Permit Application Status

PRCOM20110307


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110307
Building Permit - Commercial
Certificate of Occupancy
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
Expansion of existing hospital lab on first floor Remodel of old respiratory therapy area for accounting
03/09/2011
03/28/2011
08/23/2011
Locations
Contacts
ACI BOLAND, Address:11229 NALL, SUITE 140  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
P1 CONSTRUCTION LLC, Address:13605 W 96TH TERR, Phone:(913) 529-5000  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
JE DUNN CONSTRUCTION CO, Address:120 S CENTRAL AVE STE 350, Phone:(816) 474-8600  
SAINT LUKES EAST HOSPITAL, Address:901 E 104TH ST MAILSTOP 900N  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 04/11/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/11/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received April 8, 2011.
Installation acceptance testing
Corrective Action Required
04/11/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Provide adocumentation of any required testing for the system per NFPA 25 and 13. Visual inspection to be completed at occupancy inspection.
Internal Plan Review (Res) Approved 03/17/2011 03/21/2011
Mike Weisenborn
Fire Plan Review Approved 03/17/2011 03/15/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
03/15/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
03/15/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alrm system alteration.
Installation acceptance testing
Corrective Action Required
03/15/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test.
Misc
Corrective Action Required
03/15/2011

2006 IFC 3006.1 General. Compressed gases at hospitals and similar facilities intended for inhalation or sedation including, but not limited to, analgesia systems for dentistry, podiatry, veterinary and similar uses shall comply with this section in addition to other requirements of this chapter. All gas lines shall be maitained or altered in accordance with this section of the code.
Building Plan Review Approved 03/17/2011 03/14/2011
Mike Weisenborn
Misc
Corrective Action Required
03/14/2011

Phasing of the project and inspections shall be reviewed and worked out with the building inspector assigned to the project. Action Required - The contractor shall establish inspection requirements with John Borns. (816) 969-1200. This comment is for information purposes.
License Tax Codes Approved 03/17/2011 03/14/2011
Mike Weisenborn
Historical Preservation Review Approved 03/17/2011 03/10/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,154.65 $1,154.65 Paid 03/28/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Commercial Partial 4/1/2011 at 12:00 AM 04/01/2011
Misc
Partial Correction
04/01/2011
ARCHITECTURAL AND ELECTRICAL MODIFICATIONS IN PHASE I AREA -- NO ISSUES FOUND; OK FOR USE.
In-wall Inspection Partial 4/6/2011 at 12:00 AM 04/06/2011
Misc
Partial Correction
04/06/2011
OK TO COVER WHEN READY WALL FRAMING @ 1A037A N WALL
In-wall Inspection Partial 5/4/2011 5/4/2011 at 12:00 AM 05/04/2011
Misc
Partial Correction
04/06/2011
OK TO COVER WHEN READY WALL FRAMING AT: 1A037A N WALL; PHASE 2 AREA;
In-wall Inspection Partial 5/4/2011 at 12:00 AM 05/04/2011
Misc
Partial Correction
05/04/2011
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT: 1A037A N WALL; PHASE 2 AREA;
Above Ceiling Inspection Partial 5/25/2011 5/25/2011 at 12:00 AM 05/25/2011
Misc
Partial Correction
05/25/2011
OK TO COVER WHEN READY CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: PHASE I (ENSURE ONE ELECT J.B. IS CLOSED WHEN TEMPORARY POWER FEED IS REMOVED);
Above Ceiling Inspection Partial 5/25/2011 at 12:00 AM 05/25/2011
Misc
Partial Correction
05/25/2011
OK TO COVER WHEN READY CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: PHASE II (ENSURE ONE ELECT J.B. IS CLOSED WHEN TEMPORARY POWER FEED IS REMOVED);
Alarm Test Passed 6/21/2011 at 6:00 AM 06/21/2011
Occupancy Inspection - Fire Passed 06/24/2011
Occupancy Inspection - Codes Commercial Temporary C of O 6/24/2011 at 12:00 AM 06/24/2011
Misc
Partial Correction
06/24/2011
MODIFICATIONS OK FOR USE IN AREAS: PHASE I; 041; 041A; 041B; 041C; 041D; 041E; 041L; 041M;
In-wall Inspection Partial 7/25/2011 7/25/2011 at 12:00 AM 07/25/2011
Misc
Partial Correction
05/04/2011
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT: 1A037A N WALL; PHASE 2 AREA;
In-wall Inspection Partial 7/25/2011 at 12:00 AM 07/25/2011
Misc
Partial Correction
07/25/2011
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT: 1A037A N WALL; PHASE 2 AREA; 037 N & E WALLS; 038 E WALL;
Occupancy Inspection - Codes Commercial Temporary C of O 7/28/2011 at 12:00 AM 07/28/2011
Misc
Partial Correction
06/24/2011
MODIFICATIONS OK FOR USE IN AREAS: PHASE I; 041; 041A; 041B; 041C; 041D; 041E; 041L; 041M;
Above Ceiling Inspection Passed 8/8/2011 at 12:00 AM 08/08/2011
Misc
Resolved
08/08/2011
OK TO COVER WHEN READY CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT FOLLOWING SPACES: PHASE 1; PHASE 2; PHASE 3; PHASE 4
Occupancy Inspection - Codes Commercial Full C of O 8/23/2011 8/23/2011 at 12:00 AM 08/23/2011
Misc
Resolved
08/23/2011
MODIFICATIONS OK FOR USE IN PHASE AREAS 1 THROUGH 4
In-wall Inspection Passed 8/23/2011 at 12:00 AM 08/23/2011
Misc
Resolved
08/23/2011
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT: 1A037A N WALL; PHASE 2 AREA; 037 N & E WALLS; 038 E WALL;
Documents & Images
Date Uploaded File Type Document Name
03/15/2011 Letter Fire Building Plan Review
03/28/2011 Letter Building Permit
04/01/2011 Letter Inspection Summary
04/06/2011 Letter Inspection Summary
04/11/2011 Letter Fire (Sprinkler) Plan Review
05/04/2011 Letter Inspection Summary
05/25/2011 Letter Inspection Summary
06/24/2011 Letter Fire Loss Reduction Form
06/24/2011 Letter Temporary Certificate of Occupancy
07/25/2011 Letter Inspection Summary
08/08/2011 Letter Inspection Summary
08/23/2011 Letter Field Certificate of Occupancy
08/24/2011 Letter Final Certificate of Occupancy
07/02/2013 Letter Plan Review Conditions
08/21/2013 Letter Inspection Summary
08/28/2013 Letter Temporary Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home