Summary
B9902144
Building Permit - Commercial
Final Completion
PFIZER INC
NEW OTHER
GENERATOR INSTALLATION BLDG 200
10/13/1999
02/11/2000
08/09/2000
01/28/2002
Locations
Contacts
U.S. ENGINEERING, Address:3433 ROANOKE  
PFIZER INC, Address:150 E 42ND ST FL 38TH  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/10/2000 10/29/2010
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

COMMUNITY DEVELOPMENT - 1) Provide overall site plan indicating all buildings (similar to Chiller site Plan) 2) Indicate existing and proposed fence and shrubs to screen additional generator(s) 3) Indicate color schedule of generator on elevation detail D/E-2
Correction

Trenches shall be inspected and approved prior to covering or backfilling.
Correction

Fire Department- General Note. The drawings call out a 2,000 gallon tank. It is understood it will be only 200 gallons.
Correction

Fire Department- UFC 79.110. Aboveground storage tanks over 100-gallon water capacity permanently installed, mounted or affixed and used for storage of ClassI,II or III-A liquids shall bear a label or placard identifying the material therein in accordance with UFC Standard No. 79-3.
Correction

Codes Administration- Direct burried cable or conduit or other raceways shall be installed to meet the minimum cover requirements of Table 300-5.
Correction

Fire Department- A completed hazardous materials permit application shall be submitted to the Lee's Summit fire department. (UFC Section 4.103 and UFC Section 80.103.(a))
Correction

Fire Department- Guard post or other means shall be provided to protect the exterior storage tanks from vehicular damage. When guard post are installed, the post shall be: 1. Constructed of steel not less than 4 inches in diameter and concrete filled, 2. Spaced not more than 4 feet between post on center, 3. Set not less than 3 feet deep in a concrete footing of not less than 15 inch diameter, 4. Set with the top of the posts not less than 3 feet above ground, and 5. Located not less than 5 feet from the tank. UFC Section 80.301.(w)
Correction

Fire Department- Tanks shall be installed in accordance with article 79, Division V, and shall be installed in special enclosures constructed in accordance with Section 79.902(c) or in listed and approved tank enclosures or materials providing fire protection of not less than 2 hours. The following additional criteria shall apply: (a) Gaurd posts or other means shall be provided to protect the area where tanks are installed. The design shall be in accordance with Sec. 80.301(w). (b) Each tank and each special enclosure shall be surrounded by a clear space of not less than 3 feet to allow for maintenance and inspection. (c) Conspicuous signs prohibiting simultaneous tank filling and fuel dispensing shall be posted. (e) Tanks shall be provided with automatic fuel shut off devices capable of stopping the delivery of fuel when the level of the tank reaches 90 percent of tank capacity. UFC Appendix II-F
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Plan Check Fees $56.25 $56.25 Paid 02/11/2000
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home