Permit Application Status

B1001011


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1001011
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
WHITE BOX FOR HEAVENLY OILS
08/20/2010
09/10/2010
04/20/2011
10/27/2010
Locations
Contacts
CAMM CONSTRUCTION INC, Address:7216 MAPEL  
UNITED HEATING & COOLING, Address:301 DUCK RD  
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
PALMER ELECTRIC, INC., Address:6600 ROYAL ST BLDG B  
STEVE THE PLUMBER, Address:601 S STELLA  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/08/2011 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

CA - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

CA - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

Codes Administration - Details for the installation of the transformer have not been provided.
Correction

Codes Administration - 2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $188.04 $188.04 Paid 09/10/2010
89 Sewer Tap Fees $120.00 $120.00 Paid 09/10/2010
0120 Building Permit Fee $62.53 $62.53 Paid 10/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 09/13/2010
Correction
Resolved
09/13/2010
None
All Rough Inspection - Commercial Passed 09/17/2010
Correction
Resolved
09/17/2010
None
Correction
Resolved
09/17/2010
None
Gas Piping Inspection - Commercial Failed 09/28/2010
Correction
Corrective Action Required
09/28/2010
Fuel Gas Listing & Labeling (IRC) LABEL METER WITH ADDRESS PAINT ROOF TOP GAS PIPING
Gas Service Inspection - Commercial Passed 09/28/2010
Correction
Resolved
09/28/2010
None
Above Ceiling Inspection Partial 10/05/2010
Correction
Partial Correction
10/05/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS SALES 101 [NOT INCLUDING VESTIBULE @ DOORS 102 & 103] REMOVAL OF TEMPORARY ELECTRICAL WIRING TO BE VERIFIED AT OR BEFORE FINAL INSPECTION OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Electrical Service Inspection Passed 10/05/2010
Correction
Resolved
10/05/2010
ELECTRICAL SERVICE INSTALLATION BEFORE SERVICE IS ACTIVATED MAKE PROVISION TO DEFLECT POTENTIAL WATER LEAK FROM COLD WATER SUPPLY LINE ABOVE TRANSFORMER. 277/480V 3P 4W 100A MLO > 30KVA XFMR > 120/208V 3P 4W 100A MCB RELEASE SERVICE CONTINGENT ON BELOW:
Above Ceiling Inspection Partial 10/06/2010
Correction
Partial Correction
10/06/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS SALES 101 [NOT INCLUDING VESTIBULE @ DOORS 102 & 103]; 103 EXCEPT FOR SOUTH 6' REMOVAL OF TEMPORARY ELECTRICAL WIRING TO BE VERIFIED AT OR BEFORE FINAL INSPECTION OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Partial 10/08/2010
Correction
Partial Correction
10/08/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS SALES 101 EXCEPT CAN LIGHT YET TO BE INSTALLED AT VESTIBULE @ DOORS 102 & 103; 103 COMPLETE OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Not Ready 10/18/2010
Correction
Corrective Action Required
10/18/2010
ELECTRICAL RECEPTACLE @ S.E. CORNER OF SALES SPACE NOT SOLID TO BOX
Correction
Corrective Action Required
10/18/2010
INSTALLATION OF LIGHTED SIGN PER NEC 600-3: SUBJECT TO NATIONAL 2005 ELECTRICAL CODE. IF INTERNALLY LIGHTED > 12V MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN. SUBJECT TO APPROVAL. WHEN INSTALLED
Correction
Corrective Action Required
10/18/2010
CONVERSION OF PERMIT FROM WHITE BOX TO FULL TENANT FINISH WHEN PERMIT IS UPGRADED AND FINISH WORK PROCEEDS. IN PROGRESS SHEDULE RE-INSPECTION
Correction
Corrective Action Required
10/18/2010
ROOFTOP GAS PIPING 1) PIPING SUPPORT BLOCK SPACING NOT PER IPC - 10" MAX 2) SUPPORT PIPE WITHIN 2' OF CONNECTIONS 3) SECURE SUPPORT BLOCK SLIP SHEETS TO BLOCKS
Correction
Corrective Action Required
10/18/2010
Receive Fire Department approval SEE REPORT PROVIDED
Above Ceiling Inspection Passed 10/18/2010
Correction
Resolved
10/18/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS
Gas Piping Inspection - Commercial Passed 10/18/2010
Correction
Resolved
10/18/2010
Fuel Gas Listing & Labeling (IRC)
Occupancy Inspection - Codes Commercial Failed 10/20/2010
Correction
Resolved
10/20/2010
ELECTRICAL RECEPTACLE @ S.E. CORNER OF SALES SPACE
Correction
Corrective Action Required
10/20/2010
INSTALLATION OF LIGHTED SIGN PER NEC 600-3: SUBJECT TO NATIONAL 2005 ELECTRICAL CODE. IF INTERNALLY LIGHTED > 12V MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN. SUBJECT TO APPROVAL. WHEN INSTALLED
Correction
Resolved
10/20/2010
CONVERSION OF PERMIT FROM WHITE BOX TO FULL TENANT FINISH COMPLETED
Correction
Resolved
10/20/2010
ROOFTOP GAS PIPING
Correction
Resolved
10/20/2010
Receive Fire Department approval CLEARED
Occupancy Inspection - Codes Commercial Passed 10/26/2010
Correction
Resolved
10/26/2010
INSTALLATION OF LIGHTED SIGN
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home