Summary
B1001302
Building Permit - Commercial
Final Completion
CHANGE OF TENANT
Change of tenant. Work covered by this permit is limited to upgrading the existing Type II hood with a Type I hood. Electrical work is under permit B1001325.
10/20/2010
11/18/2010
04/30/2011
12/28/2010
Locations
Contacts
HBT INDUSTRIES, Address:1830 JASPER  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/18/2010
Codes Admin
Sprinkler Plan Review Approved 11/12/2010
Jim Eden
Fire Plan Review Approved 11/01/2010 11/09/2010
Jim Eden
Type I hood - Where required
Resolved
11/09/2010

Fire Department- 2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action required - Provide plans for the fire suppression component of the hood. 904.11 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry- and wet-chemical extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with this code, its listing and the manufacturer’s installation instructions. Automatic fire-extinguishing systems of the following types shall be installed in accordance with the referenced standard indicated, as follows: 5. Wet-chemical extinguishing systems, NFPA 17A. Exception: Factory-built commercial cooking recirculating systems that are tested in accordance with UL 710B and listed, labeled and installed in accordance with Section 304.1 of the International Mechanical Code.
Misc
Resolved
11/09/2010

Fire Department- 2006 IFC 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. Action Required - Show the location of the manual pull station.
Installation acceptance testing
Corrective Action Required
11/01/2010

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required - Call (816) 969-1300 to schedule a test of the hood system.
Portable fire extinguishers for commercial cooking equipment.
Resolved
11/09/2010

Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action required - Locate a K-class fire extinguisher under the manual pull station for the hood.
Misc
Corrective Action Required
11/01/2010

Fire Department- 2006 IFC 904.11.2 System interconnection. The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual. Action required - For information only. Verified at test.
Internal Plan Review (Res) Rejected 11/01/2010
Mike Weisenborn
Building Plan Review Rejected 11/01/2010 11/01/2010
Mike Weisenborn
Misc
Corrective Action Required
11/01/2010

2006 IMC Section 507.9 - A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches. Action required - Provide an architectural plan showing the layout of the area where the hood is to be installed. The plan shall provide details for the the construction of any walls or ceilings located within 18 inches of the hood to show compliance with this section.
Bldg - Posting of occupant load
Corrective Action Required
11/01/2010

Codes Administration - 2003 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required - This will be verified on inspection.
Misc
Corrective Action Required
11/01/2010

2006 IMC - Section 506.3.6 - Grease duct clearances. Grease duct systems and exhaust equipment serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches, and shall have a clearance to noncombustible construction and qypsum wallboard attached to noncombustible structures of not less than 3 inches. Action required - This will be verified on inspection.
Misc
Corrective Action Required
11/01/2010

Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit. Action required - Provide documentation of approval prior to permit issuance.
Misc
Corrective Action Required
11/01/2010

Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy. Action required - This comment is for information purposes.
License Tax Codes Approved 11/01/2010 11/01/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $40.85 $40.85 Paid 11/18/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Hood/Duct Inspection Failed 11/19/2010 at 12:00 AM 11/19/2010
M506 COMMERCIAL KITCHEN HOOD VENT. SYSTEM DUCTS AND EXHAUST EQUIPMENT
Corrective Action Required
11/19/2010
- REMOVE VENT FOR INSPECTION
Hood/Duct Inspection Partial 11/19/2010
M506 COMMERCIAL KITCHEN HOOD VENT. SYSTEM DUCTS AND EXHAUST EQUIPMENT
Partial Correction
11/19/2010
- SHOP WELDS INSPECTED. - FIELD WELDS TO BE INSPECTED FOLLOWING INSTALLATION
Hood/Duct Inspection Passed 11/22/2010 at 12:00 AM 11/22/2010
M506 COMMERCIAL KITCHEN HOOD VENT. SYSTEM DUCTS AND EXHAUST EQUIPMENT
Resolved
11/22/2010
- SHOP WELDS INSPECTED. - FIELD WELDS TO BE INSPECTED FOLLOWING INSTALLATION
Final Mechanical Inspection Passed 12/8/2010 at 12:00 AM 12/08/2010
Documents & Images
Date Uploaded File Type Document Name
11/01/2010 Letter Plan Review Conditions
11/18/2010 Letter Building Permit
11/19/2010 Letter Inspection Summary
11/22/2010 Letter Inspection Summary
12/08/2010 Letter Inspection Summary
05/10/2012 Letter Fire Loss Reduction Form
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home