Permit Application Status

B1001103


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001103
Building Permit - Commercial
Certificate of Occupancy
CHANGE OF TENANT
PRUTERS MARTIAL ARTS TENANT EXPANSION
09/08/2010
10/14/2010
04/20/2011
03/10/2011
Locations
Contacts
UNITED HEATING & COOLING, Address:301 DUCK RD  
CLAYCO ELECTRIC COMPANY, Address:319 E 11TH AVE  
MILLER PLUMBING CO., Address:PO BOX 393  
AMERICAN CATASTROPHE, Address:13850 WYANDOTTE  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 04/09/2011 10/29/2010
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - ICC/ANSI A117.1-2003 604.5.2 - Rear wall grab bars. The rear wall grab bar shall be 36 inches minimum in length, and extend from the centerline of the water closet 12 inches minimum on the side closest to the wall, and 24 inches minimum on the transfer side.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
Correction

Codes Administration - A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - The plans indicate that the new restroom fixtures are to be connected to the existing plumbing. It does not indicate if there waste, vent and water lines are existing for the fixtures or if connections to the trunk lines is required.
Correction

Codes Administration - Details for the construction of the new interior walls is not provided on the plans.
Correction

Codes Administration - Details for the alteration to the electrical system have not been provided.
Correction

Codes Administration - The plans do not provide information on the required exhaust in the new restroom.
Correction

Codes Administration - 2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Correction

Codes Administration - 2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

Codes Administration - 2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $35.24 $35.24 Paid 10/14/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Not Ready 10/20/2010
Correction
Corrective Action Required
10/20/2010
READINESS FOR INSPECTION IBC 109.1, 109.5: NOT READY PROPERTY LOCKED INTERIOR NOT ACCESSIBLE
All Rough Inspection - Commercial Failed 10/22/2010
Correction
Corrective Action Required
10/22/2010
INSTALL BLOCKING FOR GRAP BARS
Correction
Corrective Action Required
10/22/2010
TYPE MC CABLE -PROVIDE LISTED MC WITH OUTER SHEATHING APPROVED AS EQUIPMENT GROUNDING CONDUCTOR, INSTALLED WITH APPROVED FITTING
Correction
Corrective Action Required
10/22/2010
READINESS FOR INSPECTION -PROTECT PLUMBING AT WALL BOTTOM TRACK
Above Ceiling Inspection Partial 10/22/2010
Correction
Partial Correction
10/22/2010
None ABOVE CEILING APPROVED TO COVER BELOW: -RESTROOMS
Underslab Plumbing Inspection - Commercial Passed 10/22/2010
Correction
Resolved
10/22/2010
None UNDERSLAB PLUMBING APPROVED TO COVER BELOW: -RESTROOMS
All Rough Inspection - Commercial Partial 10/25/2010
Correction
Resolved
10/25/2010
INSTALL BLOCKING FOR GRAP BARS
Correction
Partial Correction
10/25/2010
TYPE MC CABLE BATHROOMS INSPECTION ONLY 2 RESTROOMS AND ABOVE CEILING IN RESTROOMS OK TO COVER
Correction
Resolved
10/25/2010
READINESS FOR INSPECTION
Rough Plumbing Inspection - Commercial Passed 11/12/2010
Above Ceiling Inspection Partial 11/12/2010 at 12:00 AM 11/12/2010
Correction
Partial Correction
11/11/2010
ABOVE CEILING APPROVED TO COVER BELOW: RESTROOMS; ACT CEILING EAST-WEST ELEVATION TRANSITION PROPOSAL APPROVED PROVIDED EACH PIECE OF LATERAL TRANSITION GRID IS SUPPORTED BOTH ENDS;
Above Ceiling Inspection Partial 11/15/2010 at 12:00 AM 11/15/2010
Correction
Resolved
11/15/2010
ABOVE CEILING APPROVED TO COVER BELOW: RESTROOMS; ACT CEILING EAST-WEST ELEVATION TRANSITION PROPOSAL APPROVED PROVIDED EACH PIECE OF LATERAL TRANSITION GRID IS SUPPORTED BOTH ENDS
Misc
Corrective Action Required
11/15/2010
ELECTRICAL SPLICE BOX ABOVE CEILING: SECURE TO STRUCTURE; INSTALL GROMMETS AT MC BOX ENTRY
Occupancy Inspection - Fire Temporary C of O 11/15/2010
Resolved
11/22/2010
Resolved
11/22/2010
Resolved
11/22/2010
Resolved
11/22/2010
Occupancy Inspection - Codes Commercial Temporary C of O 11/15/2010 at 12:00 AM 11/15/2010
Misc
Corrective Action Required
11/15/2010
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
11/15/2010
IDENTIFY GAS SERVICE WITH PERMANENT ADDRESS TAG HUNG ON LOAD SIDE PIPE AT METER
Misc
Corrective Action Required
11/15/2010
COMMERCIAL WATER CLOSETS REQUIRE OPEN FRONT SEATS
Misc
Corrective Action Required
11/15/2010
ADA SIGN REQUIRED AT ACCESSIBLE RESTROOM
Misc
Corrective Action Required
11/15/2010
RESOLVE WATER DEPARTMENT ISSUE(S) -- IF ANY
Occupancy Inspection - Fire Passed 11/22/2010
Above Ceiling Inspection Not Ready 3/9/2011 at 12:00 AM 03/09/2011
Misc
Corrective Action Required
11/15/2010
ELECTRICAL SPLICE BOX ABOVE CEILING: SECURE TO STRUCTURE; INSTALL GROMMETS AT MC BOX ENTRY
Occupancy Inspection - Codes Commercial Not Ready 3/9/2011 at 12:00 AM 03/09/2011
Misc
Corrective Action Required
11/15/2010
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
11/15/2010
IDENTIFY GAS SERVICE WITH PERMANENT ADDRESS TAG HUNG ON LOAD SIDE PIPE AT METER
Occupancy Inspection - Codes Commercial Full C of O 3/10/2011 at 12:00 AM 03/10/2011
Misc
Resolved
03/10/2011
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Resolved
03/10/2011
IDENTIFY GAS SERVICE WITH PERMANENT ADDRESS TAG HUNG ON LOAD SIDE PIPE AT METER
Documents & Images
Date Uploaded File Type Document Name
11/12/2010 Letter Inspection Summary
11/15/2010 Letter Inspection Summary
11/15/2010 Letter Inspection Summary
11/15/2010 Letter Fire Loss Reduction Form
11/15/2010 Letter Fire Loss Reduction Form
11/15/2010 Letter Temporary Certificate of Occupancy
11/22/2010 Letter Fire Loss Reduction Form
11/22/2010 Letter Fire Loss Reduction Form
02/16/2011 Letter 10-Day Notice of Violation
03/10/2011 Letter Final Certificate of Occupancy
03/11/2011 Letter Final Certificate of Occupancy
03/11/2011 Letter Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home