Permit Application Status

B9801675


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B9801675
Building Permit - Commercial
Certificate of Occupancy
SOUTHWESTERN BELL TELEPHONE
ALTERATION COMMERCIAL
BASEMENT FINISH SOUTHWESTER BELL BUILDING
10/13/1998
11/09/1998
05/08/1999
11/01/1999
Locations
Contacts
KEARNEY & SONS CONST., Address:15156 K-4 HWY  
SOUTHWESTERN BELL TELEPHONE, Address:ONE SBC CENTER 36-M-1  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/08/1999 10/29/2010
Correction

Two additional exit sign are to be added per my phone conversation with Mike Hampton on 10-30-98.
Correction

A smoke and fire damper is required at the point the existing heating and ventalating duct penetrates the one hour occupancy seperation wall.
Correction

Any HVAC penetrations into the rated corridor must be properly protected with smoke and fire dampers.
Correction

The door labeled number 4 is required to be provided with a smoke seal.
Correction

The design professional must confirm the roof structure will support the addition of two new roof top units.
Correction

Codes Administration- A reinspection fee may be assessed if an approved set of plans are not readily available to the inspector and the permit card is not posted at the time of the inspection. (UBC Section 305.(g))
Correction

Codes Administration- A reinspection fee may be assessed for each inspection or reinspection when such portion of work for which inspection is called is not complete or when corrections called for are not made. ( UBC Section 305.(g))
Correction

Codes Administration- It shall be the duty of the person doing the work authorized by a permit to notifiy the Building Inspections Division that such work is ready for inspection. (UBC Section 305.(c))
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $752.00 $752.00 Paid 11/09/1998
24 BLDG Plan Check Fees $32.50 $32.50 Paid 11/09/1998
25 Electrical Permit Fee $58.95 $58.95 Paid 11/09/1998
25 Mechanical Permit Fees $65.50 $65.50 Paid 11/09/1998
25 Plumbing Permit Fees $20.00 $20.00 Paid 11/09/1998
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home