Permit Application Status

B9900172


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B9900172
Building Permit - Commercial
Final Completion
LEES SUMMIT SCHOOL DIST R 7
ALTERATION COMMERCIAL
HVAC ALTERATIONS
02/05/1999
03/22/1999
09/18/1999
11/11/1999
Locations
Contacts
REORGANIZED SCHOOL DIST. #7, Address:600 SE MILLER ST  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 08/04/1999 10/29/2010
Correction

Codes Administration- A demolition permit is required. (UBC Section 301)
Correction

Codes Administration- The special inspector shall observe the work assigned for conformance, shall furnish inspection reports to the Codes Administration Department and the engineer or architect of record and shall submit a final signed report stating whether the work requiring special inspection was in conformance with the approved plans and applicable sections of this code. The final report shall be submitted prior to receiving a Certificate of Occupancy. (UBC Section 306.(c))
Correction

Codes Administration- Every room containing a boiler, central heating plant or hot-water supply boiler shall be separated from the rest of the building by not less than a one-hour fire-resistive occupancy separation. 1991 UBC Section 708.
Correction

Fireproofing of penetrations shall be installed per the Manufacturer's recommendations.
Correction

When inspections are made, an on site representative of the contractor shall assist the inspector to such areas of which the inspection is requested.
Correction

Submit documentation explaining how the renovation is not creating a greater hazard for the building and it's occupants. (This requirement was previously communicated to the Designer at a preliminary meeting, however has not been received by the Codes Administration Department).
Correction

The engineer or architect in responsible charge of the structural design work shall include in the construction documents the special inspections required by UBC section 306 and other structural inspections required by the engineer or architect. (UBC Section 302.(c))
Correction

General safety rules for any cutting or welding shall be in accordance with Article 49 of the UFC. This includes but is no limited to: Separation of cutting/welding operations from combustibles. When welding or cutting is performed above or withing 10 feet of combustible construction or material or near a place where workers or other persons are likely to pass, noncombustible shields shall be used to protect such materials or persons. Fire extinguisher shall be kept at locations where welding or cutting is performed. During and after welding and cutting operations, a fire watch shall be present. The fire watch shall be maintained at least one hour after completion of cutting operations to detect any smoldering fires. Upon detection, the fire department shall be immediately contacted.
Correction

Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practical. Combustible debris, waste material and trash shall not be burned on site. (UFC Section 87.103.(e))
Correction

Fire Department- During construction fire department access shall be maintained and not obstructed. UFC Section 87.103.(b)
Correction

Fire Department- During construction required exit components shall be maintained. UFC Section 87.101.(c)
Correction

Fire Department- During construction and alteration fire-resistive assemblies and construction shall be maintained in accordance with Section 10.602. and 10.602. UFC Section 87.104.(d)
Correction

Codes Administration- Each single system providing heating or cooling air in excess of 2,000 cubic feet per minute in Group A, Divisions 1, 2 and 2.1; Group B, Division 2; Group E; Group I and Group R, Division 1 Occupancies shall be equipped with an automatic shutoff activated by smoke detectors. When the system serves more than one occupancy, automatic shutoff shall be provided. (1991 Uniform Mechanical Code, Section 1009.a.)
Correction

Codes Administration- Smoke detectors required by Subsection (a) shall be installed in the main return-air duct ahead of any outside-air inlet or they may be installed in each room or space served by the return-air duct. Detectors shall also be installed in the supply duct, downstream of the filters. Activation of any detector shall cause the air-moving equipment to automatically shut down. (1991 Uniform Mechanical Code, Section 1009.b.)
Correction

Codes Administration- When a cooling coil or cooling unit is located in an attic or furred space where damage may result from condensate overflow, an additional water tight pan of corrosion resistant metal shall be installed beneath the cooling coil or unit to catch the overflow condensate due to clogged primary condensate drain, or one pan with a standing overflow and separate secondary drain may be provided with a drain pipe, minimum 3/4 nominal pipe size, discharging at a point which can be readily observed. This requirement is in addition to the requirements for condensate waste piping set forth in section 510 of this code. (UMC Section 1205)
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Plan Check Fees $270.00 $270.00 Paid 03/22/1999
25 Electrical Permit Fee $15.00 $15.00 Paid 03/22/1999
25 Mechanical Permit Fees $2,019.00 $2,019.00 Paid 03/22/1999
25 Plumbing Permit Fees $104.00 $104.00 Paid 03/22/1999
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home