Permit Application Status

B1001347


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001347
Building Permit - Commercial
Certificate of Occupancy
MIDWEST DIVISION LSH LLC
NEW TENANT FINISH
Tenant finish for Pain Managment Suite and Ortho Exam Rooms 4 and 5, storage room and hall.
10/27/2010
11/19/2010
10/18/2014
01/27/2011
Locations
Contacts
METRO AIR CONDITIONING COMPANY, Address:10035 LACKMAN RD  
PURDUM CONSTRUCTION, Address:400 E RIDGE BRIDGE RD STE 106  
HMN ARCHITECTS INC, Address:7400 W 110TH ST  
FAITH TECHNOLOGIES INC, Address:11086 STRANG LINE RD  
ALL STATE MECHANICAL INC, Address:12604 N 6TH ST  
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 01/14/2011
Jim Eden
Misc
Corrective Action Required
01/14/2011

See Sprinkler Review Plan for B1001348.
Fire Plan Review Approved 11/08/2010 11/22/2010
Jim Eden
Misc
Corrective Action Required
11/03/2010

901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required:Provide sprinkler system and alarm system shop drawings for review and approval.
Address numbers required
Corrective Action Required
11/03/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: Show suite number s on all doors to public corridors.
Portable fire extinguishers - general
Corrective Action Required
11/03/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher in the space in a conspicuous location.
Misc
Resolved
11/16/2010

Fire Department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Show where the lighting is being provided. Fixtures to be connected to emergency generator.
Internal Plan Review (Res) Approved 11/18/2010
Mike Weisenborn
Building Plan Review Approved 11/23/2010 11/18/2010
Mike Weisenborn
Project cost
Resolved
11/18/2010

Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the cost of this tenant space.
Misc
Resolved
11/18/2010

I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
Accessibility - Lavatories and sinks - Clear floor space
Resolved
11/18/2010

Codes Administration - ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - This requirement is not met for the sink in Toilet 255. Make needed corrections.
Misc
Resolved
11/18/2010

ICC/ANSI A117.1-2003 - Maneuvering clearance at doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear floor space is not provided on the push side of door 254. The sink can not be located in the clear space. Make needed corrections.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
11/18/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
11/17/2010

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Resolved
11/18/2010

Specifications for the electrical installation have not been provided. Action required - Provide addtional information.
Misc
Corrective Action Required
11/17/2010

Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans. Action required - This will be verified on inspection
Fire Plan Review Approved 11/08/2010 11/18/2010
Mike Weisenborn
Misc
Corrective Action Required
11/18/2010

901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required:Provide sprinkler system and alarm system shop drawings for review and approval.
Address numbers required
Corrective Action Required
11/18/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: Show suite number s on all doors to public corridors.
Portable fire extinguishers - general
Corrective Action Required
11/18/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher in the space in a conspicuous location.
Zoning Review Approved 11/23/2010 11/17/2010
Mike Weisenborn
Alarm Plan Review Approved 11/16/2010
Jim Eden
Internal Plan Review (Res) Rejected 11/08/2010 11/08/2010
Mike Weisenborn
Building Plan Review Rejected 11/08/2010 11/08/2010
Mike Weisenborn
Project cost
Corrective Action Required
11/01/2010

Codes Administration - The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the cost of this tenant space.
Misc
Resolved
11/08/2010

Plans for the mechanical, electrical and plumbing alterations have not been provided. Action required - Provide plans for the mechanical, electrical and plumbing work.
Misc
Corrective Action Required
11/08/2010

I am unable to locate information on the door hardware to be installed. Action required - Provide additional information.
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
11/08/2010

Codes Administration - ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - This requirement is not met for the sink in Toilet 255. Make needed corrections.
Misc
Corrective Action Required
11/08/2010

ICC/ANSI A117.1-2003 - Maneuvering clearance at doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear floor space is not provided on the push side of door 254. The sink can not be located in the clear space. Make needed corrections.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
11/08/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - The reception counter does not meet this requirement. Make needed corrections.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
11/08/2010

Codes Administration - ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Corrective Action Required
11/08/2010

Specifications for the electrical installation have not been provided. Action required - Provide addtional information.
Misc
Corrective Action Required
11/08/2010

Compliance with Article 517 of the 2005 National Electrical Code for electrical in patient care areas is not shown on the plans. Action required - Show compliance with this Article.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,011.08 $1,011.08 Paid 11/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 12/7/2010 at 12:00 AM 11/24/2010
Misc
Resolved
12/07/2010
- WAITING ROOM 240 - NOT READY - OKAY TO ROCK OUTSIDE OF WALLS OF ROOM 240. OKAY TO INSULATE & ROCK REMAINING AREA
In-wall Inspection Passed 11/24/2010 at 12:00 AM 11/24/2010
All Rough Inspection - Commercial Passed 12/7/2010 at 12:00 AM 12/07/2010
Above Ceiling Inspection Failed 12/22/2010 at 12:00 AM 12/22/2010
Misc
Corrective Action Required
12/22/2010
- OPEN J-BOX - AT INTERSECTION OF CORRIDORS 241B & 241D
Misc
Corrective Action Required
12/22/2010
- ROOMS 243, 244 & 257 - 2'X4' LIGHT FIXTURES MUST BE SUPPORTED AT EACH END AT OPPOSITE CORNERS.
Above Ceiling Inspection Passed 12/27/2010 at 12:00 AM 12/27/2010
Misc
Resolved
12/27/2010
- OPEN J-BOX - AT INTERSECTION OF CORRIDORS 241B & 241D
Misc
Resolved
12/27/2010
- ROOMS 243, 244 & 257 - 2'X4' LIGHT FIXTURES MUST BE SUPPORTED AT EACH END AT OPPOSITE CORNERS.
Occupancy Inspection - Codes Commercial Failed 1/14/2011 at 12:00 AM 01/14/2011
Misc
Corrective Action Required
01/14/2011
- RM 246 - GFCI INOP
Misc
Corrective Action Required
01/14/2011
- BATHROOMS - INSTALL SIGNAGE
Misc
Corrective Action Required
01/14/2011
- ROOMS NOT NUMBERED TO MATCH PANEL SCHEDULE
Misc
Corrective Action Required
01/14/2011
- PROVIDE CITY APPROVED PLANS FOR ELECTRICAL PANEL SCHEDULE
Occupancy Inspection - Fire Temporary C of O 01/14/2011
Resolved
01/25/2011
Resolved
01/25/2011
Resolved
01/25/2011
Alarm Test Passed 1/19/2011 at 12:00 AM 01/25/2011
Occupancy Inspection - Fire Passed 1/25/2011 at 12:00 AM 01/25/2011
Occupancy Inspection - Codes Commercial Full C of O 1/27/2011 at 12:00 AM 01/27/2011
Misc
Resolved
01/27/2011
- RM 246 - GFCI INOP
Misc
Resolved
01/27/2011
- BATHROOMS - INSTALL SIGNAGE
Misc
Resolved
01/27/2011
- ROOMS NOT NUMBERED TO MATCH PANEL SCHEDULE
Misc
Resolved
01/27/2011
- PROVIDE CITY APPROVED PLANS FOR ELECTRICAL PANEL SCHEDULE
Documents & Images
Date Uploaded File Type Document Name
11/03/2010 Letter Plan Review Conditions
11/08/2010 Letter Plan Review Conditions
11/19/2010 Letter Building Permit
11/24/2010 Letter Inspection Summary
11/24/2010 Letter Inspection Summary
12/07/2010 Letter Inspection Summary
12/22/2010 Letter Inspection Summary
12/27/2010 Letter Inspection Summary
01/14/2011 Letter Fire Loss Reduction Form
01/14/2011 Letter Inspection Summary
01/14/2011 Letter Inspection Summary
01/14/2011 Letter Inspection Summary
01/14/2011 Letter Inspection Summary
01/25/2011 Letter Fire Loss Reduction Form
01/27/2011 Letter Field Certificate of Occupancy
01/27/2011 Letter Field Certificate of Occupancy
01/28/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home