Permit Application Status

B1001313


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001313
Building Permit - Commercial
Final Completion
SAINT LUKES EAST HOSPITAL
ALTERATION COMMERCIAL
Expanding OB by relocating security doors.
10/22/2010
11/04/2010
11/29/2010
Locations
Contacts
ACI BOLAND - KANSAS CITY, Address:1421 E 104TH STREET  
J E DUNN CONSTRUCTION, Address:1001 LOCUST  
SHAW ELECTRIC COMPANY, Address:3600 FULLER AVE  
SAINT LUKES EAST HOSPITAL, Address:100 NW SAINT LUKES BOULEVARD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/02/2010
Mike Weisenborn
Building Plan Review Approved 11/03/2010 11/02/2010
Mike Weisenborn
Fire Plan Review Approved 11/03/2010 11/02/2010
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
11/02/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required - Provide shop drawings.
Installation acceptance testing
Corrective Action Required
11/02/2010

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required - Call (816) 969-1300 to schedule testing.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
11/02/2010

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Action required - This comment is for information purposes.
Misc
Corrective Action Required
11/02/2010

Fire Department- 2006 IFC 1008.1.3.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. Action required - The use of access controlled doors shall meet the above requirements.
Historical Preservation Review Approved 11/03/2010 11/02/2010
Mike Weisenborn
License Tax Codes Approved 11/03/2010 11/02/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $214.44 $214.44 Paid 11/04/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Partial 11/10/2010 at 12:00 AM 11/10/2010
Misc
Partial Correction
11/10/2010
JAMB ANCHORING & SETTING OF FRAME FOR DOOR 2A097 APPROVED
Above Ceiling Inspection Partial 11/10/2010
Misc
Partial Correction
11/10/2010
ACT GRID + ABOVE-CEILING WORK AT NEW DOOR 2A097 APPROVED
Alarm Test Passed 11/24/2010 at 12:00 AM 11/24/2010
Occupancy Inspection - Fire Passed 11/30/2010 at 12:00 AM 11/30/2010
Above Ceiling Inspection Passed 12/1/2010 at 12:00 AM 12/01/2010
All Rough Inspection - Commercial Partial 11/24/2010 12/01/2010
All Rough Inspection - Commercial Passed 12/1/2010 at 12:00 AM 12/01/2010
Rough Framing Inspection - Commercial Passed 12/1/2010 at 12:00 AM 12/01/2010
Misc
Partial Correction
11/10/2010
JAMB ANCHORING & SETTING OF FRAME FOR DOOR 2A097 APPROVED
Final Inspection - Commercial Passed 12/2/2010 at 12:00 AM 12/02/2010
Documents & Images
Date Uploaded File Type Document Name
11/02/2010 Letter Plan Review Conditions
11/04/2010 Letter Building Permit
11/04/2010 Letter Plan Review Conditions
11/10/2010 Letter Inspection Summary
11/30/2010 Letter Building Permit
11/30/2010 Letter Fire Loss Reduction Form
12/01/2010 Letter Inspection Summary
12/01/2010 Letter Inspection Summary
12/02/2010 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home