Internal Plan Review (Res)
|
Approved
|
11/17/1999
|
10/29/2010
|
|
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
Correction
Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
|
|
Correction
Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
|
|
Correction
UFC 10.513. Approved fire suppression and hood systems shall be provided for the protection of commercial food heat-processing equipment that produces grease laden vapors. The applicant shall provide documentation on kitchen appliance type and planned utilization for determination on whether or not further protection will be required. UFC 10.513
|
|
Correction
The meeting room/kitchen must be seperated from the remaining portion of the hanger by not less than a one-hour fire-resistive occupancy seperation. This occupancy seperation must be a complete seperation of the two spaces from the finish floor to the roof deck. All opening must be properly protected. All doors must be self closing self latching with smoke seals. The serving window must be protected by a fusable linked roll down fire door.
|
|
Correction
Varify the existing private sewer system at the airport will support the additional load that will be placed upon it with this addition.
|
|
Correction
Both restrooms are required to be handicap accessible. Grab bars must be installed and the proper door hardware must be used. All other elements must be installed to meet the hanicap requirements. UBC Chapter 31
|
|
Correction
Reverse the swing of the double door. When the occupant load served exceeds 50 the exit doors must swing in the direction of travel. UBC Section 3304(b)
|
|
Correction
Both new restrooms must be properly vented per the 1991 Uniform Building Code.
|
|
Correction
The handicap accessible restroom must comply with the 1991 Uniform Building Code, Chapter 31.
|
|
Correction
A landing must be installed outside the new exterior door that complies with the 1991 Uniform Building Code, Chapter 33.
|
|
Correction
All joints of the double layer of 5/8" type X rock must be staggered. Each layer must be screwed at not less than 6" arround the edge and 12" in the field.
|
|
Correction
This permit has been issued with the assumption the architect of record, Thomas Gibbens, has visited the job site and observed the framing members used for the ceiling construction and approved such members.
|
|
Correction
This permit is being issued with the assumption that Jackson County has approved the installation of additional plumbing fixtures on the existing holding tank. The applicant has assured this department that this new load was taken into consideration when the holding tank was installed.
|
|
Correction
The applicant shall call for an inspection at each layer to the rated ceiling construction. Per the approved plans nothing is allowed to penetrate the two layers of 5/8" type X rock of the floor ceiling seperation.
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
|