Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
|
05/11/2011
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved
|
05/13/2011
|
05/11/2011
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Submit a layout of alarm notification appliances.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule alarm testing.
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Provide a minimum of two, 2A:10B:C fire extinguishers. Verified at inspection.
|
|
Misc
Corrective Action Required
Exit and emergency lighting shall be provided if not already part of the shell building.
Verified at inspection.
|
|
Address numbers required
Corrective Action Required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Verified at inspection.
|
|
|
Historical Preservation Review
|
Approved
|
05/13/2011
|
05/10/2011
|
|
Mike Weisenborn
|
|
|
License Tax Codes
|
Approved
|
05/13/2011
|
05/10/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
05/13/2011
|
05/10/2011
|
|
Mike Weisenborn
|
|
Planning - Signs
Corrective Action Required
Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirements.
Action required - This comment is for information purposes only.
|
|
Misc
Corrective Action Required
This permit is to set the occupancy only. It does not include any plumbing, electrical, mechanical or construction work.
Action required - This comment is for information purposes.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
|
05/05/2011
|
|
Brian Austerman
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Plans received on 4/25/2011, relesed for construction as shown on plans
|
|
Misc
Corrective Action Required
Use of the space not shown, Ordinary Hazard II for general mercantile only
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call 969-1300 to schedule acceptance testing prior to final
|
|
|
Zoning Review
|
Approved
|
05/13/2011
|
05/03/2011
|
|
Hector Soto Jr.
|
|
|