Permit Application Status

B9901265


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B9901265
Building Permit - Commercial
Final Completion
PFIZER INC
ALTERATION COMMERCIAL
INTERIOR ROOM ADDITION
07/08/1999
08/24/1999
02/20/2000
08/13/2002
Locations
Contacts
PFIZER, INC, Address:1 PFIZER WAY  
PFIZER INC, Address:150 E 42ND ST FL 38TH  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/04/2000 10/29/2010
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Fire-protection or extinguishing system coverage, spacing and specifications shall be maintained accordance with recognized standards at all time. Such systems shall be extended, altered or augmented as necessary to maintain and continue protection whenever any building so equipped is altered, remondeled or added to. Additions, repairs, alterations and servicing shall be in accordance with recognized standards. UFC Section 10.504(a)
Correction

F80.302(u) Emergency Alarm. An approved emergency alarm system shall be provided in buildings , rooms or areas used for storage of hazardous materials . Emergency alarm signal device shall be installed outside of each interior exit door of storage buildings , rooms or areas. Activation of emergency alarm-initiating device shall sound a local alarm to alert occupants of an emergency situation involving hazardous materials.
Correction

F80.301(v) Supervision. When emergency alarm, detection or automatic fire-extinguishing systems are required in Sections 80.302 through 80.315, such systems shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible an visual signal at a constantly attended on-site location.
Correction

General Note(Fire)- It is understood that flammable liquids will NOT be stored or tested in the relocated (north) testing chamber, and spill control measures will not be installed.
Correction

General Note- The plans do not address ventilation of the chamber if conditions in the chamber exceed LEL. There is constant ventilation of the room, but in order to ventilate the chamber someone would have to enter into an explosive atmosphere. A method of ventilation should be provided that does not involve placing someone into a hazardous area The exhaust fan to the room does not have an indication it is rated for flammable enviroments.
Correction

General Note(Fire)- Construction of the room shall meet all UBC, NEC and Mechanical Code requirements for hazardous locations (H3).
Correction

Clarify rating of UL label B as called out on the door scedule.
Correction

Codes Administration also has concerns about the type of electrical equipment that will be installed in the room. Respond to condition number CON0004591.
Correction

Both the emergency lighting and the exit sign installed in the room must be intrinsically safe.
Correction

Fire Department- Fire-protection equipment and fire hydrants shall be clearly identified in a manner approved by the chief to prevent obstruction by parking and other obstructions. (UFC Section 10.105b)
Correction

Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
Correction

Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
Correction

Fire Department- The chief is authorized to require warning signs for the purpose of pointing out the hazards of storing flammable liquids. UFC Section 79.109.(a)
Correction

Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practical. Combustible debris, waste material and trash shall not be burned on site. (UFC Section 87.103.(e))
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $302.00 $302.00 Paid 08/24/1999
24 BLDG Plan Check Fees $20.00 $20.00 Paid 08/24/1999
BLDG Investigation Fees $151.00 $151.00 Paid 08/24/1999
25 Electrical Permit Fee $48.09 $48.09 Paid 08/24/1999
25 Mechanical Permit Fees $32.50 $32.50 Paid 08/24/1999
25 Plumbing Permit Fees $34.00 $34.00 Paid 08/24/1999
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home