Permit Application Status

PRCOM20116335


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20116335
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
REMODEL SHELL SPACE ON THIRD FLOOR OF HOSPITAL FOR IT & MARKETING OFFICES. IT WILL MOVE OUT OF ADMITTING AREA ON 1ST FLOOR AND ADMITTING AREA WILL BE REMODELED TO ADD 2 OFFICES. IT SPACE WILL BE USED FOR STAFF OFFICES AND TO BUILDING COMPUTER WORKSTATIONS.
12/19/2011
01/05/2012
05/11/2012
Locations
Contacts
ACI BOLAND, Address:11229 NALL, SUITE 140  
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 01/26/2012
Jim Eden
Misc
Corrective Action Required
01/26/2012

Alterations shall be designed and completed to the 2002 edition of NFPA 13.
Misc
Corrective Action Required
01/26/2012

Alterations will be inspected at occupancy inspection.
Internal Plan Review (Res) Approved 01/03/2012 01/04/2012
Mike Weisenborn
True
Building Plan Review Approved 01/03/2012 01/03/2012
Mike Weisenborn
Alarm Plan Review Released for Construction 01/03/2012
Jim Eden
Installation acceptance testing
Corrective Action Required
01/03/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Hold open devices and notification appliances to be tested at occupancy inspection.
Misc
Corrective Action Required
01/03/2012

Replace the visual appliance in the Admitting area. Verified at inspection.
Fire Plan Review Approved 01/03/2012 01/03/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
01/03/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for sprinkler alateration.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
01/03/2012

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Verified at inspection.
License Tax Codes Approved 01/03/2012 12/21/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $610.32 $610.32 Paid 01/05/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 1/24/2012 at 12:00 AM 01/24/2012
Misc
Partial Correction
01/24/2012
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT 077 N,E,S WALLS;
In-wall Inspection Partial 2/8/2012 2/8/2012 at 12:00 AM 02/08/2012
Misc
Partial Correction
01/24/2012
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT 077 AFTER PUTTY PAD IS COMPLETED AT WEST WALL; 68A, 69A, 69B, 69C, 69D AFTER TWO ELECTRICAL BOXES ARE PUTTY-PADDED PER DISCUSSION
Above Ceiling Inspection Partial 2/8/2012 2/8/2012 at 12:00 AM 02/08/2012
Misc
Partial Correction
02/08/2012
OK TO COVER WHEN READY GYP BOARD CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 077 AFTER TEMPORARY ELECTRICAL WIRING IS REMOVED;
Rated Assembly Inspection Partial 2/15/2012 at 12:00 AM 02/15/2012
Misc
Partial Correction
02/15/2012
OK TO COVER WHEN READY FOLLOWING RATED ASSEMBLY COMPONENTS: SPACE 069D LID AND VERTICAL SHAFT WALL PER RFI-3;
Rated Assembly Inspection Not Ready 2/16/2012 at 12:00 AM 02/16/2012
Misc
Partial Correction
02/15/2012
OK TO COVER WHEN READY FOLLOWING RATED ASSEMBLY COMPONENTS: SPACE 069D LID AND VERTICAL SHAFT WALL PER RFI-3;
Rated Assembly Inspection Partial 2/17/2012 2/16/2012 at 12:00 AM 02/16/2012
Misc
Partial Correction
02/16/2012
OK TO COVER WHEN READY FOLLOWING RATED ASSEMBLY COMPONENTS: SPACE 069D LID AND VERTICAL SHAFT WALL PER RFI-3; WALLS @ 068A, 069A, 069B, 069D, INCLUDING OFFSET PER RFI-3;
Above Ceiling Inspection Partial 2/28/2012 (8:00 to 5:00) 2/28/2012 at 12:00 AM 02/28/2012
Misc
Partial Correction
02/08/2012
OK TO COVER WHEN READY GYP BOARD CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 077; 068A; 069B; 069C; 069D;
In-wall Inspection Passed 2/28/2012 at 12:00 AM 02/28/2012
Misc
Resolved
02/28/2012
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT 077 AFTER PUTTY PAD IS COMPLETED AT WEST WALL; 68A, 69A, 69B, 69C, 69D AFTER TWO ELECTRICAL BOXES ARE PUTTY-PADDED PER DISCUSSION
Alarm Test Partial 3/8/2012 at 12:00 AM 03/08/2012
Occupancy Inspection - Codes Commercial Partial 3/14/2012 at 12:00 AM 03/14/2012
Misc
Partial Correction
03/14/2012
FOLLOWING SPACES OK FOR USE & OCCUPANCY: 068A; 069A; 069C; 069D; 077;
Occupancy Inspection - Fire Temporary C of O 3/14/2012 at 12:00 AM 03/14/2012
Misc
Corrective Action Required
03/14/2012
Ok for tco when approved by codes administration
Rough Framing Inspection - Commercial Partial 3/28/2012 3/28/2012 at 12:00 AM 03/28/2012
Misc
Partial Correction
03/28/2012
OK TO COVER WHEN READY WALL FRAMING AND DOOR FRAME INSTALLATION FOR DOOR 1A038A PER PR-2
Occupancy Inspection - Fire Temporary C of O 4/9/2012 at 12:00 AM 04/09/2012
Misc
Corrective Action Required
04/06/2012
Ok for tco when approved by codes administration
Final Inspection - Commercial Partial 4/9/2012 at 12:00 AM 04/09/2012
Misc
Partial Correction
04/09/2012
FOLLOWING SPACES OK FOR USE & OCCUPANCY: 068A; 069A; 069C; 069D; 077; 007 PER PR-3;
In-wall Inspection Passed 4/20/2012 at 12:00 AM 04/20/2012
Above Ceiling Inspection Partial 5/3/2012 (8:00 to 5:00) 5/3/2012 at 12:00 AM 05/03/2012
Misc
Partial Correction
02/28/2012
OK TO COVER WHEN READY GYP BOARD CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 077; 068A; 069B; 069C; 069D; 007C; 007D;
Above Ceiling Inspection Partial 5/3/2012 at 12:00 AM 05/03/2012
Misc
Partial Correction
05/03/2012
OK TO COVER WHEN READY GYP BOARD CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 077; 068A; 069B; 069C; 069D;
Misc
Partial Correction
05/03/2012
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 007C; 007D;
Above Ceiling Inspection Partial 5/3/2012 at 12:00 AM 05/03/2012
Misc
Partial Correction
05/03/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 077; 069B;
Misc
Partial Correction
05/03/2012
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 007C; 007D; 068A; 069B; 069C; 069D;
Occupancy Inspection - Codes Commercial Partial 5/10/2012 5/9/2012 at 12:00 AM 05/09/2012
Misc
Partial Correction
03/14/2012
FOLLOWING SPACES OK FOR USE & OCCUPANCY: 068A; 069A; 069C; 069D; 077; 007; 007C; 007D
Alarm Test Passed 5/10/2012 at 12:00 AM 05/10/2012
Occupancy Inspection - Fire Passed 5/10/2012 at 12:00 AM 05/10/2012
Misc
Corrective Action Required
04/09/2012
Ok for tco when approved by codes administration
Final Inspection - Commercial Passed 5/11/2012 at 12:00 AM 05/11/2012
Misc
Resolved
05/11/2012
FOLLOWING SPACES OK FOR USE & OCCUPANCY: 068A; 069A; 069C; 069D; 077; 007 PER PR-3;
Above Ceiling Inspection Passed 5/11/2012 at 12:00 AM 05/11/2012
Misc
Resolved
05/11/2012
OK TO COVER WHEN READY GWB CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 077; 069B;
Misc
Resolved
05/11/2012
OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 007C; 007D; 068A; 069B; 069C; 069D;
Rated Assembly Inspection Passed 5/11/2012 at 12:00 AM 05/11/2012
Misc
Resolved
05/11/2012
OK TO COVER WHEN READY FOLLOWING RATED ASSEMBLY COMPONENTS: SPACE 069D LID AND VERTICAL SHAFT WALL PER RFI-3; WALLS @ 068A, 069A, 069B, 069D, INCLUDING OFFSET PER RFI-3;
Rough Framing Inspection - Commercial Passed 5/11/2012 at 12:00 AM 05/11/2012
Misc
Resolved
05/11/2012
OK TO COVER WHEN READY WALL FRAMING AND DOOR FRAME INSTALLATION FOR DOOR 1A038A PER PR-2
Documents & Images
Date Uploaded File Type Document Name
01/05/2012 Letter Building Permit
01/05/2012 Letter Plan Review Conditions
01/24/2012 Letter Inspection Summary
02/08/2012 Letter Inspection Summary
02/15/2012 Letter Inspection Summary
02/16/2012 Letter Inspection Summary
02/28/2012 Letter Inspection Summary
03/08/2012 Letter Fire Loss Reduction Form
03/14/2012 Letter Inspection Summary
03/28/2012 Letter Inspection Summary
04/09/2012 Letter Inspection Summary
04/20/2012 Letter Inspection Summary
05/03/2012 Letter Inspection Summary
05/03/2012 Letter Inspection Summary
05/03/2012 Letter Inspection Summary
05/03/2012 Letter Inspection Summary
05/03/2012 Letter Inspection Summary
05/09/2012 Letter Inspection Summary
05/10/2012 Letter Fire Loss Reduction Form
05/11/2012 Letter Inspection Summary
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
06/27/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home