Permit Application Status

PRCOM20110078


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110078
Building Permit - Commercial
Final Completion
SOUTHWESTERN BELL TELEPHONE
ALTERATION COMMERCIAL
Fire Safety Improvements
01/21/2011
04/27/2011
08/03/2011
07/20/2011
Locations
Contacts
NABHOLZ CONSTRUCTION CORPORATION, Address:PO BOX 2090, Phone:(501) 505-5800  
Schwerdt Design Group, Inc., Address:2231 SW Wanamaker Rd  
SOUTHWESTERN BELL TELEPHONE, Address:ONE SBC CENTER 36-M-1  
R F FISHER ELECTRIC COMPANY LLC, Address:5299 DTC BLVD STE 600, Phone:(913) 384-1500  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 05/16/2011
Brian Austerman
Installation acceptance testing
Corrective Action Required
05/16/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: CALL 969-1300 FOR ALARM TESTING PRIOR TO FINAL
Misc
Corrective Action Required
05/16/2011

2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED: IF HVAC IS OVER 2000 CFM IT SHALL HAVE DUCT DETECTION ON THE RETURN AIR SUPPLY
Misc
Corrective Action Required
05/16/2011

FIRE DEPT. The outside horn strobe shall activate on sprinkler waterflow only
Misc
Corrective Action Required
05/16/2011

FIRE DEPT. Recommendation- Suggest using heat detector instead of smoke detector in the engine room, or the use of IR flame detection only
Misc
Corrective Action Required
05/16/2011

FIRE DEPT- ASSDS shall only transmit an alarm condition to the FACP in alarm mode
Misc
Corrective Action Required
05/16/2011

FIRE DEPT- Need to provide smoke detection over FACP
Internal Plan Review (Res) Approved 02/25/2011
Mike Weisenborn
Building Plan Review Approved 03/01/2011 02/25/2011
Mike Weisenborn
Misc
Resolved
02/25/2011

I am unable to locate any details on the mechanical, electrical and plumbing work to be performed. Action required - Provide details and specs on the alterations to the m/e/p systems. Additional information provided on the plans.
Misc
Resolved
02/25/2011

Sheet G-002 shows details for repairing and penetrations of fire-resistive assemblies but I am unable to locate on the plans where these situations exist. Action required - Provide additional information.
Fire Plan Review Approved 03/01/2011 02/24/2011
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
02/24/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for review and approval.
Misc
Corrective Action Required
02/24/2011

2006 IFC 907.10.1.2 Employee work areas. Where employee work areas have audible alarm coverage, the notification appliance circuits serving the employee work areas shall be initially designed with a minimum of 20 percent spare capacity to account for the potential of adding visible notification appliances in the future to accommodate hearing impaired employee(s). Action required: Shop drawings shall include the additional capacity. Action required: Add the additional RESOLVED ON RESUBMITTAL
Misc
Corrective Action Required
02/24/2011

2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required: Duct detectors shall be supervisory signals; shuting done assiciated AHU, and shall not activate building horn/strobes. RESOLVED ON RESUBMITTAL
Misc
Corrective Action Required
02/24/2011

The exterior sprinkler alarm shall be a weatherproof horn strobe. RESOLVED ON RESUBMITTAL
Misc
Corrective Action Required
02/24/2011

2006 IFC 608.5.1 Nonrecombinant battery neutralization. For battery systems containing lead-acid, nickel-cadmium or other types of batteries with free-flowing electrolyte, the method and materials shall be capable of neutralizing a spill from the largest lead-acid battery to a pH between 7.0 and 9.0. Action required: Provide the required neutralization. RESUBMITTAL LETTER ADDRESSED THIS, RESOLVED
Misc
Corrective Action Required
02/24/2011

608.1 Scope. Stationary storage battery systems having an electrolyte capacity of more than 50 gallons (189 L) for flooded lead acid, nickel cadmium (Ni-Cd) and valve-regulated lead acid (VRLA), or 1,000 pounds (454 kg) for lithium-ion, used for facility standby power, emergency power or uninterrupted power supplies, shall comply with this section and Table 608.1. Action required: Indicate if there will be a change in the current type or method of storage other than containment. RESUBMITTAL LETTER ACKNOWLEDGED THIS, RESOLVED
Installation acceptance testing
Corrective Action Required
02/24/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test and inspection.
License Tax Codes Approved 03/01/2011 02/24/2011
Mike Weisenborn
Internal Plan Review (Res) Rejected 02/04/2011
Mike Weisenborn
Fire Plan Review Rejected 02/02/2011 02/03/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
02/03/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for review and approval.
Misc
Corrective Action Required
02/03/2011

2006 IFC 907.10.1.2 Employee work areas. Where employee work areas have audible alarm coverage, the notification appliance circuits serving the employee work areas shall be initially designed with a minimum of 20 percent spare capacity to account for the potential of adding visible notification appliances in the future to accommodate hearing impaired employee(s). Action required: Shop drawings shall include the additional capacity. Action required: Add the additional
Misc
Corrective Action Required
02/03/2011

2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required: Duct detectors shall be supervisory signals; shuting done assiciated AHU, and shall not activate building horn/strobes.
Misc
Corrective Action Required
02/03/2011

The exterior sprinkler alarm shall be a weatherproof horn strobe.
Misc
Corrective Action Required
02/03/2011

2006 IFC 608.5.1 Nonrecombinant battery neutralization. For battery systems containing lead-acid, nickel-cadmium or other types of batteries with free-flowing electrolyte, the method and materials shall be capable of neutralizing a spill from the largest lead-acid battery to a pH between 7.0 and 9.0. Action required: Provide the required neutralization.
Misc
Corrective Action Required
02/03/2011

608.1 Scope. Stationary storage battery systems having an electrolyte capacity of more than 50 gallons (189 L) for flooded lead acid, nickel cadmium (Ni-Cd) and valve-regulated lead acid (VRLA), or 1,000 pounds (454 kg) for lithium-ion, used for facility standby power, emergency power or uninterrupted power supplies, shall comply with this section and Table 608.1. Action required: Indicate if there will be a change in the current type or method of storage other than containment.
Installation acceptance testing
Corrective Action Required
02/03/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test and inspection.
Building Plan Review Rejected 02/02/2011 01/31/2011
Mike Weisenborn
Misc
Corrective Action Required
01/31/2011

I am unable to locate any details on the mechanical, electrical and plumbing work to be performed. Action required - Provide details and specs on the alterations to the m/e/p systems.
Misc
Corrective Action Required
01/31/2011

Sheet G-002 shows details for repairing and penetrations of fire-resistive assemblies but I am unable to locate on the plans where these situations exist. Action required - Provide additional information.
Historical Preservation Review Approved 02/02/2011 01/24/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $242.81 $242.81 Paid 04/27/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Passed 7/6/2011 at 12:00 AM 07/06/2011
Alarm Test Passed 7/6/2011 at 12:00 AM 07/06/2011
Final Electrical Inspection - Commercial Passed 7/6/2011 at 12:00 AM 07/06/2011
Documents & Images
Date Uploaded File Type Document Name
02/04/2011 Letter Plan Review Conditions
04/27/2011 Letter Building Permit
04/27/2011 Letter Plan Review Conditions
07/06/2011 Letter Inspection Summary
07/06/2011 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire (Alarm) Plan Review Notice
07/02/2013 Letter Plan Review Conditions
07/02/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.