Summary
PRCOM20115254
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
NEW OTHER
ELECTRICAL AND LIGHT POLE BASES FOR EAST PARKING LOT
09/22/2011
09/22/2011
05/07/2013
Locations
Contacts
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/22/2011
Mike Weisenborn
Building Plan Review Approved 10/06/2011 09/22/2011
Mike Weisenborn
Final Development Plan Review Approved 10/06/2011 09/22/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $219.99 $219.99 Paid 09/22/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 9/22/2011 9/22/2011 at 12:00 AM 09/22/2011
Misc
Partial Correction
09/22/2011
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6;
Misc
Partial Correction
09/22/2011
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6;
Underground Electrical Inspection - Commercial Partial 9/23/2011 (8:00 to 5:00) 9/23/2011 at 12:00 AM 09/23/2011
Misc
Partial Correction
09/22/2011
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9;
Misc
Partial Correction
09/22/2011
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6;
Underground Electrical Inspection - Commercial Partial 9/27/2011 at 12:00 AM 09/27/2011
Misc
Partial Correction
09/23/2011
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9; FROM #6 TO #7, THEN 35' NORTH; FROM #7 W TO BUS STOP, THEN 40' NW TO CURB
Misc
Partial Correction
09/23/2011
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6;
Underground Electrical Inspection - Commercial Not Ready 9/30/2011 9/30/2011 at 12:00 AM 09/30/2011
Misc
Partial Correction
09/27/2011
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9; FROM #6 TO #7, THEN 35' NORTH; FROM #7 W TO BUS STOP, THEN 40' NW TO CURB
Misc
Partial Correction
09/27/2011
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6;
Underground Electrical Inspection - Commercial Partial 9/30/2011 at 12:00 AM 09/30/2011
Misc
Partial Correction
09/30/2011
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9; FROM #6 TO #7, THEN 35' NORTH; FROM #7 W TO BUS STOP, THEN 40' NW TO CURB
Misc
Partial Correction
09/30/2011
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6; #2; #4; 5; #7;
Final Electrical Inspection - Commercial Failed 11/18/2011 11/18/2011 at 12:00 AM 11/18/2011
Misc
Corrective Action Required
11/18/2011
6-PARKING LIGHT POLES- INSPECTED 6 POLE LIGHT- 2 REMAIN ON PERMIT TO BE COMPLETED IN SPRING 2012
Final Electrical Inspection - Commercial Partial 4/6/2012 at 12:00 AM 04/06/2012
Misc
Partial Correction
04/06/2012
6-PARKING LIGHT POLES- INSPECTED 6 POLE LIGHT- 2 REMAIN ON PERMIT TO BE COMPLETED IN SPRING 2012
Underground Electrical Inspection - Commercial Partial 9/12/2012 9/12/2012 at 12:00 AM 09/12/2012
Misc
Partial Correction
09/30/2011
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9; FROM #6 TO #7, THEN 35' NORTH; FROM #7 W TO BUS STOP, THEN 40' NW TO CURB; FROM EXTENSION FROM PHASE 1 TO LOCATION OF PHASE 2 POLE 2;
Misc
Partial Correction
09/30/2011
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6; #2; #4; 5; #7;
Underground Electrical Inspection - Commercial Partial 9/13/2012 9/13/2012 at 12:00 AM 09/13/2012
Misc
Partial Correction
09/12/2012
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9; FROM #6 TO #7, THEN 35' NORTH; FROM #7 W TO BUS STOP, THEN 40' NW TO CURB; PHASE 2 LINE CURRENT BURIED CONDUIT OK TO COVER WHEN READY
Misc
Partial Correction
09/12/2012
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6; #2; #4; 5; #7;
Underground Electrical Inspection - Commercial Passed 9/17/2012 9/17/2012 at 12:00 AM 09/17/2012
Misc
Resolved
09/17/2012
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM LP BASE #1 TO #2 TO #3 TO #4 TO #5 TO #6; FROM #6 TO 15' NORTH; FROM #6 WEST TO SOURCE @ EXISTING L.P. #10; FROM #6 TO #9; FROM #6 TO #7, THEN 35' NORTH; FROM #7 W TO BUS STOP, THEN 40' NW TO CURB; PHASE 2 LINE CURRENT BURIED CONDUIT OK TO COVER WHEN READY
Misc
Resolved
09/17/2012
OK TO POUR WHEN READY CONCRETE LIGHT POLE BASE(S) AT FOLLOWING LOCATIONS: #3; #6; #2; #4; 5; #7; #1; #8; #9
Final Electrical Inspection - Commercial Partial 10/19/2012 at 12:00 AM 10/19/2012
Misc
Partial Correction
04/06/2012
8 PARKING LOT LIGHT POLES COMPLETED
Final Electrical Inspection - Commercial Partial 10/22/2012 at 12:00 AM 10/22/2012
Misc
Partial Correction
10/19/2012
PARKING LIGHTING PHASE 1 COMPLETED & APPROVED. PHASE 2 SUBSTANTIALLY COMPLETED; SUBJECT TO P&D APPROVAL;
Final Electrical Inspection - Commercial Partial 10/24/2012 at 12:00 AM 10/24/2012
Misc
Partial Correction
10/22/2012
PARKING LIGHTING PHASE 1 COMPLETED & APPROVED. PHASE 2 SUBSTANTIALLY COMPLETED; SUBJECT TO P&D APPROVAL. ROCKHILL PHASE IN PROGRESS 10/24/12
Underground Electrical Inspection - Commercial Partial 10/26/2012 10/26/2012 at 12:00 AM 10/26/2012
Misc
Partial Correction
10/26/2012
OK TO COVER WHEN READY BURIED CONDUIT AT ROCKHILL SECTION PARKING LOT
Underground Electrical Inspection - Commercial Passed 10/30/2012 10/30/2012 at 12:00 AM 10/30/2012
Misc
Resolved
10/30/2012
ROCKHILL SECTION PARKING LOT: OK TO COVER WHEN READY BURIED CONDUIT. OK TO POUR WHEN READY TWO LIGHT POLE BASES.
Final Electrical Inspection - Commercial Partial 11/9/2012 at 12:00 AM 11/09/2012
Misc
Partial Correction
10/24/2012
PARKING LIGHTING PHASE 1 COMPLETED & APPROVED. PHASE 2 SUBSTANTIALLY COMPLETED; SUBJECT TO P&D APPROVAL. ROCKHILL PHASE ELECTRICAL WORK SUBSTANTIALLY COMPLETED; LANDSCAPING SUBJECT TO P&D APPROVAL
Final Electrical Inspection - Commercial Passed 5/7/2013 at 12:00 AM 05/07/2013
Misc
Resolved
05/07/2013
PARKING LIGHTING PHASE 1 COMPLETED & APPROVED. PHASE 2 SUBSTANTIALLY COMPLETED; SUBJECT TO P&D APPROVAL. ROCKHILL PHASE ELECTRICAL WORK SUBSTANTIALLY COMPLETED; LANDSCAPING SUBJECT TO P&D APPROVAL
Documents & Images
Date Uploaded File Type Document Name
09/22/2011 Letter Building Permit
09/22/2011 Letter Inspection Summary
09/22/2011 Letter Inspection Summary
09/23/2011 Letter Inspection Summary
09/27/2011 Letter Inspection Summary
09/30/2011 Letter Inspection Summary
11/18/2011 Letter Inspection Summary
04/06/2012 Letter Inspection Summary
09/12/2012 Letter Inspection Summary
09/13/2012 Letter Inspection Summary
09/17/2012 Letter Inspection Summary
10/24/2012 Letter Inspection Summary
10/26/2012 Letter Inspection Summary
10/30/2012 Letter Inspection Summary
11/09/2012 Letter Inspection Summary
05/07/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home