Permit Application Status

B1001151


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001151
Building Permit - Commercial
Certificate of Occupancy
LS INVESTORS ONE LLC
NEW TENANT FINISH
TENANT FINISH FOR ANY LAB TEST NOW
09/17/2010
10/04/2010
04/02/2011
01/11/2011
Locations
Contacts
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
STAR ELECTRICAL, Address:814 SW 6TH ST  
ISEMAN CONSTRUCTION ENTERPRISES, INC., Address:1270 NW MAIN  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/30/2011 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - The plans do not indicate what walls and fixtures are existing and what is new.
Correction

Codes Administration - I am unable to locate details for the wall construction.
Correction

Fire Department- The building fire sprinkler system shall have documentation of current annual inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $65.94 $65.94 Paid 10/04/2010
89 Sewer Tap Fees $30.00 $30.00 Paid 10/04/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Passed 10/05/2010
Correction
Resolved
10/05/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Occupancy Inspection - Fire Failed 11/02/2010
Corrective Action Required
11/02/2010
EXISTING SPRINKLER SYSTEM SHALL BE MODIFIED TO MAINTAIN COVERAGE PER NFPA 13
Corrective Action Required
11/02/2010
PROVIDE SHOP DRAWINGS FOR REVIEW AND APPROVAL
Occupancy Inspection - Codes Commercial Failed 11/2/2010 at 12:00 AM 11/02/2010
B1110 SIGNAGE
Corrective Action Required
11/02/2010
RESTROOM HANDICAP SIGN TO BE AFFIXED
A305.4 Knee and Toe Clearance
Corrective Action Required
11/02/2010
PADDING ON PIPING UNDER LAV TO BE INSTALLED
A404.2.7.1 Door Closers
Corrective Action Required
11/02/2010
DOORS AND DOORWAYS. Door closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to an open position of 12 degrees shall be 5 seconds minimum. RESTROOM DOOR
Misc
Corrective Action Required
11/02/2010
OBTAIN FIRE DEPARTMENT APPROVAL
Occupancy Inspection - Codes Commercial Failed 11/11/2010 at 12:00 AM 11/11/2010
B1110 SIGNAGE
Resolved
11/11/2010
RESTROOM HANDICAP SIGN TO BE AFFIXED
A305.4 Knee and Toe Clearance
Resolved
11/11/2010
PADDING ON PIPING UNDER LAV TO BE INSTALLED
A404.2.7.1 Door Closers
Corrective Action Required
11/02/2010
DOORS AND DOORWAYS. Door closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to an open position of 12 degrees shall be 5 seconds minimum. RESTROOM DOOR
Misc
Corrective Action Required
11/02/2010
OBTAIN FIRE DEPARTMENT APPROVAL
Occupancy Inspection - Fire Temporary C of O 11/11/2010 at 12:00 AM 11/11/2010
Alarm Test Failed 11/15/2010 at 12:00 AM 11/15/2010
Alarm Test Passed 11/29/2010 at 12:00 AM 11/29/2010
Occupancy Inspection - Fire Passed 11/29/2010 at 12:00 AM 11/29/2010
Occupancy Inspection - Codes Commercial Failed 1/7/2011 at 12:00 AM 01/07/2011
A404.2.7.1 Door Closers
Corrective Action Required
11/11/2010
DOORS AND DOORWAYS. Door closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to an open position of 12 degrees shall be 5 seconds minimum. RESTROOM DOOR
Misc
Resolved
01/07/2011
OBTAIN FIRE DEPARTMENT APPROVAL
Occupancy Inspection - Codes Commercial Full C of O 1/12/2011 at 12:00 AM 01/11/2011
A404.2.7.1 Door Closers
Corrective Action Required
01/07/2011
DOORS AND DOORWAYS. Door closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to an open position of 12 degrees shall be 5 seconds minimum. RESTROOM DOOR
Documents & Images
Date Uploaded File Type Document Name
11/02/2010 Letter Fire Loss Reduction Form
11/02/2010 Letter Fire Loss Reduction Form
11/02/2010 Letter Inspection Summary
11/11/2010 Letter Inspection Summary
11/30/2010 Letter Fire Loss Reduction Form
11/30/2010 Letter Fire Loss Reduction Form
01/11/2011 Letter Final Certificate of Occupancy
01/13/2011 Letter Final Certificate of Occupancy
01/13/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home