Permit Application Status

PRCOM20115556


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20115556
Building Permit - Commercial
Certificate of Occupancy
CATHOLIC DIOCESE OF KC-ST JOE
ALTERATION COMMERCIAL
INTERIOR REMODEL
10/07/2011
11/08/2011
04/17/2012
07/12/2012
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
CITY WIDE HEATING & COOLING INC, Address:2824 ROE LANE, Phone:(913) 384-6006  
R F FISHER ELECTRIC COMPANY LLC, Address:5299 DTC BLVD STE 600, Phone:(913) 384-1500  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
CATHOLIC DIOCESE OF KC-ST JOE, Address:130 NE MURRAY RD  
HMN ARCHITECTS INC, Address:7400 W 110TH ST, SUITE 200, Phone:(913) 451-9075  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/21/2011 03/15/2012
Jim Eden
Installation acceptance testing
Corrective Action Required
03/15/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
Misc
Corrective Action Required
03/15/2012

The exterior horn strobe shall activate for water flow only. Verified at inspection.
Alarm Plan Review Rejected 01/26/2012
Jim Eden
Misc
Resolved
03/15/2012

907.4.1 Location. Manual fire alarm boxes shall be located not more than 5 feet (1524 mm) from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet (60 960 mm). Action required: Provide manual pull stations in the sanctuary.
Installation acceptance testing
Corrective Action Required
01/26/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
Misc
Resolved
03/15/2012

The floor plan for the classroom addition does not match the floor plan for what is being built (all alternates). Action required: Provide revised plans to include alternates.
Misc
Resolved
03/15/2012

Provide a waterproof horn/strobe over the FDC.
Misc
Corrective Action Required
03/15/2012

The exterior horn strobe shall activate for water flow only. Verified at inspection.
Internal Plan Review (Res) Approved 11/07/2011
Mike Weisenborn
True
Building Plan Review Approved 11/07/2011 11/07/2011
Mike Weisenborn
Screening - Rooftop equipment
Resolved
11/07/2011

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - Contact the Planning and Development Department for possible screening requirements for the new mechanical equipment.
Bldg - Accessibility - Assistive listening systems
Corrective Action Required
11/03/2011

2006 IBC 1108.2.6 - Assistive listening systems. Each assembly area where audible communications are integral to the use of the space shall have an assistive listening system. Action required - Provide additional informaiton.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
11/03/2011

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - I am unable to locate the emergency lighting in the Nave. Please provide additional informaiton.
Fire Plan Review Approved 11/07/2011 11/07/2011
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
11/03/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for allarm system alteration. ADDRESSED IN RESUBMITTAL
Installation acceptance testing
Corrective Action Required
11/03/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Posting of occupant load
Corrective Action Required
11/03/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: The occupant load(s) shall be posted in all assembly areas. The occupant loads in the Mulligan Rooms shall be posted by use i.e. Tables and chairs (15sqft/person), classroom (20sqft/person), or non-fixed seating (7sqft/person). It shall also be posted that non-fixed seating may only be utilized with the partitions open. ADDRESSED IN RESUBMITTAL
Misc
Corrective Action Required
11/03/2011

1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Forces shall be applied to the latch side. Action required: Doors 116 and 117 shall swing in the direction of travel. The door portion of the operable wall system shall swing in the direction of travel , out of the sanctuary. ADDRESSED IN RESUB, WITH THE ADDITION OF THE 3 MARKED EXITS THIS RESPONSE IS SATISFACTORY
Misc
Corrective Action Required
11/03/2011

703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position. Action required: Doors 116 and 117 shall be latching. ADDRESSED IN RESUB
Misc
Corrective Action Required
11/03/2011

Indicate where the west door from room 121 (Mulligan B) goes to. ADDRESSED IN RESUBMITTAL. A SITE VISIT WAS MADE AND EGRESS IS SATISFACTORY
Misc
Corrective Action Required
11/03/2011

IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required: Provide exit signage from the Mulligan Room(s), and above the center door of the sanctuary operable wall system. ADDRESSED IN RESUBMITTAL
Portable fire extinguishers - general
Corrective Action Required
11/03/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a fire extinguisher near the altar. ADDRESSED IN RESUBMITTAL
Misc
Corrective Action Required
11/03/2011

All duct detection shall be connected to the building fire alarm system. ADDRESSED IN RESUBMITTAL
Misc
Corrective Action Required
11/03/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required. Provide additional emergency lighting to the front of the sanctuary. ADDRESSED IN RESUBMITTAL
Internal Plan Review (Res) Rejected 10/19/2011 10/20/2011
Mike Weisenborn
Building Plan Review Rejected 10/19/2011 10/20/2011
Mike Weisenborn
Screening - Rooftop equipment
Corrective Action Required
10/20/2011

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - Contact the Planning and Development Department for possible screening requirements for the new mechanical equipment.
Bldg - Accessibility - Assistive listening systems
Corrective Action Required
10/20/2011

2006 IBC 1108.2.6 - Assistive listening systems. Each assembly area where audible communications are integral to the use of the space shall have an assistive listening system. Action required - Provide additional informaiton.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
10/20/2011

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - I am unable to locate the emergency lighting in the Nave. Please provide additional informaiton.
Fire Plan Review Rejected 10/19/2011 10/19/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
10/19/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for allarm system alteration.
Installation acceptance testing
Corrective Action Required
10/19/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Posting of occupant load
Corrective Action Required
10/19/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: The occupant load(s) shall be posted in all assembly areas. The occupant loads in the Mulligan Rooms shall be posted by use i.e. Tables and chairs (15sqft/person), classroom (20sqft/person), or non-fixed seating (7sqft/person). It shall also be posted that non-fixed seating may only be utilized with the partitions open.
Misc
Corrective Action Required
10/19/2011

1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Forces shall be applied to the latch side. Action required: Doors 116 and 117 shall swing in the direction of travel. The door portion of the operable wall system shall swing in the direction of travel , out of the sanctuary.
Misc
Corrective Action Required
10/19/2011

703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position. Action required: Doors 116 and 117 shall be latching.
Misc
Corrective Action Required
10/19/2011

Indicate where the west door from room 121 (Mulligan B) goes to.
Misc
Corrective Action Required
10/19/2011

IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required: Provide exit signage from the Mulligan Room(s), and above the center door of the sanctuary operable wall system.
Portable fire extinguishers - general
Corrective Action Required
10/19/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a fire extinguisher near the altar.
Misc
Corrective Action Required
10/19/2011

All duct detection shall be connected to the building fire alarm system.
Misc
Corrective Action Required
10/19/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required. Provide additional emergency lighting to the front of the sanctuary.
License Tax Codes Approved 10/19/2011 10/17/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $2,639.20 $2,639.20 Paid 11/08/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 11/14/2011
Misc
Partial Correction
11/14/2011
OK TO POUR WHEN READY PER DETAIL 03/S2.2 FOUR ADDITIONS TO EXISTING FOOTINGS AT NAVE SOUTH;
Footing Inspection - Commercial Partial 11/15/2011 (2:00) 11/15/2011 at 12:00 AM 11/15/2011
Misc
Partial Correction
11/15/2011
OK TO POUR WHEN READY PER DETAIL 03/S2.2 FOUR ADDITIONS TO EXISTING FOOTINGS AT NAVE SOUTH; PER A/E REVISION, TWO FOOTING ADDITIONS AT BAPTISTRY CORNERS PER 03/S2.2 IN LIEU OF BEAM PER 04/S2.2;
Underground Plumbing Inspection - Commercial Failed 1/3/2012 at 12:00 AM 01/03/2012
Misc
Partial Correction
02/22/2012
PARTIAL- RM 102 4" DRAIN FOR BACKFLOW RM 122 2" SINK
Underslab Electrical Inspection - Commercial Partial 2/7/2012 at 12:00 AM 02/07/2012
Misc
Partial Correction
02/07/2012
OK TO COVER WHEN READY: SIX 3/4" PVC CONDUITS FROM CHOIR LOFT AREA ALONG NW WALL OF NAVE TO RISERS @ WEST;
Foundation Inspection - Commercial Partial 2/7/2012 at 12:00 AM 02/07/2012
Misc
Partial Correction
02/07/2012
REPAIRS OF ANCHORAGE OF LAMINATED STRUCTURAL ARCHES: STRUCTURAL ASPECTS GUIDED & CERTIFIED BY ENGINEER OF RECORD. WEST / SOUTH / SOUTHEAST LOCATIONS POURED 2/7/12;
Footing Inspection - Commercial Passed 2/15/2012 at 12:00 AM 02/15/2012
Foundation Inspection - Commercial Passed 2/15/2012 at 12:00 AM 02/15/2012
Misc
Resolved
02/15/2012
REPAIRS OF ANCHORAGE OF LAMINATED STRUCTURAL ARCHES: STRUCTURAL ASPECTS GUIDED & CERTIFIED BY ENGINEER OF RECORD.
Rough Framing Inspection - Commercial Partial 2/22/2012 at 12:00 AM 02/22/2012
Misc
Partial Correction
02/22/2012
OK TO COVER WHEN READY: STRUCTURAL FRAMING PER 02 PARTIAL ROOF FRAMING PLAN ON S1.1; HANGING SOFFITS PER 2/A3.3 @ NAVE 106 SE/S/SW/W;
Rated Assembly Inspection Partial 2/29/2012 at 12:00 AM 02/29/2012
Misc
Partial Correction
02/29/2012
OK TO COVER WHEN READY 5/8" TYPE X GWB @ REMOVED AREAS OF CEILING AT NAVE 106 SE/S/SW/W: 1ST OF TWO LAYERS;
Rated Assembly Inspection Partial 3/2/2012 at 12:00 AM 03/02/2012
Misc
Partial Correction
02/29/2012
OK TO COVER WHEN READY 5/8" TYPE X GWB @ REMOVED AREAS OF CEILING AT NAVE 106 SE/S/SW/W: 1ST OF TWO LAYERS; 2ND OF TWO LAYERS
Sprinkler - Hydrostatic Test Passed 3/20/2012 at 10:00 AM 03/20/2012
Underground Plumbing Inspection - Commercial Passed 1/3/2012 at 12:00 AM 03/27/2012
Misc
Resolved
03/27/2012
PARTIAL- RM 102 4" DRAIN FOR BACKFLOW RM 122 2" SINK
Underslab Electrical Inspection - Commercial Passed 2/7/2012 at 12:00 AM 03/27/2012
Misc
Resolved
03/27/2012
OK TO COVER WHEN READY: SIX 3/4" PVC CONDUITS FROM CHOIR LOFT AREA ALONG NW WALL OF NAVE TO RISERS @ WEST;
All Rough Inspection - Commercial Partial 3/27/2012 at 12:00 AM 03/27/2012
Misc
Partial Correction
03/27/2012
FRAMING AND ENCLOSED SYSTEMS OK TO COVER AT FOLLOWING LOCATIONS: CANOPY SOFFIT @ DOOR E113; GWB LID AT 113; WALLS @ 109, 113, 115; WALLS AND GWB SOFFITS & CEILINGS @ 101, 105, 112, 114;
Gas Piping Inspection - Commercial Partial 3/30/2012 at 12:00 AM 03/30/2012
Misc
Partial Correction
03/30/2012
PRESSURE TEST ON GAS PIPING TO RTU's HELD STEADY AT > 10 PSI FOR > 20 MIN. APPROVED
Misc
Corrective Action Required
03/30/2012
BEFORE FINAL INSPECTION SUPPORT GAS PIPING PER INTERNATIONAL FUEL GAS CODE + PAINT PIPING TO PREVENT CORROSION.
In-wall Inspection Partial 4/4/2012 at 12:00 AM 04/04/2012
Misc
Partial Correction
04/04/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: 110;
Alarm Test Passed 04/19/2012
Occupancy Inspection - Fire Temporary C of O 4/19/2012 at 12:00 AM 04/19/2012
Misc
Corrective Action Required
04/19/2012
(1) removed door labeling from old sprinkler room door (2) label access doors to new sprinkler riser (3) label all sprinkler riser valves (4) label the FDC with wording indicating coverage of sprinkler sys. ( tower/south wing) (5) mount knox box by the fdc approx 6' off ground (6) keys needed for knox box: main FACP pull stations exterior access door sprinkler room doors padlock key to the corridor cages (70 arttempt to have duct detectors programed as supervisory with hvac shutdown OK for TCO once cleared through codes administration
Above Ceiling Inspection Failed 5/30/2012 at 12:00 AM 05/30/2012
Misc
Corrective Action Required
05/30/2012
ISSUES POINTED OUT TO SUPT KELLY
Above Ceiling Inspection Partial 5/31/2012 5/31/2012 at 12:00 AM 05/31/2012
Misc
Partial Correction
05/31/2012
OK TO COVER WHEN READY ACT CEILING FRAMING & ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: 101; 104A; 104B; 105; 110; 111; 114; 115;
All Rough Inspection - Commercial Partial 6/11/2012 (8:00 to 5:00) 6/11/2012 at 12:00 AM 06/11/2012
Misc
Partial Correction
03/27/2012
FRAMING AND ENCLOSED SYSTEMS OK TO COVER AT FOLLOWING LOCATIONS: CANOPY SOFFIT @ DOOR E113; GWB LID AT 113; WALLS @ 109, 113, 115; WALLS AND GWB SOFFITS & CEILINGS @ 101, 105, 112, 114; 122 W WALL AFTER BOCA PLATE IN PLACED TO PROTECT PVC FROM PENETRATION AND AFTER TOP PLATE OPENINGS ARE FIRE-BLOCKED
Above Ceiling Inspection Partial 6/19/2012 6/19/2012 at 12:00 AM 06/19/2012
Misc
Partial Correction
05/31/2012
OK TO COVER WHEN READY ACT CEILING FRAMING & ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: 101; 104A; 104B; 105; 110; 111; 114; 115; 120; 121; 122 EXCEPT WHERE SINK VENT MUST BE VTR
Alarm Test Passed 6/26/2012 at 1:00 PM 06/26/2012
Occupancy Inspection - Fire Temporary C of O 6/26/2012 at 12:00 AM 06/26/2012
Above Ceiling Inspection Partial 6/26/2012 at 12:00 AM 06/26/2012
Misc
Partial Correction
06/19/2012
OK TO COVER WHEN READY ACT CEILING FRAMING & ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: 101; 104A; 104B; 105; 110; 111; 114; 115; 120; 121; 122 EXCEPT WHERE SINK VENT MUST BE VTR
Occupancy Inspection - Codes Commercial Temporary C of O 6/26/2012 6/26/2012 at 12:00 AM 06/26/2012
Misc
Corrective Action Required
06/26/2012
SINK VENT @ 122 MUST BE VTR
Misc
Corrective Action Required
06/26/2012
ELECT RECEPT @ CHAPEL SW ARCED AT TEST -- THIS ROOM NOT TO BE OCCUPIED BEFORE REPAIR IS COMPLETED
Misc
Corrective Action Required
06/26/2012
OBTAIN APPROVAL OF PLANNING & DEVELOPMENT DEPT
Misc
Corrective Action Required
06/26/2012
OBTAIN APPROVAL OF FIRE DEPT
Misc
Corrective Action Required
06/26/2012
OBTAIN APPROVAL OF WATER DEPT
Above Ceiling Inspection Passed 6/26/2012 at 12:00 AM 06/26/2012
Misc
Resolved
06/26/2012
OK TO COVER WHEN READY ACT CEILING FRAMING & ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: 101; 104A; 104B; 105; 110; 111; 114; 115; 120; 121; 122 EXCEPT WHERE SINK VENT MUST BE VTR
All Rough Inspection - Commercial Passed 6/26/2012 at 12:00 AM 06/26/2012
Misc
Resolved
06/26/2012
FRAMING AND ENCLOSED SYSTEMS OK TO COVER AT FOLLOWING LOCATIONS: CANOPY SOFFIT @ DOOR E113; GWB LID AT 113; WALLS @ 109, 113, 115; WALLS AND GWB SOFFITS & CEILINGS @ 101, 105, 112, 114; 122 W WALL AFTER BOCA PLATE IN PLACED TO PROTECT PVC FROM PENETRATION AND AFTER TOP PLATE OPENINGS ARE FIRE-BLOCKED
Gas Piping Inspection - Commercial Passed 6/26/2012 at 12:00 AM 06/26/2012
Misc
Resolved
06/26/2012
PRESSURE TEST ON GAS PIPING TO RTU's HELD STEADY AT > 10 PSI FOR > 20 MIN. APPROVED
Misc
Resolved
06/26/2012
BEFORE FINAL INSPECTION SUPPORT GAS PIPING PER INTERNATIONAL FUEL GAS CODE + PAINT PIPING TO PREVENT CORROSION.
In-wall Inspection Passed 6/26/2012 at 12:00 AM 06/26/2012
Misc
Resolved
06/26/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: 110;
Rated Assembly Inspection Passed 06/26/2012
Misc
Resolved
06/26/2012
OK TO COVER WHEN READY 5/8" TYPE X GWB @ REMOVED AREAS OF CEILING AT NAVE 106 SE/S/SW/W: 1ST OF TWO LAYERS; 2ND OF TWO LAYERS
Rough Framing Inspection - Commercial Passed 6/26/2012 at 12:00 AM 06/26/2012
Misc
Resolved
06/26/2012
OK TO COVER WHEN READY: STRUCTURAL FRAMING PER 02 PARTIAL ROOF FRAMING PLAN ON S1.1; HANGING SOFFITS PER 2/A3.3 @ NAVE 106 SE/S/SW/W;
Occupancy Inspection - Codes Commercial Partial 7/2/2012 at 12:00 AM 07/02/2012
Misc
Resolved
07/02/2012
SINK VENT @ 122 MUST BE VTR
Misc
Resolved
07/02/2012
ELECT RECEPT @ CHAPEL SW ARCED AT TEST -- THIS ROOM NOT TO BE OCCUPIED BEFORE REPAIR IS COMPLETED
Misc
Corrective Action Required
06/26/2012
OBTAIN APPROVAL OF PLANNING & DEVELOPMENT DEPT
Misc
Corrective Action Required
06/26/2012
OBTAIN APPROVAL OF FIRE DEPT
Misc
Corrective Action Required
06/26/2012
OBTAIN APPROVAL OF WATER DEPT
Occupancy Inspection - Fire Passed 7/11/2012 at 12:00 AM 07/11/2012
Occupancy Inspection - Planning Passed 7/12/2012 at 12:00 AM 07/12/2012
Occupancy Inspection - Codes Commercial Full C of O 7/12/2012 at 12:00 AM 07/12/2012
Misc
Resolved
07/12/2012
OBTAIN APPROVAL OF PLANNING & DEVELOPMENT DEPT
Misc
Resolved
07/12/2012
OBTAIN APPROVAL OF FIRE DEPT
Misc
Resolved
07/12/2012
OBTAIN APPROVAL OF WATER DEPT
Occupancy Inspection - Engineering Passed 12/05/2013
Documents & Images
Date Uploaded File Type Document Name
10/20/2011 Letter Plan Review Conditions
11/08/2011 Letter Plan Review Conditions
11/08/2011 Letter Building Permit
11/15/2011 Letter Inspection Summary
01/03/2012 Letter Inspection Summary
01/03/2012 Letter Inspection Summary
01/03/2012 Letter Inspection Summary
01/26/2012 Letter Fire (Alarm) Plan Review Notice
02/07/2012 Letter Inspection Summary
02/07/2012 Letter Inspection Summary
02/22/2012 Letter Inspection Summary
02/29/2012 Letter Inspection Summary
02/29/2012 Letter Inspection Summary
03/02/2012 Letter Inspection Summary
03/05/2012 Letter 20120305113220184.pdf
03/15/2012 Letter Fire (Alarm) Plan Review Notice
03/15/2012 Letter Fire (Alarm) Plan Review Notice
03/27/2012 Letter Inspection Summary
03/30/2012 Letter Inspection Summary
04/04/2012 Letter Inspection Summary
04/19/2012 Letter Fire Loss Reduction Form
05/30/2012 Letter Inspection Summary
05/31/2012 Letter Inspection Summary
06/11/2012 Letter Inspection Summary
06/19/2012 Letter Inspection Summary
06/26/2012 Letter Fire Loss Reduction Form
06/26/2012 Letter Temporary Certificate of Occupancy
07/02/2012 Letter Inspection Summary
07/12/2012 Letter Field Certificate of Occupancy
07/13/2012 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents