Permit Application Status

PRCOM20111175


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20111175
Building Permit - Commercial
Certificate of Occupancy
SUMMIT NORTHRIDGE LLC
NEW TENANT FINISH
SET OCCUPANCY FOR RETAIL STORE. CONSTRUCTION OF THE SPACE WAS COMPLETED ON THE SHELL PERMIT
05/03/2011
05/12/2011
06/06/2011
Locations
Contacts
SUMMIT NORTHRIDGE LLC, Address:605 W 47TH ST STE 200  
SLEEPONE INC, Address:9900 PFLUMM #51, Phone:(816) 525-7001  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/11/2011
Mike Weisenborn
Fire Plan Review Approved 05/13/2011 05/11/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
05/11/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit a layout of alarm notification appliances.
Installation acceptance testing
Corrective Action Required
05/11/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm testing.
Portable fire extinguishers - general
Corrective Action Required
05/11/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two, 2A:10B:C fire extinguishers. Verified at inspection.
Misc
Corrective Action Required
05/11/2011

Exit and emergency lighting shall be provided if not already part of the shell building. Verified at inspection.
Address numbers required
Corrective Action Required
05/11/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Historical Preservation Review Approved 05/13/2011 05/10/2011
Mike Weisenborn
License Tax Codes Approved 05/13/2011 05/10/2011
Mike Weisenborn
Building Plan Review Approved 05/13/2011 05/10/2011
Mike Weisenborn
Planning - Signs
Corrective Action Required
05/10/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirements. Action required - This comment is for information purposes only.
Misc
Corrective Action Required
05/10/2011

This permit is to set the occupancy only. It does not include any plumbing, electrical, mechanical or construction work. Action required - This comment is for information purposes.
Sprinkler Plan Review Released for Construction 05/05/2011
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
05/05/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received on 4/25/2011, relesed for construction as shown on plans
Misc
Corrective Action Required
05/05/2011

Use of the space not shown, Ordinary Hazard II for general mercantile only
Installation acceptance testing
Corrective Action Required
05/05/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call 969-1300 to schedule acceptance testing prior to final
Zoning Review Approved 05/13/2011 05/03/2011
Hector Soto Jr.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Tenent Finish $32.97 $32.97 Paid 05/12/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Hydrostatic Test Passed 4/7/2011 at 12:00 AM 05/20/2011
Sprinkler - Flow Test Passed 4/7/2011 at 12:00 AM 05/20/2011
Alarm Test Passed 4/7/2011 at 12:00 AM 05/20/2011
Occupancy Inspection - Codes Commercial Temporary C of O 5/20/2011 at 12:00 AM 05/20/2011
Misc
Corrective Action Required
05/20/2011
RESOLUTION OF SHELL PERMIT ISSUES IN PROGRESS
Occupancy Inspection - Fire Passed 5/20/2011 at 12:00 AM 05/20/2011
Occupancy Inspection - Codes Commercial Partial 5/23/2011 at 12:00 AM 05/23/2011
Misc
Corrective Action Required
05/20/2011
RESOLUTION OF SHELL PERMIT ISSUES IN PROGRESS
Occupancy Inspection - Codes Commercial Partial 6/2/2011 at 12:00 AM 06/02/2011
Misc
Corrective Action Required
05/23/2011
RESOLUTION OF SHELL PERMIT ISSUES NOT COMPLETED/APPROVED.
Occupancy Inspection - Codes Commercial Full C of O 6/6/2011 at 12:00 AM 06/06/2011
Misc
Corrective Action Required
06/02/2011
RESOLUTION OF SHELL PERMIT ISSUES NOT COMPLETED/APPROVED.
Documents & Images
Date Uploaded File Type Document Name
05/05/2011 Letter Fire (Sprinkler) Plan Review
05/12/2011 Letter Building Permit
05/12/2011 Letter Plan Review Conditions
05/20/2011 Letter Temporary Certificate of Occupancy
05/20/2011 Letter Fire Loss Reduction Form
05/23/2011 Letter Inspection Summary
06/06/2011 Letter Field Certificate of Occupancy
06/07/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home