supplied with different amounts of supply air. The amount of outside air being supplied to the restrooms does not match the requirement in Table 403.3. Action required - Make needed corrections.
Screening - Ground mounted equipment
Corrective Action Required
03/07/2012

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Obtain approval from Planning and Development for required screening of the new exterior mechanical units.
Misc
Corrective Action Required
03/07/2012

Obtain zoning approval due to increased parking requirements for the use prior to permit approval.
Misc
Resolved
03/09/2012

The plans indicate a warming kitchen but nothing on the plans indicate any kind of food warming devices being installed. Action required - Please clearify.
Misc
Resolved
03/09/2012

Electrical panel schedules have not been provided. Action required - Provide additional information.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
03/07/2012

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - The plans do not provide details showing the height of the sink in the warming kitchen. As this is not a commercial kitchen it is required to meet this requirement. Provide additional information. THE SINK MUST BE INSTALLED AT A MAXIMUM OF 34 INCHES ABOVE THE FLOOR.
Bldg - Exit signage - Where required
Resolved
03/09/2012

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - An exit sign for the west exit shall be installed so that it is visable from the space. Make needed corrections.
Misc
Corrective Action Required
03/07/2012

As this space is receiving power from two services, all associated equipment on the exterior of the building, such as disconnects and meters shall be labeled with this tenant address. Action required - This will be verified on inspection.
WITH ATTACHED CONDITIONS. TRACY DEISTER 03/09/2012 4:38 PM
Fire Plan Review Approved 03/13/2012 03/07/2012
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
03/07/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide stamped plans for sprinkler system modification.
Construction documents for fire alarm systems
Corrective Action Required
03/07/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for alarm system alteration.
Misc
Corrective Action Required
03/07/2012

Per a phone conversation with the contractor the space was to be used as a wedding chapel. Recalculate the occupant load for the space for non-fixed seating. Action Required 3/7/2012: Occupancy for "The Room" is to be calculated as an assebblywithout fixed seats, concentrated (chairs only). This is to be reflected on the occupancy load sign as required for this space. Verified at inspection
Installation acceptance testing
Corrective Action Required
03/07/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Posting of occupant load
Corrective Action Required
03/07/2012

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Misc
Corrective Action Required
03/07/2012

The existing exterior doors shall be push/pull, or provided with panic hardware. Verified at inspection.
Misc
Corrective Action Required
03/07/2012

2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Provide an exit sign near the corridor from the Room to the west exit. Shown on resubmittal 3/7/12
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/07/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. All existing fire protection systems shall have documentation of a current annual inspection. Verified at inspection.
Zoning Review Approved 02/24/2012
Mike Weisenborn
Internal Plan Review (Res) Rejected 02/24/2012 02/24/2012
Mike Weisenborn
Fire Plan Review Rejected 02/24/2012 02/24/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/24/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide stamped plans for sprinkler system modification.
Construction documents for fire alarm systems
Corrective Action Required
02/24/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for alarm system alteration.
Misc
Corrective Action Required
02/24/2012

Per a phone conversation with the contractor the space was to be used as a wedding chapel. Recalculate the occupant load for the space for non-fixed seating.
Installation acceptance testing
Corrective Action Required
02/24/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Posting of occupant load
Corrective Action Required
02/24/2012

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Misc
Corrective Action Required
02/24/2012

The existing exterior doors shall be push/pull, or provided with panic hardware. Verified at inspection.
Misc
Corrective Action Required
02/24/2012

2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Provide an exit sign near the corridor from the Room to the west exit.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/24/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. All existing fire protection systems shall have documentation of a current annual inspection. Verified at inspection.
License Tax Codes Approved 02/24/2012 02/23/2012
Mike Weisenborn
Building Plan Review Rejected 02/24/2012 02/23/2012
Mike Weisenborn
Accessibility - Water closet - Grab bars
Corrective Action Required
03/09/2012

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - Add the required vertical grab bar to the plans.
Misc
Corrective Action Required
03/09/2012

The door and fram schedule is not complete. Door hardware information is not provided. Action required - Door hardware information, such as closers and latch, is needed to determine clear floor space requirements. Add additional information.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
03/09/2012

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the pull side of doors 02 and 04. Make needed corrections.
Misc
Corrective Action Required
03/09/2012

Not all new walls are provided with construction notes. Action required - Provide construction notes for all new walls.
Plumb - Urinal partitions
Corrective Action Required
03/09/2012

2006 IPC 310.5 - Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater. Action required - A partition is required between the urinal and the lavatory. Make needed corrections.
Bldg - Toilet rooms - Walls
Corrective Action Required
03/09/2012

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - If paint is to be used in these areas it must be an epoxy based paint. Make needed corrections.
Plumb - Water closet general clearance
Corrective Action Required
03/09/2012

2006 IPC 405.3.1 - Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition, vanity or other obstruction, or closer than 30 inches center-to-center between adjacent fixtures. There shall be at least a 21-inch clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches wide and 60 inches deep. Action required - The two non-accessible water closets in the womens restroom do not meet this requirement. Make needed corrections.
Mech - Outdoor air required
Corrective Action Required
03/09/2012

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - I am unable to locate the calculations for this. Please provide additional information.
Misc
Corrective Action Required
03/09/2012

Exhaust fans are to be sized based on the number of water closets/urinals located in the space. The plans show the same size fan in each of the restrooms and each restroom has a different number of fixtures and is being supplied with different amounts of supply air. The amount of outside air being supplied to the restrooms does not match the requirement in Table 403.3. Action required - Make needed corrections.
Screening - Ground mounted equipment
Corrective Action Required
02/23/2012

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Obtain approval from Planning and Development for required screening of the new exterior mechanical units.
Misc
Corrective Action Required
02/23/2012

Obtain zoning approval due to increased parking requirements for the use prior to permit approval.
Misc
Corrective Action Required
03/09/2012

The plans indicate a warming kitchen but nothing on the plans indicate any kind of food warming devices being installed. Action required - Please clearify.
Misc
Corrective Action Required
03/09/2012

Electrical panel schedules have not been provided. Action required - Provide additional information.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
02/23/2012

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - The plans do not provide details showing the height of the sink in the warming kitchen. As this is not a commercial kitchen it is required to meet this requirement. Provide additional information.
Bldg - Exit signage - Where required
Corrective Action Required
03/09/2012

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - An exit sign for the west exit shall be installed so that it is visable from the space. Make needed corrections.
Misc
Corrective Action Required
02/23/2012

As this space is receiving power from two services, all associated equipment on the exterior of the building, such as disconnects and meters shall be labeled with this tenant address. Action required - This will be verified on inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $98.97 $98.97 Paid 03/12/2012
8331507-Sewer Connection Fee $300.00 $300.00 Paid 03/12/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 3/13/2012 3/13/2012 at 12:00 AM 03/13/2012
Misc
Partial Correction
03/13/2012
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING EXCEPT F.D. @ MECH RM NOT YET INSTALLED.
In-wall Inspection Failed 3/19/2012 at 12:00 AM 03/19/2012
Misc
Corrective Action Required
03/19/2012
MECH RM @ SE: 1) FIREBLOCKING AND SHIELD PLATES WITHIN MECH RM NOT REQ'D IF AND ONLY IF NO DRYWALL AT WALLS AND NO CEILING 2) TRUSS JOIST AT W WALL: BOTTOM CHORD NOTCHED -- ENGINEER REPORT REQUIRED 3) OVERBORED(>60%) NON-BEARING STUDS REQUIRE REINFORCEMENT 4) PLUMBING SHIELD PLATES AT TOP AND BOTTOM PLATES MUST BE DEEP BOCA PLATES
Sprinkler - Hydrostatic Test Passed 3/19/2012 at 12:00 AM 03/19/2012
All Rough Inspection - Commercial Partial 3/26/2012 at 12:00 AM 03/26/2012
Misc
Corrective Action Required
03/26/2012
TOPS OF EXTERIOR WALL CAVITIES TO BE FIREBLOCKED TO PREVENT FIRE COMMUNICATION TO INTERSTITIAL SPACE ABOVE CEILING
Misc
Corrective Action Required
03/26/2012
FIREBLOCKING REQUIRED AT 10' HORIZONTAL INTERVALS TO PREVENT FIRE TRAVEL WITHIN EXTERIOR WALLS
Misc
Corrective Action Required
03/26/2012
BOCA PROTECTION PLATES REQUIRED AT PVC PLUMBING STACK
All Rough Inspection - Commercial Partial 3/27/2012 at 12:00 AM 03/27/2012
Misc
Corrective Action Required
03/26/2012
TOP OF SOUTH EXTERIOR WALL CAVITY TO BE FIREBLOCKED TO PREVENT FIRE COMMUNICATION TO INTERSTITIAL SPACE ABOVE CEILING
Misc
Resolved
03/27/2012
FIREBLOCKING REQUIRED AT 10' HORIZONTAL INTERVALS TO PREVENT FIRE TRAVEL WITHIN EXTERIOR WALLS
Misc
Partial Correction
03/27/2012
5" TALL BOCA PROTECTION PLATE REQUIRED AT BOTTOM OF PVC PLUMBING STACK
All Rough Inspection - Commercial Passed 3/30/2012 at 12:00 AM 03/30/2012
Misc
Resolved
03/30/2012
TOP OF SOUTH EXTERIOR WALL CAVITY TO BE FIREBLOCKED TO PREVENT FIRE COMMUNICATION TO INTERSTITIAL SPACE ABOVE CEILING
Misc
Resolved
03/30/2012
5" TALL BOCA PROTECTION PLATE REQUIRED AT BOTTOM OF PVC PLUMBING STACK
Above Ceiling Inspection Partial 3/30/2012 at 12:00 AM 03/30/2012
Misc
Partial Correction
03/30/2012
OK TO COVER WHEN READY GWB CEILINGS; ACT CEILING AREAS SUBJECT TO APPROVAL WHEN GRID IS IN PLACE AND ABOVE-CEILING SYSTEMS ARE COMPLETED
Above Ceiling Inspection Passed 4/24/2012 at 12:00 AM 04/24/2012
Misc
Resolved
04/24/2012
OK TO COVER WHEN READY GWB CEILINGS; ACT CEILING AREAS SUBJECT TO APPROVAL WHEN GRID IS IN PLACE AND ABOVE-CEILING SYSTEMS ARE COMPLETED
Gas Piping Inspection - Commercial Passed 4/24/2012 at 12:00 AM 04/24/2012
Gas Service Inspection - Commercial Passed 4/24/2012 at 12:00 AM 04/24/2012
Rough Electrical Inspection - Commercial Passed 4/27/2012 (8:00 to 5:00) 4/27/2012 at 12:00 AM 04/27/2012
Alarm Test Passed 4/27/2012 at 1:00 AM 04/27/2012
Occupancy Inspection - Codes Commercial Temporary C of O 5/4/2012 5/4/2012 at 12:00 AM 05/04/2012
Misc
Corrective Action Required
05/04/2012
ADA/ANSI: PADDING REQUIRED ON PIPING UNDER ACCESSIBLE RESTROOM LAVS/SINKS
Misc
Corrective Action Required
05/04/2012
ADVISE TO CAP DISCONTINUOUS WATER PIPE AT UTILITY ROOM S.E.
Misc
Corrective Action Required
05/04/2012
DUPLEX RECEPTACLES AT SUMP PUMP AND CLOTHES WASHER -- PROVIDE GFCI PROTECTION OR CHANGE TO DEDICATED SINGLE PLUG
Misc
Corrective Action Required
05/04/2012
MAKE ELECTRICAL RECEPTACLES SOLID TO BOX @ CATERING ROOM EAST WALL
Misc
Corrective Action Required
05/04/2012
AFFIX "NO SMOKING" SIGN TO PUBLIC ENTRY DOORS
Misc
Corrective Action Required
05/04/2012
PLACE 133 MAX OCCUPANCY SIGN PER FIRE DEPT
Occupancy Inspection - Fire Passed 5/4/2012 at 12:00 AM 05/04/2012
In-wall Inspection Passed 5/4/2012 at 12:00 AM 05/04/2012
Misc
Resolved
05/04/2012
MECH RM @ SE: 1) FIREBLOCKING AND SHIELD PLATES WITHIN MECH RM NOT REQ'D IF AND ONLY IF NO DRYWALL AT WALLS AND NO CEILING 2) TRUSS JOIST AT W WALL: BOTTOM CHORD NOTCHED -- ENGINEER REPORT REQUIRED 3) OVERBORED(>60%) NON-BEARING STUDS REQUIRE REINFORCEMENT 4) PLUMBING SHIELD PLATES AT TOP AND BOTTOM PLATES MUST BE DEEP BOCA PLATES
Underslab Plumbing Inspection - Commercial Passed 5/4/2012 at 12:00 AM 05/04/2012
Misc
Resolved
05/04/2012
OK TO COVER WHEN READY UNDER-SLAB PVC DWV PIPING EXCEPT F.D. @ MECH RM NOT YET INSTALLED.
Occupancy Inspection - Codes Commercial Partial 5/4/2012 at 12:00 AM 05/04/2012
Misc
Corrective Action Required
05/04/2012
ADA/ANSI: PADDING REQUIRED ON PIPING UNDER ACCESSIBLE RESTROOM LAVS/SINKS
Misc
Corrective Action Required
05/04/2012
ADVISE TO CAP DISCONTINUOUS WATER PIPE AT UTILITY ROOM S.E.
Misc
Corrective Action Required
05/04/2012
DUPLEX RECEPTACLES AT SUMP PUMP AND CLOTHES WASHER -- PROVIDE GFCI PROTECTION OR CHANGE TO DEDICATED SINGLE PLUG
Misc
Corrective Action Required
05/04/2012
MAKE ELECTRICAL RECEPTACLES SOLID TO BOX @ CATERING ROOM EAST WALL
Misc
Corrective Action Required
05/04/2012
AFFIX "NO SMOKING" SIGN TO PUBLIC ENTRY DOORS
Misc
Resolved
05/04/2012
PLACE 133 MAX OCCUPANCY SIGN PER FIRE DEPT
Occupancy Inspection - Codes Commercial Full C of O 5/14/2012 5/14/2012 at 12:00 AM 05/14/2012
Misc
Resolved
05/14/2012
ADA/ANSI: PADDING REQUIRED ON PIPING UNDER ACCESSIBLE RESTROOM LAVS/SINKS
Misc
Resolved
05/14/2012
ADVISE TO CAP DISCONTINUOUS WATER PIPE AT UTILITY ROOM S.E.
Misc
Resolved
05/14/2012
DUPLEX RECEPTACLES AT SUMP PUMP AND CLOTHES WASHER -- PROVIDE GFCI PROTECTION OR CHANGE TO DEDICATED SINGLE PLUG
Misc
Resolved
05/14/2012
MAKE ELECTRICAL RECEPTACLES SOLID TO BOX @ CATERING ROOM EAST WALL
Misc
Resolved
05/14/2012
AFFIX "NO SMOKING" SIGN TO PUBLIC ENTRY DOORS
Documents & Images
Date Uploaded File Type Document Name
02/24/2012 Letter Plan Review Conditions
03/09/2012 Letter Plan Review Conditions
03/12/2012 Letter Building Permit
03/12/2012 Letter Plan Review Conditions
03/13/2012 Letter Inspection Summary
03/19/2012 Letter Fire (Sprinkler) Plan Review
03/19/2012 Letter Inspection Summary
03/26/2012 Letter Inspection Summary
03/26/2012 Letter Inspection Summary
03/27/2012 Activity Document 20120327084542998.pdf
03/27/2012 Letter Inspection Summary
03/30/2012 Letter Inspection Summary
03/30/2012 Letter Inspection Summary
04/24/2012 Letter Inspection Summary
04/27/2012 Letter Inspection Summary
05/04/2012 Letter Temporary Certificate of Occupancy
05/04/2012 Letter Fire Loss Reduction Form
05/14/2012 Letter Field Certificate of Occupancy
05/15/2012 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home