Permit Application Status

PRCOM20114000


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20114000
Building Permit - Commercial
Final Completion
CBL LEES SUMMIT EAST LLC
ALTERATION COMMERCIAL
WHITE BOX INCLUDING SINGLE RESTROOM AND SUSPENDED CEILING
07/22/2011
08/19/2011
10/17/2011
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
CAMM CONSTRUCTION INC, Address:PO BOX 1417, Phone:(816) 607-3602  
ACCURATE MECHANICAL LLC, Address:205 E 13TH AVE, Phone:(816) 471-2272  
CATES ELECTRIC LLC, Address:4568 MEADOW LANE, Phone:(913) 915-2953  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/05/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/05/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received October 3, 2011.
Installation acceptance testing
Corrective Action Required
10/05/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test. Tests are to be completed before or after regular business hours.
Misc
Corrective Action Required
10/05/2011

Duct detectors shall send be supervisory alarms only and shall NOT activate the interior horn/strobes. Verified at inspection.
Sprinkler Plan Review Released for Construction 09/13/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
09/13/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received for 910 NW Blue Parkway, Suite R on Sept. 2, 2011.
Installation acceptance testing
Corrective Action Required
09/13/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Misc
Corrective Action Required
09/13/2011

For information only- Plan design shall be to the 2002 edition of NFPA 13 and the 2003 edition of the IBC.
Misc
Corrective Action Required
09/13/2011

Sprinkler head model to be confirmed at inspection.
Internal Plan Review (Res) Approved 08/03/2011 08/02/2011
Mike Weisenborn
Building Plan Review Approved 08/03/2011 08/02/2011
Mike Weisenborn
Tenant Finish Plans Required
Corrective Action Required
08/02/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
License Tax Codes Approved 08/03/2011 08/02/2011
Mike Weisenborn
Fire Plan Review Approved 08/03/2011 07/29/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/29/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for sprinkler and alarm system modification.
Address numbers required
Corrective Action Required
07/29/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Historical Preservation Review Approved 08/03/2011 07/25/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $247.43 $247.43 Paid 08/19/2011
8331507-Sewer Connection Fee $90.00 $90.00 Paid 08/19/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 8/29/2011 (8:00 to 5:00) 8/29/2011 at 12:00 AM 08/29/2011
In-wall Inspection Partial 9/6/2011 at 12:00 AM 09/06/2011
Misc
Partial Correction
10/14/2011
OK TO COVER WHEN READY WALL FRAMNG AND IN-WALL SYSTEMS AT: NORTH, EAST, SOUTH DEMISING WALLS; RESTROOM 102;
Gas Piping Inspection - Commercial Failed 9/20/2011 at 12:00 AM 09/20/2011
Misc
Corrective Action Required
09/20/2011
PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS: ATTACH APPROVED SLIP SHEETS TO BOTTOM OF BLOCKS, SECURING SHEETS TO SIDES OF BLOCKS
Misc
Corrective Action Required
09/20/2011
IFGC 407 / 415: ROOFTOP STEEL GAS PIPING SUPPORT SPACING INTERVAL: MAXIMUM 8' FOR 3/4" OR 1"; 10' FOR 1-1/4" OR LARGER
Misc
Corrective Action Required
09/20/2011
IFGC 404.8: EXTERIOR EXPOSED GAS PIPING MUST BE PAINTED OR OTHERWISE PROTECTED FROM CORROSION.
Gas Service Inspection - Commercial Passed 9/20/2011 at 12:00 AM 09/20/2011
Above Ceiling Inspection Partial 9/23/2011 (8:00 to 5:00) 09/23/2011
Misc
Corrective Action Required
09/23/2011
EXPANSION TANK NOT FOUND AT WATER HEATER
Misc
Partial Correction
09/23/2011
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WATER HEATER
Above Ceiling Inspection Partial 9/23/2011 at 12:00 AM 09/23/2011
Misc
Corrective Action Required
09/23/2011
EXPANSION TANK NOT FOUND AT WATER HEATER
Misc
Partial Correction
09/23/2011
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WATER HEATER AND AT TRUSS JOIST BOTTOM CHORD BRACES
Misc
Corrective Action Required
09/23/2011
TRUSS JOIST BOTTOM CHORD BRACES MUST BE WELDED TO BAR JOISTS
Electrical Service Inspection Passed 9/27/2011 at 12:00 AM 09/27/2011
Above Ceiling Inspection Partial 9/27/2011 at 12:00 AM 09/27/2011
Misc
Resolved
09/27/2011
EXPANSION TANK NOT FOUND AT WATER HEATER
Misc
Partial Correction
09/23/2011
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WATER HEATER AND AT TRUSS JOIST BOTTOM CHORD BRACES
Misc
Corrective Action Required
09/23/2011
TRUSS JOIST BOTTOM CHORD BRACES MUST BE WELDED TO BAR JOISTS
Electrical Service Inspection Passed 10/5/2011 at 12:00 AM 10/05/2011
Above Ceiling Inspection Passed 10/5/2011 at 12:00 AM 10/05/2011
Misc
Resolved
10/05/2011
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WATER HEATER AND AT TRUSS JOIST BOTTOM CHORD BRACES
Misc
Resolved
10/05/2011
TRUSS JOIST BOTTOM CHORD BRACES MUST BE WELDED TO BAR JOISTS
In-wall Inspection Passed 10/14/2011 at 12:00 AM 10/14/2011
Misc
Resolved
10/14/2011
OK TO COVER WHEN READY WALL FRAMNG AND IN-WALL SYSTEMS AT: NORTH, EAST, SOUTH DEMISING WALLS; RESTROOM 102;
Occupancy Inspection - Fire Passed 10/14/2011 at 12:00 AM 10/14/2011
Gas Piping Inspection - Commercial Passed 10/14/2011 at 12:00 AM 10/14/2011
Misc
Resolved
10/14/2011
PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS: ATTACH APPROVED SLIP SHEETS TO BOTTOM OF BLOCKS, SECURING SHEETS TO SIDES OF BLOCKS
Misc
Resolved
10/14/2011
IFGC 407 / 415: ROOFTOP STEEL GAS PIPING SUPPORT SPACING INTERVAL: MAXIMUM 8' FOR 3/4" OR 1"; 10' FOR 1-1/4" OR LARGER
Misc
Resolved
10/14/2011
IFGC 404.8: EXTERIOR EXPOSED GAS PIPING MUST BE PAINTED OR OTHERWISE PROTECTED FROM CORROSION.
Final Inspection - Commercial Passed 10/14/2011 10/14/2011 at 12:00 AM 10/14/2011
Alarm Test Passed 10/14/2011 at 12:00 AM 10/14/2011
Documents & Images
Date Uploaded File Type Document Name
08/19/2011 Letter Building Permit
08/19/2011 Letter Plan Review Conditions
08/29/2011 Letter Inspection Summary
09/06/2011 Letter Inspection Summary
09/13/2011 Letter Fire (Sprinkler) Plan Review
09/20/2011 Letter Inspection Summary
09/23/2011 Letter Inspection Summary
09/23/2011 Letter Inspection Summary
09/27/2011 Letter Inspection Summary
10/05/2011 Letter Inspection Summary
10/05/2011 Letter Inspection Summary
10/05/2011 Letter Inspection Summary
10/05/2011 Letter Fire (Alarm) Plan Review Notice
10/14/2011 Letter Inspection Summary
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home