Permit Application Status

PRCOM20115824


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20115824
Building Permit - Commercial
Certificate of Occupancy
ERIC DEAN ENTERPRISES INC
ALTERATION COMMERCIAL
MGA 2ND FLOOR NORTH - HARRIS CORPORATION TENANT REMODEL
10/27/2011
11/04/2011
05/02/2012
12/06/2011
Locations
Contacts
3 SQUARE CONTRACTING INC, Address:1243 MERRIAM LANE, Phone:(913) 754-3033  
ERIC DEAN ENTERPRISES INC, Address:255 NW BLUE PKWY  
NSPJ ARCHITECTS, Address:3515 W 75TH ST, SUITE 201  
BOWERS ELECTRIC LLC, Address:720 S ROGERS RD, STE C200, Phone:(913) 530-8003  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 11/11/2011 11/07/2011
Brian Austerman
Misc
Corrective Action Required
11/07/2011

Fire Department- Plans approved as per conditions listed in comments from 11-02-2011
Internal Plan Review (Res) Approved 11/04/2011
Joe Frogge
True
Building Plan Review Approved 11/11/2011 11/04/2011
Joe Frogge
Misc
Resolved
11/04/2011

2006 IBC 1109.11 Seating at tables, counters and work surfaces. Where seating or standing space at fixed or built-in tables, counters or work surfaces is provided in accessible spaces, at least 5 percent of the seating and standing spaces, but not less than one, shall be accessible. In Group I-3 occupancy visiting areas 5 percent, but not less than one, cubicle or counter shall be accessible on both the visitor and detainee sides. Exceptions: 1. Check-writing surfaces at check-out aisles not required to comply with Section 1109.12.2 are not required to be accessible. 2. In Group I-3 occupancies, the counter or cubicle on the detainee side is not required to be accessible at noncontact visiting areas or in areas not serving accessible holding cells or sleeping units. Action: Update drawing to depict how this requirement will be met. Note: accessible portion of counter must meet requirements of 2003 ICC/ANSI A117.1 Chapters 3 and 9.
License contractors
Resolved
11/04/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action: Licensed electrical and mechanical contractors must be listed on permit prior to issuance. Notes: 1. The electrical contractor (Bowers) listed on permit application is not licensed to work in Lee's Summit. 2. Provide letter describing how mechincal work is not required.
Construction documents required
Resolved
11/04/2011

Lees Summit Code of Ordinance - 7-138 - Construction documents shall be dimensioned and drawn upon suitable material. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. In other than occupancies in Groups R-2, R-3 and I-1, the construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. Construction documents for all buildings shall describe the exterior wall envelope in sufficient detail to determine compliance with this code. Action: Provide mechanical and electrical drawins or detailed scopes of work.
Internal Plan Review (Res) Rejected 11/08/2011 11/04/2011
Codes Admin
Building Plan Review Rejected 11/08/2011 11/02/2011
Joe Frogge
Misc
Corrective Action Required
11/02/2011

2006 IBC 1109.11 Seating at tables, counters and work surfaces. Where seating or standing space at fixed or built-in tables, counters or work surfaces is provided in accessible spaces, at least 5 percent of the seating and standing spaces, but not less than one, shall be accessible. In Group I-3 occupancy visiting areas 5 percent, but not less than one, cubicle or counter shall be accessible on both the visitor and detainee sides. Exceptions: 1. Check-writing surfaces at check-out aisles not required to comply with Section 1109.12.2 are not required to be accessible. 2. In Group I-3 occupancies, the counter or cubicle on the detainee side is not required to be accessible at noncontact visiting areas or in areas not serving accessible holding cells or sleeping units. Action: Update drawing to depict how this requirement will be met. Note: accessible portion of counter must meet requirements of 2003 ICC/ANSI A117.1 Chapters 3 and 9.
License contractors
Corrective Action Required
11/02/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action: Licensed electrical and mechanical contractors must be listed on permit prior to issuance. Notes: 1. The electrical contractor (Bowers) listed on permit application is not licensed to work in Lee's Summit. 2. Provide letter describing how mechincal work is not required.
Construction documents required
Corrective Action Required
11/02/2011

Lees Summit Code of Ordinance - 7-138 - Construction documents shall be dimensioned and drawn upon suitable material. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. In other than occupancies in Groups R-2, R-3 and I-1, the construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. Construction documents for all buildings shall describe the exterior wall envelope in sufficient detail to determine compliance with this code. Action: Provide mechanical and electrical drawins or detailed scopes of work.
Fire Plan Review Approved 11/08/2011 11/02/2011
Brian Austerman
Misc
Corrective Action Required
11/02/2011

1006.4 Performance of system. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 1 foot-candle (11 lux) and a minimum at any point of 0.1 foot-candle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 foot-candle (6 lux) average and a minimum at any point of 0.06 foot-candle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded. Action Required: Provide emergency lighting if not already equipped, verified at inspection
Misc
Corrective Action Required
11/02/2011

1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action Required: Provide exit signs if not already present, verified at inspection
Portable fire extinguishers - general
Corrective Action Required
11/02/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide a minimum of a 2A10B:C for every 75' of travel distance. Verified at inspection
Address numbers required
Corrective Action Required
11/02/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Provide addressing on all doors leading into the space, including suite designation. Verified at inspection
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $84.13 $84.13 Paid 11/04/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 11/9/2011 11/9/2011 at 12:00 AM 11/09/2011
Above Ceiling Inspection Not Ready 12/1/2011 at 12:00 AM 11/17/2011
Misc
Corrective Action Required
11/17/2011
ELECTRICAL WORK IN PROGRESS ABOVE CEILING. FIRE ALARM WIRING AND DEVICES NOT IN PERMANENT LOCATIONS. MC CABLE TO BE SECURED WITHIN 12" OF BOXES WHEREVER PRACTICAL. TWO UNUSED OPENINGS AT BOXES POINTED-OUT TO ELECTRICIAN ON JOB -- TO BE CLOSED. GENERAL CONTRACTOR NOT ON JOBSITE.
Above Ceiling Inspection Partial 11/21/2011 at 12:00 AM 11/21/2011
Misc
Partial Correction
11/21/2011
AFTER DAMAGEED HVAC DUCT INSULATION IS FULLY REPAIRED OK TO COVER ACT TILE CEILING EXCEPT LEAVE OUT TWO TILES WHERE MC CABLE IS NOT SECURED AT ENTRY TO TWO JUNCTION BOXES -- LOCATION POINTED-OUT TO JOHNSON CONTROLS PERSONNEL. G.C. NOT ON SITE.
Misc
Corrective Action Required
11/21/2011
ENSURE ALL WATER LEAKS ARE REPAIRED. SEE LOCATIONS WHERE CEILING TILE IS STAINED.
Occupancy Inspection - Fire Temporary C of O 11/29/2011 at 12:00 AM 11/29/2011
Above Ceiling Inspection Passed 11/29/2011 at 12:00 AM 11/29/2011
Misc
Resolved
11/29/2011
AFTER DAMAGEED HVAC DUCT INSULATION IS FULLY REPAIRED OK TO COVER ACT TILE CEILING EXCEPT LEAVE OUT TWO TILES WHERE MC CABLE IS NOT SECURED AT ENTRY TO TWO JUNCTION BOXES -- LOCATION POINTED-OUT TO JOHNSON CONTROLS PERSONNEL. G.C. NOT ON SITE.
Misc
Resolved
11/29/2011
ENSURE ALL WATER LEAKS ARE REPAIRED. SEE LOCATIONS WHERE CEILING TILE IS STAINED.
Occupancy Inspection - Codes Commercial Failed 11/29/2011 at 12:00 AM 11/29/2011
Corrective Action Required
11/29/2011
NEED ADDRESSING ON EXTERIOR DOORS
Misc
Corrective Action Required
11/29/2011
SOFT/LOOSE ELECTRICAL RECEPTACLES >> CHECK ALL AND TIGHTEN AS REQUIRED
Misc
Corrective Action Required
11/29/2011
BACKSET AT MICROWAVE OVEN RECEPTACLE NOT NEC CONFORMING -- REQUIRES SPARK RING
Misc
Corrective Action Required
11/29/2011
BACKFLOW PREVENTION DEVICE REQUIRED FOR WATER FEED TO ICE MAKER
Misc
Corrective Action Required
11/29/2011
PROVIDE UPDATED ELECTRICAL PANEL SCHEDULE WITH ACCURATE, CLEAR, LEGIBLE LABELS
Occupancy Inspection - Codes Commercial Temporary C of O 12/1/2011 12/1/2011 at 12:00 AM 12/01/2011
Misc
Resolved
12/01/2011
SOFT/LOOSE ELECTRICAL RECEPTACLES >> CHECK ALL AND TIGHTEN AS REQUIRED
Misc
Resolved
12/01/2011
BACKSET AT MICROWAVE OVEN RECEPTACLE NOT NEC CONFORMING -- REQUIRES SPARK RING
Misc
Resolved
12/01/2011
BACKFLOW PREVENTION DEVICE REQUIRED FOR WATER FEED TO ICE MAKER
Misc
Corrective Action Required
12/01/2011
RESOLVE FIRE DEPARTMENT ISSUES
Occupancy Inspection - Codes Commercial Full C of O 12/6/2011 at 12:00 AM 12/06/2011
Misc
Resolved
12/06/2011
RESOLVE FIRE DEPARTMENT ISSUES -- OK PER J DIR 12/6/11
Documents & Images
Date Uploaded File Type Document Name
11/02/2011 Letter Plan Review Conditions
11/04/2011 Letter Building Permit
11/04/2011 Letter Plan Review Conditions
11/09/2011 Letter Inspection Summary
11/17/2011 Letter Inspection Summary
11/21/2011 Letter Inspection Summary
11/29/2011 Letter Inspection Summary
12/01/2011 Letter Temporary Certificate of Occupancy
12/06/2011 Letter Field Certificate of Occupancy
12/07/2011 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home