Summary
B9902286
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
ALTERATION COMMERCIAL
TENANT ADDITION SUMMIT FITNESS
10/27/1999
11/08/1999
05/06/2000
10/30/2001
Locations
Contacts
GUENTHER MILLS KEATING ARCHITECTS, Address:8801 EAST 63RD STREET, SUITE 208  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/24/2000 10/29/2010
Correction

Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
Correction

Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Codes Administration- Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the Building Official. The Building Official, upon notification, shall make the requested inspections and shall either indicate that portion of the construction is satisfactory as completed, or shall notify the permit holder or an agent of the permit holder wherein the same fails to comply with this code. Any portions which do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the Building Official. (1991 Uniform Building Code, Section 305.(d).)
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

Codes Administration- Exit doors shall be openable from the inside without the use of a key or special knowledge. (UBC Section 3304.(c))
Correction

Codes Administration- When two or more exits from a story are required by Section 3303, exit signs shall be installed at stair enclosure doors, horizontal exits and other required exits from the story. When two or more exits are required from a room or area, exit signs shall be installed at the required exits from the room or area and where otherwise necessary to clearly indicate the direction of egress. 1991 Uniform Building Code Section3314.(a)
Correction

Codes Administration - All work shall be performed in accordance with the Codes adopted by the City of Lee's Summit. Any violations addressed by the Inspections Staff shall be corrected and reinspected prior to covering.
Correction

Codes Administration - Fire assemblies required to have a one- and one-half hour fire-protection rating shall be either automatic- or self-closing fire assemblies. Automatic-closing fire assemblies to be activated by an increase in temperature shall have heat-actuating devices located as required in Item A or by a single fusible link in the opening incorpartaed in the closing device. (1991 Uniform Building Code, Section 4306.(a)1.B.)
Correction

Codes Administration - All pentrations in the two-hour area seperation wall shall be protected as required in Chapter 43 of the 1991 Uniform Building Code.
Correction

Fire Department- Exit doors shall swing in the direction of exit travel when serving an occupant load of 50 or more. Door (1) does not appear to meet this criteria. UFC 12.106 (b).
Correction

Fire Department- A set of sprinkler plans and specifications bearing a State of Missouri licensed engineers seal, shall be submitted to the Fire Department for review and approval prior to construction (system modification). Plans will only be required to be submitted of sprinkler system is to be modified. (1991 Uniform Fire Code, Section 10.503)
Correction

Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- All locksets, both new and existing shall be openable from the inside without the use of a key, special tool or knowledge. (UFC.12.106)
Correction

Fire Department- Complete plans and specifications (bearing an State of Missouri architects /engineers seal) for fire alarm systems shall be submitted for review and approval prior to system installation. (UFC Section 14.103.(a))
Correction

Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
Correction

Fire Department- During construction required exit components shall be maintained. UFC Section 87.101.(c)
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $17.00 $17.00 Paid 11/08/1999
24 BLDG Plan Check Fees $3.25 $3.25 Paid 11/08/1999
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home