Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
|
01/14/2011
|
|
Jim Eden
|
|
Misc
Corrective Action Required
See Sprinkler Review Plan for B1001348.
|
|
|
Fire Plan Review
|
Approved
|
11/08/2010
|
11/22/2010
|
|
Jim Eden
|
|
Misc
Corrective Action Required
901.2 Construction documents.
The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required:Provide sprinkler system and alarm system shop drawings for review and approval.
|
|
Address numbers required
Corrective Action Required
Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: Show suite number s on all doors to public corridors.
|
|
Portable fire extinguishers - general
Corrective Action Required
Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher in the space in a conspicuous location.
|
|
Misc
Fire Department- 2006 IFC 1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Action required: Show where the lighting is being provided.
Fixtures to be connected to emergency generator.
|
|
|
Internal Plan Review (Res)
|
Approved
|
|
11/18/2010
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
11/23/2010
|
11/18/2010
|
|
Mike Weisenborn
|
|
Project cost
Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the cost of this tenant space.
|
|
Misc
I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
|
|
Accessibility - Lavatories and sinks - Clear floor space
Codes Administration - ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.)
Action required - This requirement is not met for the sink in Toilet 255. Make needed corrections.
|
|
Misc
ICC/ANSI A117.1-2003 - Maneuvering clearance at doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear floor space is not provided on the push side of door 254. The sink can not be located in the clear space. Make needed corrections.
|
|
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
|
|
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space.
Action required - This comment is for information purposes.
|
|
Misc
Specifications for the electrical installation have not been provided. Action required - Provide addtional information.
|
|
Misc
Corrective Action Required
Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans.
Action required - This will be verified on inspection
|
|
|
Fire Plan Review
|
Approved
|
11/08/2010
|
11/18/2010
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
901.2 Construction documents.
The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required:Provide sprinkler system and alarm system shop drawings for review and approval.
|
|
Address numbers required
Corrective Action Required
Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required: Show suite number s on all doors to public corridors.
|
|
Portable fire extinguishers - general
Corrective Action Required
Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required: Provide a minimum of one 2A:10B:C fire extinguisher in the space in a conspicuous location.
|
|
|
Zoning Review
|
Approved
|
11/23/2010
|
11/17/2010
|
|
Mike Weisenborn
|
|
|
Alarm Plan Review
|
Approved
|
|
11/16/2010
|
|
Jim Eden
|
|
|
Internal Plan Review (Res)
|
Rejected
|
11/08/2010
|
11/08/2010
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
11/08/2010
|
11/08/2010
|
|
Mike Weisenborn
|
|
Project cost
Corrective Action Required
Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the cost of this tenant space.
|
|
Misc
Plans for the mechanical, electrical and plumbing alterations have not been provided. Action required - Provide plans for the mechanical, electrical and plumbing work.
|
|
Misc
Corrective Action Required
I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
|
|
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
Codes Administration - ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - This requirement is not met for the sink in Toilet 255. Make needed corrections.
|
|
Misc
Corrective Action Required
ICC/ANSI A117.1-2003 - Maneuvering clearance at doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear floor space is not provided on the push side of door 254. The sink can not be located in the clear space. Make needed corrections.
|
|
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
|
|
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
|
|
Misc
Corrective Action Required
Specifications for the electrical installation have not been provided. Action required - Provide addtional information.
|
|
Misc
Corrective Action Required
Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans. Action required - Show compliance with this Article.
|
|
|