Summary
B9800819
Building Permit - Commercial
Voided
MCBOB LLC
NEW COMMERCIAL
BUILD NEW THEATER
05/22/1998
07/24/1998
01/20/1999
11/08/2000
Locations
Contacts
TK ARCHITECTS, Address:106 W 11TH STREET SUITE 1900  
MCBOB LLC, Address:3200 NW OUTER RD S  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/20/1999 10/29/2010
Correction

Clarify where doors numbered 1068 and 1068B are located. These doors are called out on the door schedule and do not appear on the floor plan.
Correction

Provide the UL assembly numbers for the partitions labeled: A, B, C, D, E, E1, E2, H, K, K1, and L. The fire resistiveness of each of these partitions can not be determined without the UL assembly numbers.
Correction

Clarify where the sump pit and the floor drain, located in the elevator pit, will discharge.
Correction

Justify the use of fire-treated wood to construct the speaker platforms.
Correction

The mechanical, electrical and plumbing drawings are not sealed and signed. Resubmit these drawings.
Correction

Clarify that all materials exposed within ducts or plenums will have a flame spread index of not more than 25 and a smoke-developed rating of not more than 50 per UBC Standard 42-1.
Correction

Justify why the second floor projector room should not be considered as a corridor and not be constructed as a corridor with one hour fire resistive construction.
Correction

Clarify why each roof drain does not have an overflow drain as required per the UBC.
Correction

Clarify the locations of the emergency lighting located in the corridor on the first floor and the projection room of the second floor.
Correction

Drawing number A 1.30 states that the type of construction for the proposed building is a 2A. This type of construction is not recognized by the 1991 Uniform Building Code (UBC). Please clarify the type of construction for the proposed building.
Correction

Clarify why the scullery rooms located next to the concession stands are not seperated from the rated corridors. Justify how this will comply with the 1991 UBC Section 3305.
Correction

The door labeled as 2002 is not shown on the door schedule. Please clarify.
Correction

Submit two copies of the manufacturer's specifications for the proposed projectors.
Correction

Clarify what type of projectors will be used and, if applicable, the projectors and projector rooms will be required to comply with the 1991 UBC Chapter 40.
Correction

The small handicap accessible water closets located in the women's restrooms are required to have a minumum length of 69 inches when floor mounted water closets are used. ANSI Standard per the 1991 UBC.
Correction

The doors labeled as 169A, 154 and 192, as double acting doors, are required to have a minimum 200 square inch view panel. UBC Section 3304(b)
Fees
Paid Fees Amount Paid Owing Date Paid
24 BLDG Permit Fees $17,054.00 $17,054.00 Paid 07/24/1998
24 BLDG Plan Check Fees $304.20 $304.20 Paid 07/24/1998
25 Electrical Permit Fee $610.00 $610.00 Paid 07/24/1998
25 Mechanical Permit Fees $690.50 $690.50 Paid 07/24/1998
25 Plumbing Permit Fees $495.00 $495.00 Paid 07/24/1998
84 Water Meters $1,410.25 $1,410.25 Paid 07/24/1998
85 Water Taps $20,505.00 $20,505.00 Paid 07/24/1998
89 Sewer Tap Fees $2,820.00 $2,820.00 Paid 07/24/1998
99 Erosion Control $200.00 $200.00 Paid 07/24/1998
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home