| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Internal Plan Review (Res)
|
Approved
|
06/29/1999
|
10/29/2010
|
|
|
|
|
|
Correction
Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
|
|
|
Correction
Codes Administration- Erosion control shall be provided in conformance with Article VIII, Section VIII(c) & (d) and details 48 and 48A of the City of Lee's Summit Design and Construction Manual. Erosion control devices shall be installed and maintained during all phases of the construction process. Failure to provide or maintain erosion control may result in an issuance of a stop work order which is authorized by Article I, Section XXIV.
|
|
|
Correction
Parking lots and fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be provided with a surface so as to provide all-weather driving capabilities. Chip -n-seal noted on drawing.(UFC Section 10.204.(b))
|
|
|
Correction
Doors in Fire separation wall will be required to be on magnetic hold open devices connected to smoke detectors on both side of the fire wall. When a smoke detectors operates it shall cause the magnetic hold open devise to release and allow for closure of fire door. UFC Sec. 10.602.(b)
|
|
|
Correction
The occupancy classification must be listed on the drawings.
|
|
|
Correction
Submit details for the protection of all penetrations through the fire rated walls.
|
|
|
Correction
All exit doors must have landings.
|
|
|
Correction
Varify the soils been inspected and approved in accordance with the strengths listed on drawing F-1.
|
|
|
Correction
Provide the UL assembly number for the area seperation wall and occupancy seperation wall.
|
|
|
Correction
Insufficient information to complete review. After discussion with occupant on intended use of building additional information will be necessary to complete the review process. Required additional information:
1. Completed Hazardous Materials permit Application.
2. Flammable and combustible liquid storage and dispensing method and location.
3. Spray operations method and location.
4. Welding and cutting operations and location.
5. Warehouse storage layout plan including storage method, storage layout, storage height, storage isle separation distance, storage material classification.
6. Method and location of propane storage.
** This information is necessary to determine occupancy classification so applicable code requirements may be referenced.
|
|
|
Correction
The architect or engineer of record must determine which special inspecitons are required per the 1991 Uniform Building Code, Section 306. A letter must be submitted to this department from the inspector employed by the owner, listing what inspections will be performed.
|
|
|
Correction
Requires a reduced pressure principal assembly on main service line.
|
|
|
Correction
Double check detector check assembly required if the bldg is going to be sprinkled.
|
|
|
Correction
Fire Department- Two and one-half inch hose connections (standpipes) shall be provided at all exterior doors.
|
|
|
Correction
COMMUNITY DEVELOPMENT - All development shall be in accordance with the approved site plan dated December 22, 1999.
|
|
|
Correction
COMMUNITY DEVELOPMENT - Each accessible parking space shall be identified by a sign, mounted between 3 and 5 feet above the parking surface, at the head of the parking space. The sign shall be at least 12" x 18" in area and meet the requirements set forth in the manual on Uniform Traffic Control Devices, as referenced in Section 29-381 of the Lee's Summit General Code of Ordinances (sign type R7-8D)
|
|
|
Correction
COMMUNITY DEVELOPMENT - All landscaping, as shown on the approved plans dated 12-22-99, shall be installed by May 31, 2000 or prior to the receipt of a Certificate of Occupancy.
|
|
|
Correction
COMMUNITY DEVELOPMENT -No bumper blocks (concrete or wood "road ties") shall be used in front of all the parking stalls.
|
|
|
Correction
COMMUNITY DEVELOPMENT - The minor plat of "Chopp Limited Plaza, Lot 1" was recorded on June 25, 1998 and issued an instrument number of I 49104.
|
|
|
Correction
COMMUNITY DEVELOPMENT - If proposed, all parking lot lights shall be of the metal halide variety, shoebox with a flat lense--total cut-off of light at an angle of less than 90 degrees (measured from the vertical]--and of approved height. Submit manufacturer's specification for approval.
|
|
|
Correction
COMMUNITY DEVELOPMENT - What is the purpose of the "Chip 'n seal" area? Is this area strictly for storage? If so, what is going to be stored in said area? Provide a letter to Community Development Department.
|
|
|
Correction
COMMUNITY DEVELOPMENT - The tree protection plan contains minor errors which must be corrected prior to issuance a certificate of occupancy.
|
|
|
Correction
Fire Department- Fire alarm systems; fire hydrant systems; fire-extinguishing systems, including automatic sprinklers and wet and dry standpipes; halon systems and other automatic fire-extinguishing systems shall meet the approval of the fire department as to installation and locations and shall be subject to acceptance testing and such periodic testing as required by the chief. NOTE: Acceptance testing may scheduled at least 48 hours in advance by calling 969-7343. UFC 10.503
|
|
|
Correction
Fire Department- All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised when the number of sprinkler heads are one-hundred or more. Valve supervision and water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote station or proprietary supervising station as defined by national standards. UFC 10.508
|
|
|
Correction
COMMUNITY DEVELOPMENT - The ordinance requires that all off-street parking areas and all access drives in office, commercial, and industrial zoning districts shall have a boundary constructed of straight-back concrete curbing (Type CG-1) or an integral concrete sidewalk and curb with a vertical face.
|
|
|
Correction
All special inspections must be completed and approved by city staff prior to any type of occupancy.
|
|
|
Correction
Public Works - A revised storm water detention plan must be received prior to temporary or final c of o. The contractor installed a 6" outlet pipe in lieu of the 12" as shown on the approved final site plan.
|
|
|
Correction
PUBLIC WORKS - Erosion siltation control must be installed and maintained prior to the commencement of construction and a temporary or final c of o.
|
|
|
Correction
Fire Department- Fire-protection equipment and fire hydrants shall be clearly identified in a manner approved by the chief to prevent obstruction by parking and other obstructions. (UFC Section 10.105b)
|
|
|
Correction
Fire Department- Fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction when any portion of the facility or any portion of an exterior wall of the first story of the buildings is located more than 150 feet from the fire apparatus access as measured by an approved route around the exterior of the building or facility. (UFC Section 10.203.)
|
|
|
Correction
Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
|
|
|
Correction
Fire Department- The duct detectors when activated shall be received at the panel and alarm company as a trouble alarm. (UFC Section 10.503.)
|
|
|
Correction
Fire Department- A set of sprinkler plans and specifications bearing a State of Missouri licensed engineers seal, shall be submitted to the Fire Department for review and approval prior to construction (system modification). (1991 Uniform Fire Code, Section 10.503)
|
|
|
Correction
Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
|
|
|
Correction
Fire Department- Dumpsters and containers with an individual capacity of 1.5 cubic yards (40.5 cubic feet) or more shall not be stored in buildings or placed within 5 feet of combustible walls, openings or combustible roof lines. (UFC Section 11.302.(b))
|
|
|
Correction
Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
|
|
|
Correction
Fire Department- A completed hazardous materials permit application shall be submitted to the Lee's Summit fire department. (UFC Section 4.103 and UFC Section 80.103.(a))
|
|
|
Correction
Fire Department- General. Buildings or portions thereof, in which hazardous materials are stored, handled or used shall be constructed in accordance with the Building Code. (UFC Section 80.108.(a))
|
|
|
Correction
Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
|
|
|
Correction
Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practical. Combustible debris, waste material and trash shall not be burned on site. (UFC Section 87.103.(e))
|
|
|
Correction
Public Works- Prior to the start of construction, contact Public Works Inspections at 969-7450.
|
|
|
Correction
Public Works- Provide a copy of the Missouri Department of Transportation authorization for construction to be performed within the right-of-way of .
|
|
|
|