Summary
PRCOM20116192
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
PILLARS OF TRUTH TENANT FINISH
12/01/2011
01/06/2012
06/17/2012
02/21/2012
Locations
Contacts
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
INNOVATIVE DESIGN AND RENOVATION, Address:2 W 52ND ST  
OBI CONSULTING ENGINEERS INC, Address:1220 E 63RD ST STE 200, Phone:(816) 822-7292  
RW ELECTRIC AND CONSTRUCTION INC, Address:3515 E 34TH ST, Phone:(816) 935-7282  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/05/2012
Tracy Deister
True
Fire Plan Review Approved 12/13/2011 01/05/2012
Jim Eden
Address numbers required
Corrective Action Required
01/05/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The space shall be posted with one address.
Posting of occupant load
Resolved
01/05/2012

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required:Indicate how the occupant load was determined. Posting to be verified at inspection 12/22/2011- Establish the occupant load of the sanctuary based on fixed seating per IFC/IBC Section 1004.7 and Table 1004.1.1.
Misc
Resolved
01/05/2012

Provide a door schedule indicating hardware type. Panic hardware is required for occupant loads greater than 50. Provide a door schedule.
Building Plan Review Approved 12/27/2011 01/03/2012
Tracy Deister
Misc
Corrective Action Required
12/20/2011

2006 IBC Section 803 Wall and Ceiling Finishes Provide verification that finish materials comply with flame spread and smoke-develop requirements.
Bldg - Egress width - Door encroachment
Corrective Action Required
12/20/2011

2006 IBC 1005.2 - Door encroachment. Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 7 inches into the required width. Drawing resubmittal required. Three doors in Hall behind Sanctuary are non-compliant.
Misc
Corrective Action Required
12/20/2011

2006 IBC Section 1108 Special Occupancies 1108.2 General. In addition to other requirements of this chapter, the requirements of Sections 1108.2 through 1108.4 shall apply to specific occupancies. Resubmit drawings to show how accessible seating will be provided in sanctuary.
Construction documents required
Corrective Action Required
12/20/2011

Lees Summit Code of Ordinance - 7-138 - Construction documents shall be dimensioned and drawn upon suitable material. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. In other than occupancies in Groups R-2, R-3 and I-1, the construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. Construction documents for all buildings shall describe the exterior wall envelope in sufficient detail to determine compliance with this code. Resubmitted drawings to depict construction of pulpit/stage/platform.
License contractors
Corrective Action Required
12/20/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. General Contractor as well as MEP sub contractors must be licensed and listed on permit prior to approval.
WITH CONDITIONS. TRACY DEISTER 01/03/2012 10:52 AM
Fire Plan Review Rejected 12/13/2011 12/22/2011
Jim Eden
Address numbers required
Corrective Action Required
12/22/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The space shall be posted with one address.
Posting of occupant load
Corrective Action Required
12/22/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required:Indicate how the occupant load was determined. Posting to be verified at inspection 12/22/2011- Establish the occupant load of the sanctuary based on fixed seating per IFC/IBC Section 1004.7 and Table 1004.1.1.
Portable fire extinguishers - general
Resolved
12/22/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one, 2A:10B:C fire extinguisher at a conspicuous location.
Misc
Corrective Action Required
12/22/2011

Provide a door schedule indicating hardware type. Panic hardware is required for occupant loads greater than 50. Provide a door schedule.
Misc
Resolved
12/22/2011

1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. Exception: Doors, when fully opened, and handrails, shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) on each side. Action required: How will this be met?
Internal Plan Review (Res) Rejected 12/13/2011 12/20/2011
Tracy Deister
Building Plan Review Rejected 12/13/2011 12/09/2011
Joe Frogge
Misc
Resolved
12/20/2011

2006 IBC Section 803 Wall and Ceiling Finishes Provide verification that finish materials comply with flame spread and smoke-develop requirements.
Bldg - Egress width - Door encroachment
Carried Forward
01/03/2012

2006 IBC 1005.2 - Door encroachment. Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 7 inches into the required width. Drawing resubmittal required. Three doors in Hall behind Sanctuary are non-compliant. These doors will not be installed and will be cased openings only. TRACY DEISTER 01/03/2012 10:16 AM
Misc
Resolved
12/20/2011

2006 IBC Section 1108 Special Occupancies 1108.2 General. In addition to other requirements of this chapter, the requirements of Sections 1108.2 through 1108.4 shall apply to specific occupancies. Resubmit drawings to show how accessible seating will be provided in sanctuary.
Misc
Carried Forward
12/09/2011

2006 IBC Section 1110 Signage. Accessibility signage will be verifed in the field.
Construction documents required
Resolved
12/20/2011

Lees Summit Code of Ordinance - 7-138 - Construction documents shall be dimensioned and drawn upon suitable material. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. In other than occupancies in Groups R-2, R-3 and I-1, the construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. Construction documents for all buildings shall describe the exterior wall envelope in sufficient detail to determine compliance with this code. Resubmitted drawings to depict construction of pulpit/stage/platform.
License contractors
Corrective Action Required
12/09/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. General Contractor as well as MEP sub contractors must be licensed and listed on permit prior to approval.
Fire Plan Review Rejected 12/13/2011 12/05/2011
Jim Eden
Address numbers required
Corrective Action Required
12/05/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The space shall be posted with one address.
Posting of occupant load
Corrective Action Required
12/05/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required:Indicate how the occupant load was determined. Posting to be verified at inspection
Portable fire extinguishers - general
Corrective Action Required
12/05/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one, 2A:10B:C fire extinguisher at a conspicuous location.
Misc
Corrective Action Required
12/05/2011

Provide a door schedule indicating hardware type. Panic hardware is required for occupant loads greater than 50.
Misc
Corrective Action Required
12/05/2011

1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. Exception: Doors, when fully opened, and handrails, shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) on each side. Action required: How will this be met?
Zoning Review Approved 12/13/2011 12/05/2011
Hector Soto Jr.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $40.85 $40.85 Paid 01/06/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Temporary C of O 1/12/2012 at 12:00 AM 01/12/2012
Misc
Corrective Action Required
01/12/2012
(1) label all front and back dorrswith the same address (653) (2) supply (3) 2A-10BC extinguishers and mount in the locations as discussed (3) remove slide bolt locks from the rear doors and repair panic hardware (4) post an occupant load of (124) in the sanctuary
In-wall Inspection Not Ready 1/12/2012 at 12:00 AM 01/12/2012
Misc
Corrective Action Required
01/12/2012
PARTIAL IN-WALL INSPECTION TO BE PERFORMED WHEN ACCESSIBLE
Occupancy Inspection - Codes Commercial Failed 1/12/2012 at 12:00 AM 01/12/2012
Misc
Corrective Action Required
01/12/2012
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
01/12/2012
WATER UTILITIES DEPARTMENT INSPECTION (PARTICULARLY BACKFLOW PREVENTION AT MAIN ENTRY)
Misc
Corrective Action Required
01/12/2012
ELECTRICAL PANELS SCHEDULES: NEC 110-22; 384-13; IRC E36O6.2: EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
01/12/2012
ENSURE ALL ELECTRICAL RECEPTACLES SRE SECURED SOLID TO BOX
Misc
Corrective Action Required
01/12/2012
ELECTRICAL RECEPTACLE AT SW RESTROOM IS NOT GFCI PROTECTED
Misc
Corrective Action Required
01/12/2012
ENSURE ALL ELECTRICAL RECEPTACLES AND SWITCHES HAVE FACE PLATES IN PLACE
Misc
Corrective Action Required
01/12/2012
"NO SMOKING" SIGNS TO BE AFFIXED TO PUBLIC ENTRANCE DOORS
Occupancy Inspection - Codes Commercial Failed 1/12/2012 at 12:00 AM 01/12/2012
Misc
Corrective Action Required
01/12/2012
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
01/12/2012
WATER UTILITIES DEPARTMENT INSPECTION (PARTICULARLY BACKFLOW PREVENTION AT MAIN ENTRY)
Misc
Corrective Action Required
01/12/2012
ELECTRICAL PANELS SCHEDULES: NEC 110-22; 384-13; IRC E36O6.2: EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
01/12/2012
ENSURE ALL ELECTRICAL RECEPTACLES SRE SECURED SOLID TO BOX
Misc
Corrective Action Required
01/12/2012
ELECTRICAL RECEPTACLE AT SW RESTROOM IS NOT GFCI PROTECTED
Misc
Corrective Action Required
01/12/2012
ENSURE ALL ELECTRICAL RECEPTACLES AND SWITCHES HAVE FACE PLATES IN PLACE
Misc
Corrective Action Required
01/12/2012
"NO SMOKING" SIGNS TO BE AFFIXED TO PUBLIC ENTRANCE DOORS
Misc
Corrective Action Required
01/12/2012
ACCESSIBLE RESTROOM PROVISIONS TO BE COMPLETED PER PLAN
In-wall Inspection Passed 1/13/2012 at 12:00 AM 01/13/2012
Misc
Resolved
01/13/2012
PARTIAL IN-WALL INSPECTION TO BE PERFORMED WHEN ACCESSIBLE
Occupancy Inspection - Codes Commercial Temporary C of O 1/13/2012 at 12:00 AM 01/13/2012
Misc
Corrective Action Required
01/13/2012
CONTINUITY OF BRANCH WIRING EQUIPMENT GROUNDING CONDUCTORS WHEREVER >= 2 CABLES IN BOXES: NEC 250.148; IRC 3808.13: USE LISTED WIRE NUTS OR CRIMP CONNECTORS
Misc
Corrective Action Required
01/13/2012
ACCESSIBLE RESTROOM TO BE PROVIDED PER APPROVED DRAWING
Occupancy Inspection - Fire Passed 01/20/2012
Misc
Corrective Action Required
01/12/2012
(1) label all front and back dorrswith the same address (653) (2) supply (3) 2A-10BC extinguishers and mount in the locations as discussed (3) remove slide bolt locks from the rear doors and repair panic hardware (4) post an occupant load of (124) in the sanctuary
Occupancy Inspection - Codes Commercial Temporary C of O 1/24/2012 at 12:00 AM 01/24/2012
Miscellaneous Inspection Passed 1/25/2012 at 12:00 AM 01/25/2012
Occupancy Inspection - Codes Commercial Temporary C of O 2/16/2012 at 12:00 AM 02/16/2012
Misc
Partial Correction
02/16/2012
RESTROOM RE-CONFIGURATION IN PROGRESS
Occupancy Inspection - Codes Commercial Full C of O 2/21/2012 at 12:00 AM 02/21/2012
Misc
Resolved
02/21/2012
RESTROOM RE-CONFIGURATION IN PROGRESS
Documents & Images
Date Uploaded File Type Document Name
12/09/2011 Letter Plan Review Conditions
01/06/2012 Letter Building Permit
01/06/2012 Letter Plan Review Conditions
01/12/2012 Letter Fire Loss Reduction Form
01/12/2012 Letter Inspection Summary
01/13/2012 Letter Temporary Certificate of Occupancy
01/20/2012 Letter Fire Loss Reduction Form
01/24/2012 Letter Temporary Certificate of Occupancy
01/24/2012 Letter Temporary Certificate of Occupancy
02/10/2012 Letter 10-Day Notice of Violation
02/10/2012 Letter 10-Day Notice of Violation
02/14/2012 Activity Document Mail Receipt
02/16/2012 Letter Temporary Certificate of Occupancy
02/21/2012 Letter Field Certificate of Occupancy
02/22/2012 Letter Final Certificate of Occupancy
02/22/2012 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
07/02/2013 Letter Plan Review Conditions
08/27/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.