Permit Application Status

PRCOM20112117


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20112117
Building Permit - Commercial
Final Completion
CBL LEES SUMMIT EAST LLC
ALTERATION COMMERCIAL
DEMISING WALLS AND COMMON CORRIDOR
05/25/2011
06/08/2011
07/20/2011
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
CAMM CONSTRUCTION INC, Address:PO BOX 1417, Phone:(816) 607-3602  
CATES ELECTRIC LLC, Address:4568 MEADOW LANE, Phone:(913) 915-2953  
STEVE THE PLUMBER INC, Address:601 S STELLA, Phone:(913) 226-6140  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 07/05/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/05/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans recieved June 22, 2011.
Misc
Corrective Action Required
07/05/2011

Duct detection alarms shall be supervisory only without activating the interior alarm notification appliances. Verified at inspection.
Installation acceptance testing
Corrective Action Required
07/05/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule an alarm test.
Internal Plan Review (Res) Approved 06/07/2011 06/08/2011
Mike Weisenborn
Fire Plan Review Approved 06/07/2011 06/07/2011
Jim Eden
Misc
Corrective Action Required
06/07/2011

The corridor shall be posted "NO STORAGE ALLOWED". Verified at inspection
Misc
Corrective Action Required
06/07/2011

For Information Only- 1005.2 Door encroachment. Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 7 inches (178 mm) into the required width. The current layout and door width would prohibit the corridor south of the door from being used as a possible means of egress from the tenant space to the south.
Construction documents - Fire protection systems
Corrective Action Required
06/07/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
06/07/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Address numbers required
Corrective Action Required
06/07/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection. Since the building has two corridors, list on the exterior door the letter designations accessed by the corridor.
Building Plan Review Approved 06/07/2011 06/06/2011
Mike Weisenborn
Historical Preservation Review Approved 06/07/2011 06/06/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 06/08/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 6/9/2011 (8:00 to 5:00) 6/9/2011 at 12:00 AM 06/09/2011
Rated Assembly Inspection Not Ready 6/9/2011 (8:00 to 5:00) 6/9/2011 at 12:00 AM 06/09/2011
Misc
Corrective Action Required
06/09/2011
NO RATED ASSEMBLY FOUND READY FOR INSPECTION
Rated Assembly Inspection Not Ready 6/10/2011 at 12:00 AM 06/10/2011
Misc
Corrective Action Required
06/09/2011
NO RATED ASSEMBLY FOUND READY FOR INSPECTION
Rated Assembly Inspection Partial 6/14/2011 6/14/2011 at 12:00 AM 06/14/2011
Misc
Resolved
06/14/2011
NO RATED ASSEMBLY FOUND READY FOR INSPECTION
Misc
Partial Correction
06/14/2011
OK TO MUD, TAPE, AND FIRE-SEAL (PER DRAWING) 5/8" TYPE X GWB AT EAST WALL WEST FACE
All Rough Inspection - Commercial Failed 6/22/2011 at 12:00 AM 06/22/2011
Misc
Corrective Action Required
06/22/2011
CORRIDOR WALL NOT OK TO CLOSE. SEE RATED ASSEMBLY.
Rated Assembly Inspection Not Ready 6/22/2011 at 12:00 AM 06/22/2011
Misc
Partial Correction
06/14/2011
OK TO MUD, TAPE, AND FIRE-SEAL (PER DRAWING) 5/8" TYPE X GWB AT EAST WALL WEST FACE
Misc
Corrective Action Required
06/22/2011
4" MINERAL WOOL FIRE-SEAL NOT FOUND IN PLACE PER DRAWING DETAIL (6) AT EAST WALL EAST FACE
Rated Assembly Inspection Passed 6/24/2011 6/24/2011 at 12:00 AM 06/24/2011
Misc
Resolved
06/24/2011
OK TO MUD, TAPE, AND FIRE-SEAL (PER DRAWING) 5/8" TYPE X GWB AT EAST WALL WEST FACE
Misc
Resolved
06/24/2011
4" MINERAL WOOL FIRE-SEAL NOT FOUND IN PLACE PER DRAWING DETAIL (6) AT EAST WALL EAST FACE
Alarm Test Passed 7/12/2011 at 12:00 AM 07/13/2011
Sprinkler - Flow Test Passed 07/13/2011
Occupancy Inspection - Fire Passed 7/13/2011 at 12:00 AM 07/13/2011
All Rough Inspection - Commercial Passed 7/13/2011 at 12:00 AM 07/13/2011
Misc
Resolved
07/13/2011
CORRIDOR WALL NOT OK TO CLOSE. SEE RATED ASSEMBLY.
Final Inspection - Commercial Passed 7/13/2011 7/13/2011 at 12:00 AM 07/13/2011
Documents & Images
Date Uploaded File Type Document Name
06/08/2011 Letter Building Permit
06/08/2011 Letter Plan Review Conditions
06/09/2011 Letter Inspection Summary
06/14/2011 Letter Inspection Summary
06/22/2011 Letter Inspection Summary
06/24/2011 Letter Inspection Summary
07/05/2011 Letter Fire (Alarm) Plan Review Notice
07/13/2011 Letter Fire Loss Reduction Form
07/13/2011 Letter Inspection Summary
07/05/2013 Letter Final Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home