Permit Application Status

PRCOM20110702


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110702
Building Permit - Commercial
Certificate of Occupancy
PREMIERLIFE REAL ESTATE HOLDING
CHANGE OF TENANT
TENANT FINISH
04/18/2011
05/09/2011
10/24/2011
10/03/2011
Locations
Contacts
HOUSE & RENNER CONST INC, Address:5403 W 40 HWY, Phone:(816) 229-4853  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
PREMIERLIFE REAL ESTATE HOLDING, Address:400 NW MURRAY RD  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
SCHOELLER PLUMBING INC, Address:PO BOX 1268, Phone:(816) 628-3848  
HOUSE & RENNER CONST INC, Address:5403 W 40 HWY  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/06/2011
Mike Weisenborn
Building Plan Review Approved 05/11/2011 05/06/2011
Mike Weisenborn
Bldg - Doors - Size of doors
Resolved
05/06/2011

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - This comment is in regards to doors 105A and B. Make needed corrections or provide additional information. Mike Weisenborn May 06, 2011 - Approved per resubmittal letter.
Misc
Resolved
05/06/2011

2005 NEC 230.70(A)(2) - Bathrooms. Service disconnection means shall not be installed in bathrooms. Action required - The electric service panels are shown to be located in room 112 which is a private bathroom. Make needed corrections. Mike Weisenborn May 06, 2011 - Resolved per resubmittal letter.
Planning - Signs
Corrective Action Required
05/06/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments.
Internal Plan Review (Res) Rejected 04/26/2011 04/27/2011
Mike Weisenborn
Fire Plan Review Approved 04/26/2011 04/27/2011
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
04/27/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE SHOP DRAWINGS FOR NEW OR ADDITIONAL NOTIFICATION APPLIANCES
Installation acceptance testing
Corrective Action Required
04/27/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. CALL 969-1300 TO SCHEDULE TESTING PRIOR TO FINAL
Portable fire extinguishers - conspicuous locations
Corrective Action Required
04/27/2011

2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. PROVIDE 2A10B:C EXTINGUISHERS FOR COMPLIANCE OF NFPA 10
Misc
Corrective Action Required
04/27/2011

200R IFC1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. MAINTAIN THE INTEGRITY OF THE EXITS AND PASSAGEWAYS DURING CONSTRUCTION
Misc
Corrective Action Required
04/27/2011

2006 IFC 907.2.12.1 Automatic fire detection. Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows: 1. In each mechanical equipment, electrical, transformer, telephone equipment or similar room which is not provided with sprinkler protection, elevator machine rooms, and in elevator lobbies. 2. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet. 3. At each connection to a vertical duct or riser serving two or more stories from a return air duct or plenum of an air-conditioning system. In Group R-1 and R-2 occupancies, a listed smoke detector is allowed to be used in each return-air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air-inlet openings. RTU 1 IS LISTED AS 2000CFM, IT REQUIRES DUCT DETECTION THAT WILL SEND A SUPERVISORY SIGNAL TO THE ALARM PANEL UPON ACTIVATION
Building Plan Review Rejected 04/26/2011 04/26/2011
Mike Weisenborn
Bldg - Doors - Size of doors
Corrective Action Required
04/26/2011

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - This comment is in regards to doors 105A and B. Make needed corrections or provide additional information.
Misc
Corrective Action Required
04/26/2011

2005 NEC 230.70(A)(2) - Bathrooms. Service disconnection means shall not be installed in bathrooms. Action required - The electric service panels are shown to be located in room 112 which is a private bathroom. Make needed corrections.
Historical Preservation Review Approved 04/26/2011 04/25/2011
Mike Weisenborn
License Tax Codes Approved 04/26/2011 04/25/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $1,634.00 $1,634.00 Paid 05/09/2011
8331507-Sewer Connection Fee $480.00 $480.00 Paid 05/09/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Partial 5/12/2011 at 12:00 AM 05/12/2011
Misc
Partial Correction
05/12/2011
STUDOR VENTS WILL BE ALLOWED AT ISLAND SINKS AT NURSE STATION 144
Underslab Electrical Inspection - Commercial Passed 5/16/2011 5/16/2011 at 12:00 AM 05/16/2011
Underslab Plumbing Inspection - Commercial Passed 5/16/2011 5/16/2011 at 12:00 AM 05/16/2011
In-wall Inspection Failed 6/14/2011 6/14/2011 at 12:00 AM 06/14/2011
Misc
Corrective Action Required
06/14/2011
IPC 305.8: INSTALL SHIELD PLATES AT STUDS & TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES AND SHALL EXTEND A MINIMUM OF 2" ABOVE BASE TRACKS & BELOW TOP TRACKS. CHECK ALL.
In-wall Inspection Partial 6/15/2011 at 12:00 AM 06/15/2011
Misc
Corrective Action Required
06/14/2011
IPC 305.8: INSTALL SHIELD PLATES AT STUDS & TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES AND SHALL EXTEND A MINIMUM OF 2" ABOVE BASE TRACKS & BELOW TOP TRACKS. CHECK ALL.
In-wall Inspection Passed 6/16/2011 at 12:00 AM 06/16/2011
Misc
Resolved
06/16/2011
IPC 305.8: INSTALL SHIELD PLATES AT STUDS & TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES AND SHALL EXTEND A MINIMUM OF 2" ABOVE BASE TRACKS & BELOW TOP TRACKS. CHECK ALL.
Rough Plumbing Inspection - Commercial Passed 6/16/2011 (8:00 to 5:00) 6/16/2011 at 12:00 AM 06/16/2011
Misc
Resolved
06/16/2011
STUDOR VENTS WILL BE ALLOWED AT ISLAND SINKS AT NURSE STATION 144
Electrical Service Inspection Passed 7/14/2011 7/14/2011 at 12:00 AM 07/14/2011
Above Ceiling Inspection Partial 8/29/2011 (8:00 to 5:00) 10/3/2011 at 12:00 AM 08/29/2011
Misc
Corrective Action Required
08/29/2011
OPEN ELECT JUNCTION BOX: 115
Misc
Corrective Action Required
08/29/2011
UNUSED OPENING -- DOUBLE-SLAMMER WITH ONE HOLE UNUSED: 148
Misc
Corrective Action Required
08/29/2011
OPEN PULL BOX: 131
Misc
Partial Correction
08/29/2011
CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER EXCEPT SPACES NOTED ABOVE
Above Ceiling Inspection Passed 8/30/2011 at 12:00 AM 08/30/2011
Misc
Resolved
08/30/2011
OPEN ELECT JUNCTION BOX: 115
Misc
Resolved
08/30/2011
UNUSED OPENING -- DOUBLE-SLAMMER WITH ONE HOLE UNUSED: 148
Misc
Resolved
08/30/2011
OPEN PULL BOX: 131
Misc
Resolved
08/30/2011
CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER EXCEPT SPACES NOTED ABOVE
Occupancy Inspection - Codes Commercial Full C of O 10/3/2011 at 12:00 AM 10/03/2011
Occupancy Inspection - Fire Passed 10/03/2011
Documents & Images
Date Uploaded File Type Document Name
04/27/2011 Letter Plan Review Conditions
05/09/2011 Letter Plan Review Conditions
05/09/2011 Letter Building Permit
05/12/2011 Letter Inspection Summary
05/16/2011 Letter Inspection Summary
06/14/2011 Letter Inspection Summary
06/16/2011 Letter Inspection Summary
07/14/2011 Letter Inspection Summary
08/29/2011 Letter Inspection Summary
08/30/2011 Letter Inspection Summary
10/03/2011 Letter Field Certificate of Occupancy
10/03/2011 Letter Fire Loss Reduction Form
10/04/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home