Permit Application Status

PRCOM20113619


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20113619
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR CLOTHES RETAIL
07/07/2011
08/03/2011
10/14/2014
09/28/2011
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
BURDG DUNHAM & ASSOC , Address:920 S HUGHES, Phone:(816) 583-2123  
DMR SERVICES INC, Address:27215 S LEWIS RD, Phone:(816) 899-2159  
LBA AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6850 W 47TH TER, Phone:(913) 268-6822  
TAYLOR MECHANICAL INC, Address:23700 E 189th st, Phone:(816) 743-9900  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/22/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/22/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans recieved August 19, 2011.
Misc
Corrective Action Required
08/22/2011

Duct detection shall be connected to the alarm system and received and handled as supervisory alarms only without activation of interior horn/strobes. Verified at inspection.
Installation acceptance testing
Corrective Action Required
08/22/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (8160 969-1300 to schedule an alarm test. Tests shall be completed before or after regular business hours of the neighboring tenants.
Sprinkler Plan Review Released for Construction 08/12/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
08/12/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received August 8, 2011.
Installation acceptance testing
Corrective Action Required
08/12/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/12/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: The existing system shall have documentation of a current annual inspection.
Misc
Corrective Action Required
08/12/2011

IFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required: Fire sprinkler controls shall be clearly marked and accessible.
Internal Plan Review (Res) Approved 07/29/2011 07/29/2011
Mike Weisenborn
License Tax Codes Approved 07/29/2011 07/29/2011
Mike Weisenborn
Building Plan Review Approved 07/29/2011 07/29/2011
Mike Weisenborn
Misc
Resolved
07/29/2011

The unit number provided for this space on the application is Unit D. From the plans it appears that there will be an available space between this space and the existing tenant to the north with is Unit E. By addressing this as Unit D a unit disignation will not be avialable for the vacant space. Action required - Provide additional information.
Plumb - Separate facilities
Resolved
07/29/2011

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Label the restrooms on the plans.
Plumb - Required public toilet facilities
Corrective Action Required
07/22/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Accessibility - Water closet - Grab bars
Resolved
07/29/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The required vertical grab bar is not shown. Make needed corrections.
Misc
Resolved
07/29/2011

ICC/ANSI A117.1-2003 -903.3 Clear floor space. A clear floor space complying with Section 305, position for parallel approach to an end of the bench seat, shall be provided. Action required - This section requires a 30 inch wide space at the end of the bench for a side transfer to the bench. It appears that only a 24 inch space is being provided. Make needed corrections.
Bldg - Glazing - Human impact loads
Resolved
07/29/2011

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Indicate locations of required safety glazing.
Bldg - Doors - Size of doors
Resolved
07/29/2011

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The standard fitting room doors do not meet the minimum width requriement. Make needed corrections.
Misc
Resolved
07/29/2011

The plans indicate hanging bars in the rear egress corridor. The detail shows them to be mounted at 12 feet above finished floor. Action required - Provide information on how the bars are to be used. Verify that their use will not obstruct the egress path or line of site on the exit signage.
Bldg - Means of egress illumination - Emergency power
Resolved
07/29/2011

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - Verify that the required exterior emergency lighting is existing or make needed corrections.
Misc
Corrective Action Required
07/22/2011

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes.
Bldg - Toilet rooms - Walls
Resolved
07/29/2011

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Provide additional information on where the frp is to be installed.
Bldg - Toilet rooms - Floor surface and walls
Resolved
07/29/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - If the frp is not installed on all the walls in the restroom, 6 inch must be installed. Provide additional information.
Fire Plan Review Approved 07/29/2011 07/27/2011
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
07/27/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Construction documents for fire alarm systems
Corrective Action Required
07/27/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for review and approval.
Misc
Corrective Action Required
07/27/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Provide exterior emergency lighting. RESOLVED ON RESUB ADDITIONAL ACTION REQUIRED: PROVIDE EMERGENCY LIGHTING IN STOREROOM, VERIFIED AT INSPECTION
Portable fire extinguishers - general
Corrective Action Required
07/27/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of 2, 2A:10B:C fire extinguishers in conspicuous locations and in a normal path of travel. Verified at inspection.
Misc
Corrective Action Required
07/27/2011

Duct Detection- Duct detectors shall be connected to the building alarm system and give a supervisory signal only without activation of interior horn/strobes. RESOLVED ON RESUB
Address numbers required
Corrective Action Required
07/27/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE ADDRESSING ON ALL EXTERIOR DOOS LEADING INTO THE SPACE, VERIFIED AT INSPECTION
Internal Plan Review (Res) Rejected 07/19/2011 07/19/2011
Mike Weisenborn
Fire Plan Review Rejected 07/19/2011 07/18/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/18/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Construction documents for fire alarm systems
Corrective Action Required
07/18/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for review and approval.
Misc
Corrective Action Required
07/18/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Provide exterior emergency lighting.
Portable fire extinguishers - general
Corrective Action Required
07/18/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of 2, 2A:10B:C fire extinguishers in conspicuous locations and in a normal path of travel. Verified at inspection.
Misc
Corrective Action Required
07/18/2011

Duct Detection- Duct detectors shall be connected to the building alarm system and give a supervisory signal only without activation of interior horn/strobes.
Building Plan Review Rejected 07/19/2011 07/11/2011
Mike Weisenborn
Misc
Corrective Action Required
07/11/2011

The unit number provided for this space on the application is Unit D. From the plans it appears that there will be an available space between this space and the existing tenant to the north with is Unit E. By addressing this as Unit D a unit disignation will not be avialable for the vacant space. Action required - Provide additional information.
Plumb - Separate facilities
Corrective Action Required
07/11/2011

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Label the restrooms on the plans.
Plumb - Required public toilet facilities
Corrective Action Required
07/11/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - This comment is for information purposes.
Accessibility - Water closet - Grab bars
Corrective Action Required
07/11/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The required vertical grab bar is not shown. Make needed corrections.
Misc
Corrective Action Required
07/11/2011

ICC/ANSI A117.1-2003 -903.3 Clear floor space. A clear floor space complying with Section 305, position for parallel approach to an end of the bench seat, shall be provided. Action required - This section requires a 30 inch wide space at the end of the bench for a side transfer to the bench. It appears that only a 24 inch space is being provided. Make needed corrections.
Bldg - Glazing - Human impact loads
Corrective Action Required
07/11/2011

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Indicate locations of required safety glazing.
Bldg - Doors - Size of doors
Corrective Action Required
07/11/2011

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - The standard fitting room doors do not meet the minimum width requriement. Make needed corrections.
Misc
Corrective Action Required
07/11/2011

The plans indicate hanging bars in the rear egress corridor. The detail shows them to be mounted at 12 feet above finished floor. Action required - Provide information on how the bars are to be used. Verify that their use will not obstruct the egress path or line of site on the exit signage.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
07/11/2011

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - Verify that the required exterior emergency lighting is existing or make needed corrections.
Misc
Corrective Action Required
07/11/2011

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes.
Bldg - Toilet rooms - Walls
Corrective Action Required
07/11/2011

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Provide additional information on where the frp is to be installed.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
07/11/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - If the frp is not installed on all the walls in the restroom, 6 inch must be installed. Provide additional information.
Zoning Review Approved 07/19/2011 07/07/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $835.24 $835.24 Paid 08/03/2011
8331507-Sewer Connection Fee $150.00 $150.00 Paid 08/03/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 8/9/2011 8/9/2011 at 12:00 AM 08/09/2011
In-wall Inspection Partial 8/9/2011 at 12:00 AM 08/09/2011
Misc
Partial Correction
08/09/2011
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT: NORTH & SOUTH DEMISING WALLS; WEST EXTERIOR WALL EXCEPT AT WIRING TO BE INSTALLED FOR EXIT SIGN;
Miscellaneous Inspection Partial 8/19/2011 at 12:00 AM 08/19/2011
Misc
Partial Correction
08/19/2011
RESPONDED TO G.C. QUESTION RE DRAWING NOTE ABOUT "BOTTOM BRACING @ RTU'S: PERTAINS TO TRUSS JOIST BOTTOM CHORD BRACING
Misc
Partial Correction
08/19/2011
PROVIDED G.C. W/ NAME AND PH# OF KCP&L SERVICE PLANNER
In-wall Inspection Partial 8/23/2011 8/23/2011 at 12:00 AM 08/23/2011
Misc
Partial Correction
08/09/2011
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT: ALL WALLS EXCEPT EAST EXTERIOR AND WET WALL BETWEEN RESTROOMS
Misc
Corrective Action Required
08/23/2011
IPC 305.8: INSTALL HARDENED STEEL SHIELD PLATES AT STUDS AND T&B PLATES WHEREVER SURFACE OF PIPE IS LESS THAN 1-1/2" FROM FACE OF FRAMING. SHIELD PLATES SHALL COVER THE AREA OF THE PIPE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND A MINIMUM OF 2" ABOVE SOLE PLATES & BELOW TOP PLATES. CHECK ALL.
Electrical Service Inspection Passed 8/25/2011 at 12:00 AM 08/25/2011
Gas Piping Inspection - Commercial Partial 8/31/2011 at 12:00 AM 08/31/2011
Misc
Corrective Action Required
08/31/2011
EXPOSED PIPING TO BE PAINTED PRIOR TO FINAL INSPECTION
Gas Service Inspection - Commercial Not Ready 8/31/2011 at 12:00 AM 08/31/2011
Misc
Corrective Action Required
08/31/2011
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED HANG ADDRESS-STAMPED MEDALLIONS ON LOAD SIDE PIPES
Misc
Corrective Action Required
08/31/2011
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM
Rough Framing Inspection - Commercial Partial 9/8/2011 at 12:00 AM 09/08/2011
Misc
Partial Correction
09/08/2011
OK TO COVER WHEN READY FRAMING OF PILASTER @ NE CORNER PER NOTE "6"
Miscellaneous Inspection Passed 9/8/2011 at 12:00 AM 09/08/2011
Misc
Resolved
09/08/2011
RESPONDED TO G.C. QUESTION RE DRAWING NOTE ABOUT "BOTTOM BRACING @ RTU'S: PERTAINS TO TRUSS JOIST BOTTOM CHORD BRACING
Misc
Resolved
09/08/2011
PROVIDED G.C. W/ NAME AND PH# OF KCP&L SERVICE PLANNER
Gas Piping Inspection - Commercial Passed 9/8/2011 at 12:00 AM 09/08/2011
Misc
Resolved
09/08/2011
EXPOSED PIPING TO BE PAINTED PRIOR TO FINAL INSPECTION
Gas Service Inspection - Commercial Passed 9/8/2011 at 12:00 AM 09/08/2011
Misc
Resolved
09/08/2011
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED HANG ADDRESS-STAMPED MEDALLIONS ON LOAD SIDE PIPES
Misc
Resolved
09/08/2011
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM
In-wall Inspection Partial 9/8/2011 at 12:00 AM 09/08/2011
Misc
Resolved
09/08/2011
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT: ALL WALLS EXCEPT EAST EXTERIOR AND WET WALL BETWEEN RESTROOMS
Misc
Resolved
09/08/2011
IPC 305.8: INSTALL HARDENED STEEL SHIELD PLATES AT STUDS AND T&B PLATES WHEREVER SURFACE OF PIPE IS LESS THAN 1-1/2" FROM FACE OF FRAMING. SHIELD PLATES SHALL COVER THE AREA OF THE PIPE WHERE THE MEMBER IS NOTCHED OR BORED AND SHALL EXTEND A MINIMUM OF 2" ABOVE SOLE PLATES & BELOW TOP PLATES. CHECK ALL.
Misc
Partial Correction
09/08/2011
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT TYPE "B" WALL AT: 19' WALL @ SE CORNER;
In-wall Inspection Partial 9/9/2011 at 12:00 AM 09/09/2011
Misc
Partial Correction
09/08/2011
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT TYPE "B" WALL AT: 19' WALL @ SE CORNER; WALL @ NE CORNER
Above Ceiling Inspection Partial 09/21/2011
Misc
Corrective Action Required
09/21/2011
ENSURE ALL HVAC DUCT INSULATION JOINTS ARE TAPED
Misc
Corrective Action Required
09/21/2011
SPRINKLER FIRE PROTECTION PIPING: SUPPORT DROP PIPING AT/NEAR CHANGES OF DIRECTION TO PREVENT STRESS TO FITTINGS. DO NOT HANG FROM JOIST TOP CHORD BRIDGING.
Misc
Corrective Action Required
09/21/2011
OK TO PLACE ACT BORDERS LESS THAN OR EQUAL TO 2' FROM WALLS
Above Ceiling Inspection Passed 9/22/2011 at 12:00 AM 09/22/2011
Misc
Resolved
09/22/2011
ENSURE ALL HVAC DUCT INSULATION JOINTS ARE TAPED
Misc
Resolved
09/22/2011
SPRINKLER FIRE PROTECTION PIPING: SUPPORT DROP PIPING AT/NEAR CHANGES OF DIRECTION TO PREVENT STRESS TO FITTINGS. DO NOT HANG FROM JOIST TOP CHORD BRIDGING.
Misc
Resolved
09/22/2011
OK TO PLACE ACT BORDERS LESS THAN OR EQUAL TO 2' FROM WALLS
Alarm Test Passed 9/22/2011 at 12:00 AM 09/22/2011
Sprinkler - Flow Test Passed 9/22/2011 at 12:00 AM 09/22/2011
Occupancy Inspection - Codes Commercial Temporary C of O 9/27/2011 9/27/2011 at 12:00 AM 09/27/2011
Misc
Corrective Action Required
09/27/2011
DESIGNATE RTU'S #1 AND #2
Misc
Corrective Action Required
09/27/2011
COMPLETE ROOF CLEAN-UP IN UNIT FOOTPRINT
Occupancy Inspection - Fire Passed 9/27/2011 at 12:00 AM 09/27/2011
Misc
Corrective Action Required
09/27/2011
880-D appeared OK at the time of the inspection. It is OK with FD to occupy once cleared through codes administration
In-wall Inspection Passed 9/27/2011 at 12:00 AM 09/27/2011
Misc
Resolved
09/27/2011
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT TYPE "B" WALL AT: 19' WALL @ SE CORNER; WALL @ NE CORNER
Rough Framing Inspection - Commercial Passed 9/27/2011 at 12:00 AM 09/27/2011
Misc
Resolved
09/27/2011
OK TO COVER WHEN READY FRAMING OF PILASTER @ NE CORNER PER NOTE "6"
Occupancy Inspection - Codes Commercial Full C of O 9/28/2011 at 12:00 AM 09/28/2011
Misc
Resolved
09/28/2011
DESIGNATE RTU'S #1 AND #2
Misc
Resolved
09/28/2011
COMPLETE ROOF CLEAN-UP IN UNIT FOOTPRINT
Documents & Images
Date Uploaded File Type Document Name
07/19/2011 Letter Plan Review Conditions
08/03/2011 Letter Plan Review Conditions
08/03/2011 Letter Building Permit
08/09/2011 Letter Inspection Summary
08/12/2011 Letter Fire (Sprinkler) Plan Review
08/23/2011 Letter Inspection Summary
08/25/2011 Letter Inspection Summary
08/31/2011 Letter Inspection Summary
09/08/2011 Letter Inspection Summary
09/09/2011 Letter Inspection Summary
09/21/2011 Letter Inspection Summary
09/22/2011 Letter Inspection Summary
09/27/2011 Letter Temporary Certificate of Occupancy
09/27/2011 Letter Fire Loss Reduction Form
09/28/2011 Letter Field Certificate of Occupancy
09/29/2011 Letter Final Certificate of Occupancy
06/26/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home