Permit Application Status

B1001327


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001327
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
Full tenant finish in existing white box. Self serve yogurt.
10/25/2010
11/19/2010
05/04/2011
01/05/2011
Locations
Contacts
PKC CONSTRUCTION , Address:520 WEST 103RD ST STE 299, Phone:(913) 390-8402  
COUNTRYSIDE HEATING AND COOLING INC, Address:5138 MERRIAM DR, Phone:(913) 538-5264  
ACCURATE HEATING & COOLING LLC, Address:112 S MAIN ST  
PEAK INC ELECTRICAL CONTRACTORS, Address:533 N LINDENWOOD DR STE B  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Approved 12/02/2010
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
12/02/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received December 1, 2010
Installation acceptance testing
Corrective Action Required
12/02/2010

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
Fire protection equipment identification
Corrective Action Required
12/02/2010

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required: All valves shall be marked to indicate the area served. Verified at inspection.
Misc
Corrective Action Required
12/02/2010

Sprinkler heads shall be adjusted as needed in the field to maintain coverage based on existing conditions. Verified at inspection.
Alarm Plan Review Approved 11/23/2010
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
11/23/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Information received November 23, 2010
Misc
Corrective Action Required
11/23/2010

Fire Department-Duct detection shall be supervisory notification only and shall not activate interior horn/strobes or be transmitted to the central station as a fire alarm. To be verified at inspection.
Internal Plan Review (Res) Approved 11/16/2010
Mike Weisenborn
Building Plan Review Approved 11/17/2010 11/16/2010
Mike Weisenborn
Bldg - Occupancy classification - General
Resolved
11/16/2010

Codes Administration - 2006 IBC 302.1 - General. Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed below. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure is proposed for a purpose that is not specifically provided for in this code, such structure shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard involved. (See 2006 IBC for list of possible occupancy types and descriptions.) Action required - Normally this would be classified as an A-2 occupancy due to the consumption of food but exceptio 1 of Section 303.1 allows the space to be classified as a be as the calculated occupant load is less than 50. The plans indicate an occupancy type of M which is retail sales. Make needed corrections.
Mech - Outdoor air required
Resolved
11/16/2010

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - The outdoor air calcs provided are based on a retail establishment but they should be based on the use of the space which is food and beverage service. Make needed corrections.
Bldg - Occupant load calculations - Areas without fixed seats
Resolved
11/16/2010

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - The occupant load calculations for the public area are based on a merchantile use. They need to be based on movable tables and chairs and fixed bench. Make corrections to the calculated occupant load and anything related to the adjusted occupant load.
Fire Plan Review Approved 11/17/2010 11/16/2010
Jim Eden
Misc
Resolved
11/16/2010

Fire Department- 2006 IFC A-2 Assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Night clubs Restaurants Taverns and bars The business is best classified as a restaurant and not a mercantile. Action required: Recalculate the occupant load for the the space based on the most appropriate use and make changes accordingly. Per the 2006 IFC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Occupant load for the dining area is calculated at 46 and will be posted as such.
Construction documents - Fire protection systems
Corrective Action Required
11/09/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
11/09/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.Action required: Provide shop drawings for review and approval.
Address numbers required
Resolved
11/16/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Installation acceptance testing
Resolved
11/16/2010

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule testing.
Portable fire extinguishers - general
Resolved
11/16/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher and place it in a conspicuous location.
Posting of occupant load
Resolved
11/16/2010

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Post the occupant load.
Internal Plan Review (Res) Rejected 11/04/2010 11/05/2010
Mike Weisenborn
Fire Plan Review Rejected 11/04/2010 11/04/2010
Jim Eden
Misc
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC A-2 Assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Night clubs Restaurants Taverns and bars The business is best classified as a restaurant and not a mercantile. Action required: Recalculate the occupant load for the the space based on the most appropriate use and make changes accordingly. Per the 2006 IFC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Construction documents - Fire protection systems
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.Action required: Provide shop drawings for review and approval.
Address numbers required
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Installation acceptance testing
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule testing.
Portable fire extinguishers - general
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher and place it in a conspicuous location.
Posting of occupant load
Corrective Action Required
11/04/2010

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Post the occupant load.
Building Plan Review Rejected 11/04/2010 11/03/2010
Mike Weisenborn
Bldg - Occupancy classification - General
Corrective Action Required
11/03/2010

Codes Administration - 2006 IBC 302.1 - General. Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed below. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure is proposed for a purpose that is not specifically provided for in this code, such structure shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard involved. (See 2006 IBC for list of possible occupancy types and descriptions.) Action required - Normally this would be classified as an A-2 occupancy due to the consumption of food but exceptio 1 of Section 303.1 allows the space to be classified as a be as the calculated occupant load is less than 50. The plans indicate an occupancy type of M which is retail sales. Make needed corrections.
Mech - Outdoor air required
Corrective Action Required
11/03/2010

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - The outdoor air calcs provided are based on a retail establishment but they should be based on the use of the space which is food and beverage service. Make needed corrections.
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
11/03/2010

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - The occupant load calculations for the public area are based on a merchantile use. They need to be based on movable tables and chairs and fixed bench. Make corrections to the calculated occupant load and anything related to the adjusted occupant load.
Zoning Review Approved 11/04/2010 11/01/2010
Mike Weisenborn
Per Hector Soto
License Tax Codes Approved 11/04/2010 11/01/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $329.70 $329.70 Paid 11/19/2010
8331507-Sewer Connection Fee $210.00 $210.00 Paid 11/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 11/24/2010 at 12:00 AM 11/24/2010
In-wall Inspection Partial 12/2/2010 at 12:00 AM 12/02/2010
Misc
Partial Correction
12/02/2010
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS: EXCLUDING SOUTH RETAINING WALL, WEST WALL @ DOOR #2, & ANY PLUMBING WALLS
In-wall Inspection Partial 12/3/2010 at 12:00 AM 12/03/2010
Misc
Partial Correction
12/02/2010
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS: ALL EXCEPT WEST 8' OF SOUTH RETAINING WALL & WEST WALL @ DOOR #2
Gas Piping Inspection - Commercial Failed 12/07/2010
Misc
Corrective Action Required
12/07/2010
- PIPING INCOMPLETE TO APPLIANCE. COMPLETE PIPING TO ONE (1) SHORT OF THE APPLIANCE
Gas Service Inspection - Commercial Failed 12/7/2010 at 12:00 AM 12/07/2010
Misc
Corrective Action Required
12/07/2010
- SEE GAS PIPING INSPECTION
Rough Electrical Inspection - Commercial Not Ready 12/8/2010 at 12:00 AM 12/08/2010
Rated Assembly Inspection Failed 12/8/2010 at 12:00 AM 12/08/2010
Misc
Corrective Action Required
12/08/2010
-SCREW PATTERN IS REQUIRED TO BE 8" AT EDGES PER UL 465 1 HR WALL -FIRECAULK ALL PENETRATIONS. CUT OFF INSULATION AROUND WATER PIPE AND FIRECAULK MEMBRANE PENETRATION. GAPS BETWEEN TRACK AND ROOF DECK-FILL WITH GLASS FIBER AND FIRECAULK. -INSTALL APPROVED ELECTRICAL BOX FOR LOW-VOLTAGE
Rated Assembly Inspection Partial 12/9/2010 at 12:00 AM 12/09/2010
Misc
Partial Correction
12/09/2010
-SCREW PATTERN PER UL 465 TENANT SEPARATION WALL-OK
Rough Electrical Inspection - Commercial Partial 12/9/2010 at 12:00 AM 12/09/2010
Misc
Resolved
12/29/2010
-CEILING OK TO COVER: CEILING ABOVE SERVING BAR
Gas Service Inspection - Commercial Not Ready 12/10/2010 at 12:00 AM 12/10/2010
Misc
Corrective Action Required
12/07/2010
- SEE GAS PIPING INSPECTION
Gas Piping Inspection - Commercial Not Ready 12/10/2010 at 12:00 AM 12/10/2010
Rated Assembly Inspection Not Ready 12/13/2010 at 12:00 AM 12/13/2010
Misc
Corrective Action Required
12/13/2010
NO RATED ASSEMBLY WORK PRESENTLY READY FOR INSPECTION
Gas Service Inspection - Commercial Passed 12/13/2010 at 12:00 AM 12/13/2010
Misc
Corrective Action Required
12/10/2010
- SEE GAS PIPING INSPECTION
Gas Piping Inspection - Commercial Partial 12/13/2010 at 12:00 AM 12/13/2010
Misc
Resolved
12/13/2010
Misc
Partial Correction
12/13/2010
PIPING SUBJECT TO FURTHER INSPECTION WHEN NOT COVERED WITH SNOW; PIPING YET TO BE PAINTED BEFORE FINAL INSPECTION; BLOCK CLAMPS TOO LOOSE TO PREVENT BLOCKS FROM DRIFTING
In-wall Inspection Partial 12/15/2010 at 12:00 AM 12/15/2010
Misc
Partial Correction
12/03/2010
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS INCLUDING WEST 8' OF SOUTH RETAINING WALL & WEST WALL @ DOOR #2
Rated Assembly Inspection Partial 12/15/2010 at 12:00 AM 12/15/2010
Misc
Resolved
12/15/2010
NO RATED ASSEMBLY WORK PRESENTLY READY FOR INSPECTION
Misc
Partial Correction
12/15/2010
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED ASSEMBLY: GWB ENCLOSURES FOR ELECTRICAL PANELS AT RATED WALLS; REPAIR OF CORRIDOR FACE OF RATED CORRIDOR WALL ADJACENT TO EGRESS DOOR;
Rated Assembly Inspection Passed 12/20/2010 at 12:00 AM 12/20/2010
Misc
Resolved
12/20/2010
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED ASSEMBLY: GWB ENCLOSURES FOR ELECTRICAL PANELS AT RATED WALLS; REPAIR OF CORRIDOR FACE OF RATED CORRIDOR WALL ADJACENT TO EGRESS DOOR; 5/8" TYPE X GWB @ INSIDE FACE OF CORRIDOR WALL ADJACENT TO EGRESS DOOR & SOUTH DEMISING WALL AROUND ELECT PANELS OK TO TAPE, MUD, AND FIRE-SEAL
In-wall Inspection Passed 12/20/2010 at 12:00 AM 12/20/2010
Misc
Resolved
12/20/2010
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS INCLUDING WEST 8' OF SOUTH RETAINING WALL & WEST WALL @ DOOR #2
Above Ceiling Inspection Partial 12/22/2010 at 12:00 AM 12/22/2010
Misc
Partial Correction
12/22/2010
OK TO COVER WHEN READY ACT CEILING EXCEPT BELOW ROOF DRAIN PIPING PENETRATION OF RATED DEMISING WALL
Electrical Service Inspection Passed 12/27/2010 at 12:00 AM 12/27/2010
Alarm Test Passed 12/28/2010 at 12:00 AM 12/28/2010
Above Ceiling Inspection Passed 12/29/2010 at 12:00 AM 12/29/2010
Misc
Resolved
12/29/2010
OK TO COVER WHEN READY ACT CEILING EXCEPT BELOW ROOF DRAIN PIPING PENETRATION OF RATED DEMISING WALL
Rated Assembly Inspection Passed 12/29/2010 at 12:00 AM 12/29/2010
Misc
Resolved
12/29/2010
OK TO COVER WHEN READY FOLLOWING COMPONENTS OF RATED ASSEMBLY: GWB ENCLOSURES FOR ELECTRICAL PANELS AT RATED WALLS; REPAIR OF CORRIDOR FACE OF RATED CORRIDOR WALL ADJACENT TO EGRESS DOOR; 5/8" TYPE X GWB @ INSIDE FACE OF CORRIDOR WALL ADJACENT TO EGRESS DOOR & SOUTH DEMISING WALL AROUND ELECT PANELS OK TO TAPE, MUD, AND FIRE-SEAL
Rough Electrical Inspection - Commercial Passed 12/29/2010 at 12:00 AM 12/29/2010
Occupancy Inspection - Codes Commercial Not Ready 12/29/2010 at 12:00 AM 12/29/2010
Misc
Corrective Action Required
12/29/2010
REQUEST FOR INSPECTION CANCELLED BY G.C.
Gas Piping Inspection - Commercial Passed 01/03/2011
Misc
Resolved
01/03/2011
Occupancy Inspection - Codes Commercial Failed 1/3/2011 at 12:00 AM 01/03/2011
Misc
Resolved
01/03/2011
REQUEST FOR INSPECTION CANCELLED BY G.C.
Misc
Corrective Action Required
01/03/2011
LOCATION OF WATER CLOSET FLUSH CONTROL NOT ON OPEN SIDE OF WATER CLOSET: ANSI/ICC 604.6
Misc
Corrective Action Required
01/03/2011
AFFIX SUITE # TO RTU (4" MINIMUM CHARACTERS)
Misc
Corrective Action Required
01/03/2011
SPACING OF ROOFTOP GAS PIPING SUPPORTS: SOME EXCEED 10' MAX; SUPPORT 90's AND JOINTS WITHIN 2'
Misc
Corrective Action Required
01/03/2011
ROOFTOP GAS PIPING DIRT LEG CAP MUST BE READILY REMOVABLE
Misc
Corrective Action Required
01/03/2011
CLEAR ALL UNUSED MATERIAL AND DEBRIS FROM ROOFTOP
Misc
Corrective Action Required
01/03/2011
ELECTRICAL TRANSFORMER HUNG FROM ROOF JOISTS CONTRARY TO DRAWINGS; OBTAIN WRITTEN STATEMENT FROM A/E ATTESTING TO STRUCTURAL ADAQUACY.
Occupancy Inspection - Fire Passed 1/3/2011 at 12:00 AM 01/03/2011
Occupancy Inspection - Codes Commercial Failed 1/4/2011 at 12:00 AM 01/04/2011
Misc
Resolved
01/04/2011
LOCATION OF WATER CLOSET FLUSH CONTROL NOT ON OPEN SIDE OF WATER CLOSET: ANSI/ICC 604.6
Misc
Resolved
01/04/2011
AFFIX SUITE # TO RTU (4" MINIMUM CHARACTERS)
Misc
Resolved
01/04/2011
SPACING OF ROOFTOP GAS PIPING SUPPORTS: SOME EXCEED 10' MAX; SUPPORT 90's AND JOINTS WITHIN 2'
Misc
Resolved
01/04/2011
ROOFTOP GAS PIPING DIRT LEG CAP MUST BE READILY REMOVABLE
Misc
Resolved
01/04/2011
CLEAR ALL UNUSED MATERIAL AND DEBRIS FROM ROOFTOP
Misc
Corrective Action Required
01/04/2011
A/E LETTER REQUIRED ATTESTING TO ADEQUACY OF ROOF STRUCTURE TO SUPPORT ELECTRICAL TRANSFORMER.
Occupancy Inspection - Codes Commercial Full C of O 1/5/2011 at 12:00 AM 01/05/2011
Documents & Images
Date Uploaded File Type Document Name
11/04/2010 Letter Plan Review Conditions
11/04/2010 Letter Plan Review Conditions
11/04/2010 Letter Plan Review Conditions
11/05/2010 Letter Plan Review Conditions
11/19/2010 Letter Building Permit
11/23/2010 Letter Fire (Alarm) Plan Review Notice
11/24/2010 Letter Inspection Summary
12/02/2010 Letter Inspection Summary
12/03/2010 Letter Inspection Summary
12/07/2010 Letter Inspection Summary
12/07/2010 Letter Inspection Summary
12/08/2010 Letter Inspection Summary
12/09/2010 Letter Inspection Summary
12/13/2010 Letter Inspection Summary
12/15/2010 Letter Inspection Summary
12/20/2010 Letter Inspection Summary
12/22/2010 Letter Inspection Summary
12/27/2010 Letter Inspection Summary
12/29/2010 Letter Inspection Summary
12/29/2010 Letter Inspection Summary
01/03/2011 Letter Inspection Summary
01/03/2011 Letter Fire Loss Reduction Form
01/04/2011 Letter Inspection Summary
01/05/2011 Letter Final Certificate of Occupancy
01/06/2011 Letter Final Certificate of Occupancy
01/06/2011 Letter Final Certificate of Occupancy
01/06/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Plan Review Conditions
06/27/2013 Letter Fire Loss Reduction Form
08/21/2013 Letter Inspection Summary
08/27/2013 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home