Summary
B9802055
Building Permit - Commercial
Certificate of Occupancy
HUFF CARL E & ALTHEA J
NEW TENANT FINISH
TENANT FINISH
12/28/1998
01/15/1999
07/14/1999
04/07/1999
Locations
Contacts
HUFF HOMES INC, Address:656 SE BAYBERRY LANE STE 10  
HUFF CARL E & ALTHEA J, Address:656 SE BAYBERRY LN 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/26/1999 10/29/2010
Correction

Codes Administration- All signage that provides emergency information or general circulation directions or identifies rooms and spaces shall comply with 4.28.2, 4.28.3, and 4.28.5. Tactile signage shall also comply with 4.28.4. ANSI A117.7-1986 Section 4.28.1
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Codes Administration- Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the Building Official. The Building Official, upon notification, shall make the requested inspections and shall either indicate that portion of the construction is satisfactory as completed, or shall notify the permit holder or an agent of the permit holder wherein the same fails to comply with this code. Any portions which do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the Building Official. (1991 Uniform Building Code, Section 305.(d).)
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

Codes Administration- Exit doors shall be openable from the inside without the use of a key or special knowledge. (UBC Section 3304.(c))
Correction

Codes Administration- Except within individual dwelling units, guest rooms and sleeping rooms, exits shall be illuminated at any time the building is occupied with light having intensity of not less than 1 foot-candle at floor level. The power supply for exit illumination shall normally be provided by the premises' wiring system. In the event of its failure, illumination shall be automatically provided from an emergency system for group I, Division1.1 and 1.2 occupancies and for all other occupancies where the exiting system serves an occupant load of 100 or more. Emergency systems shall be supplied from storage batteries or an on-site generator system and the system shall be installed in accordance with the requirements of the Electrical Code. (1991Uniform Building Code, Section 3313.(a) & (b).)
Correction

Codes Administration- When two or more exits from a story are required by Section 3303, exit signs shall be installed at stair enclosure doors, horizontal exits and other required exits from the story. When two or more exits are required from a room or area, exit signs shall be installed at the required exits from the room or area and where otherwise necessary to clearly indicate the direction of egress. 1991 Uniform Building Code Section3314.(a)
Correction

Codes Administration- In areas serving employees only, the minimum aisle width may be 24 inches but not less than the width required by the number of employees served. 1991 UBC Section 3315.b.1
Correction

Codes Administration- In public areas of Group B, Division 2 Occupancies, and in assembly occupancies without fixed seats, the minimum clear aisle width shall be 36 inches where tables, counters, furnishings, merchandise or other similar obstructions are placed on one side of the aisle only and 44 inches when such obstructions are placed on both sides of the aisle. 1991 UBC Section 3315.b.2
Correction

Codes Administration- Buildings or portions thereof where persons are employed shall be provided with at least one water closet. Separate facilities shall be provided for each sex when the number of employees exceeds four. (UBC Section 705.(c))
Correction

All plumbing, electrical and mechanical work shall comply with the applicable codes adopted by the City of Lee's Summit. Any violations found by the inspector in the field shall be corrected in a mannner that conforms with the adopted codes.
Correction

This plan review is based upon the plans that were submitted. As these plans did not include the existing offices it was not possible to review the entire tenant space. If upon inspection, violations are found do to the layout of the tenant space, they shall be corrected to meet all applicable codes.
Correction

Fire Department- Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
Correction

Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
Correction

Fire Department- Combustible debris shall not be accumulated within buildings. Combustible debris, rubbish and waste material shall be removed from buildings as often as practicl. Combustible debris, waste material and trash shall not be burned on site. UFC Section87.103.(e)
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $11.00 $11.00 Paid 01/15/1999
24 BLDG Plan Check Fees $2.75 $2.75 Paid 01/15/1999
25 Electrical Permit Fee $17.50 $17.50 Paid 01/15/1999
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home