Permit Application Status

PRCOM20115779


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20115779
Building Permit - Commercial
Closed
PFIZER INC
ALTERATION COMMERCIAL
Alarm System Replacement
10/24/2011
08/21/2012
Locations
Contacts
PFIZER INC, Address:150 E 42ND ST FL 38TH  
SIEMENS INDUSTRY INC, Address:7938 Marshall Dr, Phone:(317) 596-3260 Ext:2546  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/24/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/24/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans recieved October 21, 2011.
Misc
Corrective Action Required
10/24/2011

Provide smoke detection over the FACP. Verified at inspection.
Installation acceptance testing
Corrective Action Required
10/24/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Misc
Corrective Action Required
10/24/2011

The fire suppression system for the hydrocarbon storage unit shall be monitored by the alarm system. Verified at inspection.
Misc
Corrective Action Required
10/24/2011

Duct detection activation shall provide a supervisory signal only without activating the interior horn/strobes. Verified at inspection.
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Alarm Test Passed 01/05/2012
Documents & Images
Date Uploaded File Type Document Name
10/24/2011 Letter Fire (Alarm) Plan Review Notice
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home