Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
01/20/1999
|
10/29/2010
|
|
|
|
Correction
Clarify where doors numbered 1068 and 1068B are located. These doors are called out on the door schedule and do not appear on the floor plan.
|
|
Correction
Provide the UL assembly numbers for the partitions labeled: A, B, C, D, E, E1, E2, H, K, K1, and L. The fire resistiveness of each of these partitions can not be determined without the UL assembly numbers.
|
|
Correction
Clarify where the sump pit and the floor drain, located in the elevator pit, will discharge.
|
|
Correction
Justify the use of fire-treated wood to construct the speaker platforms.
|
|
Correction
The mechanical, electrical and plumbing drawings are not sealed and signed. Resubmit these drawings.
|
|
Correction
Clarify that all materials exposed within ducts or plenums will have a flame spread index of not more than 25 and a smoke-developed rating of not more than 50 per UBC Standard 42-1.
|
|
Correction
Justify why the second floor projector room should not be considered as a corridor and not be constructed as a corridor with one hour fire resistive construction.
|
|
Correction
Clarify why each roof drain does not have an overflow drain as required per the UBC.
|
|
Correction
Clarify the locations of the emergency lighting located in the corridor on the first floor and the projection room of the second floor.
|
|
Correction
Drawing number A 1.30 states that the type of construction for the proposed building is a 2A. This type of construction is not recognized by the 1991 Uniform Building Code (UBC). Please clarify the type of construction for the proposed building.
|
|
Correction
Clarify why the scullery rooms located next to the concession stands are not seperated from the rated corridors. Justify how this will comply with the 1991 UBC Section 3305.
|
|
Correction
The door labeled as 2002 is not shown on the door schedule. Please clarify.
|
|
Correction
Submit two copies of the manufacturer's specifications for the proposed projectors.
|
|
Correction
Clarify what type of projectors will be used and, if applicable, the projectors and projector rooms will be required to comply with the 1991 UBC Chapter 40.
|
|
Correction
The small handicap accessible water closets located in the women's restrooms are required to have a minumum length of 69 inches when floor mounted water closets are used. ANSI Standard per the 1991 UBC.
|
|
Correction
The doors labeled as 169A, 154 and 192, as double acting doors, are required to have a minimum 200 square inch view panel. UBC Section 3304(b)
|
|
|