Permit Application Status

B9801933


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B9801933
Building Permit - Commercial
Certificate of Occupancy
RHODES GENE & JANET-TRUSTEES
NEW COMMERCIAL
CONVERT HOUSE INTO OFFICE
12/02/1998
12/17/1998
06/15/1999
01/15/1999
Locations
Contacts
KIRK SAXTON, Address:502 SW WHITE RIDGE DR  
RHODES GENE & JANET-TRUSTEES, Address:205 SW JEFFERSON ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/31/1999 10/29/2010
Correction

Codes Administration- No merchandise, stock, interior furnishings or supplies shall be placed in this facility without approval from the City of Lee's Summit.
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

Site plan shows no handicap ramp from parking lot to the sidewalk. Is there an elevation change between the two which will require an accessible ramp to be installed? Please clarify.
Correction

The furnace closet does not show any access or combustion air openings in the plans. A furnace room shall have an opening or door and passageway thereto not less than 2 feet in width and large enough to permit removal of the largest furnace in such room without disturbing piping, conduits, appurtenant valves and juction boxes. (UMC 703). One opening for combustion air shall be located within the upper 12 inches of the enclosure and one opening for combustion air shall be located in the lower 12 inches of the enclosure. (UMC Section 602).
Correction

Verify exterior wall construction is a minimum of one hour fire resistive construction as structure is situated closer than 20 feet to property lines. (UBC Table 5-A).
Correction

When access for persons with disabilities is required by Chapter 31, the floor or landing shall not be more than 1/2 inch lower than the threshold of the doorway. (UBC 3304 (i).
Correction

Every required exit doorway shall be of a size as to permit the installation of a door not less than 3 feet in width and not less than 6 feet 8 inches in height. When installed, exit doors shall be capable of opening so that the clear width of the exit is not less than 32 inches. (UBC 3304 (f).
Correction

Ramps serving an occupant load of 49 or less shall not be less than 36 inches in width. Ramps having slopes steeper than 1 vertical to 15 horizontal shall have landings at the top and bottom. Top landings shall have a dimension measured in the direction of ramp run of not less than 5 feet. Landings at the bottom of ramps shall have a dimension in the direction of ramp run of not less than 6 feet. Ramps having slopes steeper than 1 vertical to 15 horizontal shall have handrails as required for stairways. The handgrip portion of handrails shall not be less than 1-1/2 inches or more than 2 inches in cross sectional dimension. (UBC 3307).
Correction

Stairways having two or more risers shall have handrails on both sides if the stairway width is 44 inches or more. One handrail is required if stairway width is less than 44 inches. The top of handrails and handrail extensions shall be placed not less than 34 inches or more than 38 inches above the nosing of treads and landings. Handrails shall be continuous the full length of the stairs and at least one handrail shall extend in the direction of the stair run not less than 12 inches beyond the top riser or less than 12 inches beyond the bottom riser. Ends shall be returned or shall terminate in newel posts or safety terminals. The rise of every step in a stairway shall not be less than 4 inches or greater than 7 inches and the run shall not be less than 11 inches. The largest tread run or riser height shall not exceed the smallest by more than 3/8 inch within any flight of stairs.
Correction

The site plan provided does not correspond with the floor plan submitted. Dimensions of structure conflicting. Please clarify.
Correction

Permit does not include any mechanical or plumbing work. If any such work must be performed additional permits will be required.
Correction

Buildings or portions of buildings shall be accessible to persons with disabilities. (UBC Chapter 31).
Correction

Identify use of building.
Correction

Verify that the floor is capable of supporting imposed loads. Shall be submitted by registered Architect or Engineer within the State of Missouri. Shall be submitted prior to Occupancy.
Correction

Approved numbers or address shall be placed on all new and existing buildings in such a position as to be plainly visable and legible from the street or road fronting the property. Said numbers shall contrast with their background. (UFC Section 10.301.(a))
Correction

Fire Department- Portable fire extiguishers shall be installed in occupancies and locations as set forth in the Uniform Fire Code Standards and as required by the Chief. Extinguishers shall be mounted in a conspicuous place with travel distance between any point in the building and extinguisher not to exceed 75 feet. Extinguishers shall be a minimum of 2A-10BC (5 lb.). (UFC Section 10.505.(a))
Correction

Fire Department- Exit doors shall be operable from the inside without the use of a key or any special knowledge. Exit doors shall not be locked, chained, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC Section 12.106.(c))
Correction

Fire Department- Exit illumination shall be provided and maintained in accordance with the Building Code. Exits shall be illuminated when the building or structure is occupied. Equipment providing emergency power for exit illumination and exit signs shall be maintained in an operable condition. (UFC Section 12.110)
Correction

Fire Department- Extension cords shall not be utilized as a substitute for permanent wiring. Extension cords shall only be utilized with portable appliances while such appliances are in use and shall only supply one portable appliance except for approved multi-plug extension cords. Extension cords shall be grounded when serving grounded appliances. Extension cords and multi-plug extension cords shall not be affixed to structures; extened through walls, ceilings, floors, under doors or floor coverings; or be subject to environmental or physical damage. (UFC Section 85.106.(a), (b) and (c))
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $8.00 $8.00 Paid 12/17/1998
24 BLDG Plan Check Fees $2.50 $2.50 Paid 12/17/1998
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home