Permit Application Status

PRCOM20116356


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20116356
Building Permit - Commercial
Final Completion
JOHN KNOX VILLAGE
ALTERATION COMMERCIAL
ROOF MOUNTED PV SYSTEM - "SOLAR" - 8.10 KW SYSTEM
12/20/2011
12/28/2011
12/30/2011
Locations
Contacts
BRIGHTERGY LLC, Address:1712 MAIN STREEET 6TH FLOOR, Phone:(816) 866-0555  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/04/2012 12/28/2011
Mike Weisenborn
Misc
Corrective Action Required
12/27/2011

102.7 Subjects not regulated by this code. Where no applicable standards or requirements are set forth in this code, or are contained within other laws, codes, regulations, ordinances or bylaws adopted by the jurisdiction, compliance with applicable standards of the National Fire Protection Association or other nationally recognized fire safety standards, as approved, shall be deemed as prima facie evidence of compliance with the intent of this code. Nothing herein shall derogate from the authority of the fire code official to determine compliance with codes or standards for those activities or installations within the fire code official’s jurisdiction or responsibility. 102.8 Matters not provided for. Requirements that are essential for the public safety of an existing or proposed activity, building or structure, or for the safety of the occupants thereof, which are not specifically provided for by this code shall be determined by the fire code official. Section 605.11 Solar Photovoltaic Systems of the 2012 IFC has not been adopted by the City of Lee's Summit but shall serve as the regulatory document for this project per the sections listed above.
Misc
Corrective Action Required
12/27/2011

The correct address for this project is 518 NW Murray Road.
True
Fire Plan Review Approved 01/04/2012 12/27/2011
Jim Eden
Misc
Corrective Action Required
12/27/2011

102.7 Subjects not regulated by this code. Where no applicable standards or requirements are set forth in this code, or are contained within other laws, codes, regulations, ordinances or bylaws adopted by the jurisdiction, compliance with applicable standards of the National Fire Protection Association or other nationally recognized fire safety standards, as approved, shall be deemed as prima facie evidence of compliance with the intent of this code. Nothing herein shall derogate from the authority of the fire code official to determine compliance with codes or standards for those activities or installations within the fire code official’s jurisdiction or responsibility. 102.8 Matters not provided for. Requirements that are essential for the public safety of an existing or proposed activity, building or structure, or for the safety of the occupants thereof, which are not specifically provided for by this code shall be determined by the fire code official. Section 605.11 Solar Photovoltaic Systems of the 2012 IFC has not been adopted by the City of Lee's Summit but shall serve as the regulatory document for this project per the sections listed above.
Building Plan Review Approved 01/04/2012 12/21/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $98.97 $98.97 Paid 12/28/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Electrical Inspection - Commercial Passed 12/30/2011 at 12:00 AM 12/30/2011
Occupancy Inspection - Fire Temporary C of O 1/4/2012 at 12:00 AM 12/30/2011
Misc
Corrective Action Required
12/30/2011
Label breaker panel in basement mechanical room.
Misc
Corrective Action Required
12/30/2011
Label the inverter, inverter disconnects with address labels.
FD703.1.1 Fireblocking and Draftstopping.
Corrective Action Required
12/30/2011
Required fireblocking and draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction. Maint fire stopping in mechanical room per Codes Admin.
Documents & Images
Date Uploaded File Type Document Name
12/28/2011 Letter Building Permit
12/30/2011 Letter Inspection Summary
12/30/2011 Letter Inspection Summary
12/30/2011 Letter Fire Loss Reduction Form
07/05/2013 Letter Final Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home