Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
05/17/2000
|
10/29/2010
|
|
|
|
Correction
Codes Administration- Hot water and drain pipes under lavatories or sinks shall be insulated or otherwise protected if they abut the clearance areas indicated in Fig. 31. There shall be no sharp or abrasive surfaces under lavatories or sinks. (ANSI A117.1-1986, Section 4.19.4.)
|
|
Correction
Codes Administration- Faucets shall comply with 4.25.4. Conventional one-quarter-turn, lever-operated, push-type, and automatically controlled mechanisms are examples of acceptable designs. Self-closing valves are allowed if the faucet remains open for at least 10 seconds. (ANSI A117.1-1986, Section 4.19.5.)
|
|
Correction
Codes Administration- Mirrors shall be mounted with the bottom edge of the reflecting surface no higher than 40 inches from the floor. (ANSI A117.1-1986, Section 4.19.6.)
|
|
Correction
Codes Administration- If the clear floor space allows only forward aproach to an object, the maximum high forward reach allowed shall be 48 inches and the minimum low forward reach shall be unobstructed and no less than 15 inches above the floor. If the high forward reach is over an obstruction, reach and clearances shall be as shown in Fig. 5(b). (ANSI A117.1-1986, Section 4.2.5.)
|
|
Correction
Codes Administration- If the clear floor space allows parallel approach by a person in wheelchair, the maximum high side reach allowed shall be 54 inches and the low side reach shall be no less than 9 inches above the floor. If the side reach is over an obstruction, the reach and clearances shall be as shown in Fig. 6(c). (ANSI A117.1-1986, Section 4.2.6.)
|
|
Correction
Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
|
|
Correction
Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
|
|
Correction
Codes Administration- Exit doors shall be openable from the inside without the use of a key or special knowledge. (UBC Section 3304.(c))
|
|
Correction
Codes Administration- In areas serving employees only, the minimum aisle width may be 24 inches but not less than the width required by the number of employees served. 1991 UBC Section 3315.b.1
|
|
Correction
Codes Administration- In public areas of Group B, Division 2 Occupancies, and in assembly occupancies without fixed seats, the minimum clear aisle width shall be 36 inches where tables, counters, furnishings, merchandise or other similar obstructions are placed on one side of the aisle only and 44 inches when such obstructions are placed on both sides of the aisle. 1991 UBC Section 3315.b.2
|
|
Correction
Codes Administration- Buildings or portions thereof where persons are employed shall be provided with at least one water closet. Separate facilities shall be provided for each sex when the number of employees exceeds four. (UBC Section 705.(c))
|
|
Correction
Codes Administration - Provide details on wall types A and B.
|
|
Correction
Codes Administration - Hood systems shall be tested with representatives of the Codes Administration and Fire Departments present.
|
|
Correction
Codes Administration - Provide information explaining why a grease trap is not installed in this kitchen space.
|
|
Correction
Codes Administration - Provide information on the hearth oven, preferably from the manufacturer, detailing how it is to be installed and vented.
|
|
Correction
Fire Department- Plans and specifications for grease hood and duct suppression system shall be submitted to the fire department for review and approval. (UFC Section 10.503)
|
|
Correction
Fire Department- Approved fire suppression systems shall be provided for the protection of commercial food heat-processing equipment that produces grease laden vapors. The system installed to protect ventilating hoods and ducts and cooking appliances shall be installed to include cooking surfaces, deep fat fryers, griddles, upright broilers, charbroilers, range tops and grills. Protection shall also be provided for the enclosed plenum space within the hood above filters and exhaust ducts serving the hood. UFC 10.513
|
|
Correction
Fire Department- Fire-protection equipment and fire hydrants shall be clearly identified in a manner approved by the chief to prevent obstruction by parking and other obstructions. (UFC Section 10.105b)
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
Correction
Fire Department- Plans and specifications for grease hood and duct suppression system shall be submitted to the fire department for review and approval. (UFC Section 10.503)
|
|
Correction
Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
|
|
Correction
Fire Department- Fire-protection or extinguishing system coverage, spacing and specifications shall be maintained accordance with recognized standards at all time. Such systems shall be extended, altered or augmented as necessary to maintain and continue protection whenever any building so equipped is altered, remondeled or added to. Additions, repairs, alterations and servicing shall be in accordance with recognized standards. UFC Section 10.504(a)
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) or more shall not be stored in buildings or placed within 5 feet of combustible walls, openings or combustible roof lines. (UFC Section 11.302.(b))
|
|
Correction
Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
Correction
Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
|
|
Correction
Fire Department- If building alteration adversely effects exit illumination, exit illumination shall be provided and maintained in accordance with the Building Code. UFC Section 12.110.(A).
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
Correction
Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practical. Combustible debris, waste material and trash shall not be burned on site. (UFC Section 87.103.(e))
|
|
Correction
Codes Administration- A permanent electric outlet and lighting fixture controlled by a switch located at the required passageway opening shall be provided at or near the furnace. 1991 Uniform Mechanical Code Section 708
|
|
Correction
Water Utilities - Requires a reduced pressure principal assembly.
|
|
|