Internal Plan Review (Res)
|
Approved
|
08/30/1999
|
10/29/2010
|
|
|
|
|
|
Correction
Codes Administration- A Certificate of Occupancy will not be issued for a tenant finish until a minimum of a Temporary Occupancy has been issued for the shell building.
|
|
|
Correction
Codes Administration- Erosion control shall be provided in conformance with Article VIII, Section VIII(c) & (d) and details 48 and 48A of the City of Lee's Summit Design and Construction Manual. Erosion control devices shall be installed and maintained during all phases of the construction process. Failure to provide or maintain erosion control may result in an issuance of a stop work order which is authorized by Article I, Section XXIV.
|
|
|
Correction
Codes Administration- Each structure shall have the address of that structure visibly posted on the jobsite throughout the construction process.
|
|
|
Correction
Codes Administration- Provide a complete truss package designed and sealed by an engineer licensed in the State of Missouri. The package shall include the design specifications and details on the design, installation, bracing and fastening of the trusses. Two packages for each building type shall be provided to the Codes Administration Department for approval prior to installation.
|
|
|
Correction
Codes Administration- A completed License Tax application must be submitted to the City of Lee's Summit and any applicable License Tax paid prior to issuing a building permit.
|
|
|
Correction
Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
|
|
|
Correction
Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
|
|
|
Correction
Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
|
|
|
Correction
Codes Administration- Exit doors shall be openable from the inside without the use of a key or special knowledge. (UBC Section 3304.(c))
|
|
|
Correction
Requires a reduced pressure principal assembly on main water supply line.
|
|
|
Correction
The final site plan (#S99-006) was approved by the City Council on March 18, 1999.
|
|
|
Correction
All landscaping, as shown on the approved plans, shall be installed by May 31, 1999 or prior to the receipt of a Certificate of Occupancy.
|
|
|
Correction
A sidewalk is required along Executive Way.
|
|
|
Correction
Sign permits must be obtained for all signs prior to installation. All signs shall comply with Ordinance 715, Section 350.
|
|
|
Correction
All exterior mechanical equipment, whether roof mounted or ground mounted, shall be screened from view from off the property. The appearance of screens shall be coordinated with the building to maintain a unified appearance.
|
|
|
Correction
All exterior trash storage containers shall be screened as shown on the approved site plan.
|
|
|
Correction
All development shall be in accordance with the approved site plan and all conditions in the City Council letter, dated March 12, 1999.
|
|
|
Correction
The Northeast wall shall be a minimum of one hour fire resistive construction as it's location is closer than 20 feet to the property line.
|
|
|
Correction
Ventilation shall be provided for the attic area in accordance with Section 3205 (c).
|
|
|
Correction
Buildings or portions of buildings shall be accessible to persons with disabilities. (UBC Chapter 31) Restrooms shall meet accessiblility requirements.
|
|
|
Correction
Clarify size of water service. Sheet P1 indicates a 5/8 x 3/4 water service and Sheet PE1 indicates a 1.5" service.
|
|
|
Correction
One opening for combustion air shall be located within the upper 12 inches of the enclosure and one opening for combustion air shall be located in the lower 12 inches of the enclosure. (UMC Section 602) Venting of appliances shall be in accordance with their listings.
|
|
|
Correction
Double check assembly required if the property has a irrigation system.
|
|
|
Correction
Tennant finish plans will be required for each space prior to occupancy.
|
|
|
Correction
NOTE:
The rear wall shall be constructed as a one hour fire resistive assembly IF such wall is located closer than 20 feet as indicated on the site plan.
|
|
|
Correction
Glass shall meet the requirements of Chapter 54 of the 1991 Uniform Building Code when installed in locations considered specificly hazardous per Section 5406.(d). Window type "C" shall have safety glass adjacent to doors per Section 5406(d)6.
|
|
|
Correction
An attic access opening shall be provided to attics of buildings with combustible ceiling or roof construction. The openings shall be located in a corridor, hallway or other readily accessible location. Attics with a maximum vertical height of less than 30 inches need not be provided with access openings. The opening shall be at least 22 inches by 30 inches. (1991Uniform Building Code, Section 3205.(a).) Access shall be provided for each area between draftstops.
|
|
|
Correction
Buildings or portions thereof where persons are employed shall be provided with at least one water closet. Separate facilities shall be provided for each sex when the number of employees exceeds four. (UBC Section 705.(c))
NOTE:
Owner may chose to install wye off of main line for future restrooms in each space to meet this requirement without having to pay sewer connection fees. If Owner intends to stub plumbing through floor, the sewer tap fees will be included in this permit.
|
|
|
Correction
The slope of ramps required by Chapter 31 which are located within an accessible route of travel shall not be steeper than 1 vertical to 12 horizontal. (1991 Uniform Building Code Section 3307.(c)) Pertains to parking lot ramp.
|
|
|
Correction
The lighting specifications submitted on March 22, 1999 have been reviewed and approved.
|
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
|
Correction
Fire Department- When fire protection, including fire apparatus access roads and water supplies for fire protection, is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction. UFC 10.502
|
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
|
Correction
Codes Administration- When provision is made for the future installation of fixtures, those provided for shall be considered if determining the required sizes of drain pipes. Construction to provide for such future installations shall be terminated with a plugged fitting, or fittings. Where the plugged fitting is at the point where the trap of a fixture may be installed, the plumbing system for such fixture shall be complete and conform with all plumbing requirements of this Code. (UPC Section 911)
|
|
|
|