Permit Application Status

PRCOM20116313


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20116313
Building Permit - Commercial
Final Completion
THE NORTHWESTERN MUTUAL LIFE INS CO
ALTERATION COMMERCIAL
SPRINKLER SYSTEM ALTERATIONS FOR THE ENTIRE COMPLEXE
12/14/2011
12/21/2011
11/03/2014
Locations
Contacts
THE NORTHWESTERN MUTUAL LIFE INS CO, Address:PO BOX 3151  
JVM NEW LONGVIEW LLC, Address:PO BOX 06494  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/14/2011
Jim Eden
Corrective Action Required
12/14/2011

Corrective Action Required
12/14/2011

True
Sprinkler Plan Review Released for Construction 12/14/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
12/14/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Alteration plans for Buildings A-J on 12/1/2011.
Misc
Corrective Action Required
12/14/2011

Design criteria shall be to the 2002 Edition of NFPA 13. For information only.
Installation acceptance testing
Corrective Action Required
12/14/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule an inspection.
Misc
Corrective Action Required
12/14/2011

Impairment of the system shall be kept to a minimum. Notify Fire Communications at (816) 969-7407 when systems go out of service and when they are restored.
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Investigation Inspection Complete 6/19/2012 at 12:00 AM 05/24/2017
Documents & Images
Date Uploaded File Type Document Name
06/27/2013 Letter Fire (Sprinkler) Plan Review
07/02/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home