Permit Application Status

B1001348


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001348
Building Permit - Commercial
Certificate of Occupancy
MIDWEST DIVISION LSH LLC
NEW TENANT FINISH
TENANT FINISH FOR LSMC ONCOLOGY
10/27/2010
11/19/2010
10/06/2014
02/16/2011
Locations
Contacts
METRO AIR CONDITIONING COMPANY, Address:10035 LACKMAN RD  
HMN ARCHITECTS INC, Address:7400 W 110TH ST  
FAITH TECHNOLOGIES INC, Address:11086 STRANG LINE RD  
PURDUM CONSTRUCTION, Address:400 E RIDGE BRIDGE RD STE 106  
ALL STATE MECHANICAL INC, Address:12604 N 6TH ST  
Not shown for privacy reasons.
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 01/14/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
01/14/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received January 13, 2011.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
01/14/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of a current annual inspection. Veriofied at inspection.
Installation acceptance testing
Corrective Action Required
01/14/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at occupancy inspection.
Alarm Plan Review Approved 11/30/2010
Jim Eden
Installation acceptance testing
Corrective Action Required
11/30/2010

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
Corrective Action Required
11/30/2010

Building Plan Review Rejected 11/23/2010 11/19/2010
Mike Weisenborn
Project cost
Corrective Action Required
11/17/2010

Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - The project cost provided on the application was for both projects. Provide the cost of just this tenant finish.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
11/17/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
Misc
Corrective Action Required
11/17/2010

Specifications for the electrical alterations have not been provided. Action required - Provide additional information.
Misc
Corrective Action Required
11/17/2010

Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans. Action required - Show compliance with this Article.
Misc
Corrective Action Required
11/17/2010

I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
Internal Plan Review (Res) Approved 11/18/2010
Mike Weisenborn
Building Plan Review Approved 11/08/2010 11/18/2010
Mike Weisenborn
Project cost
Resolved
11/18/2010

Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - The project cost provided on the application was for both projects. Provide the cost of just this tenant finish.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
11/18/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
Misc
Resolved
11/18/2010

Specifications for the electrical alterations have not been provided. Action required - Provide additional information.
Misc
Corrective Action Required
11/18/2010

Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans. Action required - This will be verified on inspection.
Misc
Resolved
11/18/2010

I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
Fire Plan Review Approved 11/23/2010 11/18/2010
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
11/17/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Address numbers required
Corrective Action Required
11/17/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Suite numbers and identification shall be provided on both doors going to the public cooridor.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
11/17/2010

Building Plan Review Rejected 11/08/2010 11/18/2010
Mike Weisenborn
Project cost
Corrective Action Required
11/02/2010

Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - The project cost provided on the application was for both projects. Provide the cost of just this tenant finish.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
11/08/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
Misc
Corrective Action Required
11/08/2010

Specifications for the electrical alterations have not been provided. Action required - Provide additional information.
Misc
Corrective Action Required
11/08/2010

Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans. Action required - Show compliance with this Article.
Misc
Corrective Action Required
11/08/2010

I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
Internal Plan Review (Res) Rejected 11/08/2010 11/08/2010
Mike Weisenborn
Zoning Review Approved 11/08/2010 11/03/2010
Mike Weisenborn
Fire Plan Review Rejected 11/08/2010 11/01/2010
Jim Eden
Fire-resistant-rated construction - Maintenance
Corrective Action Required
11/01/2010

Construction documents - Fire protection systems
Corrective Action Required
11/01/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Address numbers required
Corrective Action Required
11/01/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Suite numbers and identification shall be provided on both doors going to the public cooridor.
Corrective Action Required
11/01/2010

Fire Department- Provide shop drawings for extension of fire alarm notification appliances into the space from the existing building system.
Resolved
11/22/2010

Fire Department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Provide emergency lighting in the space or indicate which lights are on emegency power.
Portable fire extinguishers - general
Corrective Action Required
11/01/2010

.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $527.52 $527.52 Paid 11/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 12/3/2010 at 12:00 AM 12/03/2010
Misc
Corrective Action Required
12/03/2010
- WAITING ROOM - MISSING OUTLET
Misc
Corrective Action Required
12/03/2010
- OKAY TO INSULATE & SHEETROCK - EXCEPT EAST WALL OF WAITING ROOM
All Rough Inspection - Commercial Passed 12/07/2010
Misc
Resolved
12/07/2010
- WAITING ROOM - MISSING OUTLET
Misc
Resolved
12/07/2010
- OKAY TO INSULATE & SHEETROCK - EXCEPT EAST WALL OF WAITING ROOM
Above Ceiling Inspection Passed 1/3/2011 at 12:00 AM 01/03/2011
Alarm Test Passed 1/17/2011 at 12:00 AM 02/07/2011
Occupancy Inspection - Fire Passed 2/7/2011 at 12:00 AM 02/07/2011
Occupancy Inspection - Codes Commercial Temporary C of O 2/7/2011 at 12:00 AM 02/07/2011
Misc
Corrective Action Required
02/07/2011
- SERVICE PANEL LABELING - LABEL BREAKERS TO MATCH ROOM NUMBERS
Occupancy Inspection - Codes Commercial Full C of O 2/16/2011 at 12:00 AM 02/16/2011
Misc
Resolved
02/16/2011
- SERVICE PANEL LABELING - LABEL BREAKERS TO MATCH ROOM NUMBERS
Documents & Images
Date Uploaded File Type Document Name
11/03/2010 Letter Plan Review Conditions
11/03/2010 Letter Plan Review Conditions
11/03/2010 Letter Plan Review Conditions
11/03/2010 Letter Plan Review Conditions
11/03/2010 Letter Plan Review Conditions
11/03/2010 Letter Plan Review Conditions
11/08/2010 Letter Plan Review Conditions
11/19/2010 Letter Building Permit
12/03/2010 Letter Inspection Summary
12/07/2010 Letter Inspection Summary
01/03/2011 Letter Inspection Summary
02/07/2011 Letter Fire Loss Reduction Form
02/07/2011 Letter Temporary Certificate of Occupancy
02/07/2011 Letter Temporary Certificate of Occupancy
02/16/2011 Letter Field Certificate of Occupancy
03/30/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire (Alarm) Plan Review Notice
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home