Permit Application Status

B1000995


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000995
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
NEW TENANT FINISH
NEW TENANT FINISH IN PREVIOUSLY UNOCCUPIED SPACE.
08/18/2010
01/07/2011
03/07/2011
Locations
Contacts
HOFFMAN CORTES CONTRACTING COMPANY, Address:1600 BALTIMORE, STE 102  
METRO AIR CONDITIONING , Address:8151 MCCOY ST, Phone:(913) 888-3991  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
CITY WIDE ELECTRIC INC, Address:5911 BARTON DR, Phone:(913) 631-1189  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/01/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
03/01/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received.
Misc
Corrective Action Required
03/01/2011

Per NFPA 72, provide smoke detection over the NAC power supply(BPS).
Installation acceptance testing
Corrective Action Required
03/01/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test.
Internal Plan Review (Res) Approved 01/10/2011 01/07/2011
Mike Weisenborn
CPTED Plan Review Approved 01/07/2011
Mike Weisenborn
License Tax Codes Approved 08/30/2010 11/22/2010
Mike Weisenborn
Historical Preservation Review Approved 08/30/2010 11/22/2010
Mike Weisenborn
Zoning Review Approved 08/30/2010 11/22/2010
Mike Weisenborn
Building Plan Review Approved 08/30/2010 11/22/2010
Mike Weisenborn
Misc
Corrective Action Required
11/22/2010

Planning and Development - UDO Section 7.370 - CPTED Uses Specified. The following uses have been classified as "Uses with Conditions" per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space. 1. Bank/Financial Services 2. Bank Drive-Thru Facility 3. Check Cashing and Payday Loan Business 4. Convience Store (C-Store) 5. Financial Services with Drive-up Window or Drive-Thru Facility 6. Pawn Shop 7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand 8. Unattended Self-serve gas pumps 9. Unsecured Loan Busniness 10. Other similar uses shall meet the same standards as the above. Action required - Planning and Development will be performing the review for compliance with this code requirement. Contact Planning and Development at 816-969-1600 with questions concerning these requirements.
Misc
Corrective Action Required
11/22/2010

CA - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required - Per the resubmittal letter, the escrow will be paid with the permit fee.
Misc
Resolved
11/22/2010

Codes Administration - Installation details for FC-1 and 2 have not been provided. Action required - Provide details for how FC-1 and 2 will be suspended from the floor system above. Also provide documentation that the floor system is capable of supporting the loads or what alterations are required.
Fire Plan Review Approved 08/30/2010 11/22/2010
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
11/22/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required - Provide shop drawings for review and approval.
Misc
Corrective Action Required
11/22/2010

Fire Department- 2006 IFC504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. Required fire department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 10. Access doors for high-piled combustible storage shall comply with Section 2306.6.1. Action required - Mark the door from room 114. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $703.36 $703.36 Paid 01/07/2011
9123001-Escrow Deposit $560.20 $560.20 Paid 01/07/2011
8331507-Sewer Connection Fee $210.00 $210.00 Paid 01/07/2011
9110078-Additional Permit Fee $0.03 $0.03 Paid 01/07/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 1/13/2011 at 12:00 AM 01/13/2011
All Rough Inspection - Commercial Failed 1/24/2011 at 12:00 AM 01/24/2011
P305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS
Corrective Action Required
01/24/2011
PROTECT PIPING IN WALL WITHIN 1 .5" FROM EDGE. SECURE PIPEIN WALL. 1/2 COPPER AND DWV. FOR ABOVE CEILING SUPPORT DWV 48" O.C.
Misc
Corrective Action Required
01/24/2011
DIMISING WALL- PROVIDE ACCES TO NORTH SIDE UNIT170 FOR INSPECTION ON TO INSTALL 2ND LAYER OF ROCK ON SOUTH SIDE OF WALL
B717 CONCEALED SPACES
Corrective Action Required
01/24/2011
HARD LIDS- COMPLETE INSTALLATION OF CAN LIGHTS IN CEILINGS FOR INSPECTION
All Rough Inspection - Commercial Passed 1/25/2011 at 12:00 AM 01/25/2011
P305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS
Resolved
01/25/2011
PROTECT PIPING IN WALL WITHIN 1 .5" FROM EDGE. SECURE PIPEIN WALL. 1/2 COPPER AND DWV. FOR ABOVE CEILING SUPPORT DWV 48" O.C.
Misc
Resolved
01/25/2011
DIMISING WALL- PROVIDE ACCES TO NORTH SIDE UNIT170 FOR INSPECTION ON TO INSTALL 2ND LAYER OF ROCK ON SOUTH SIDE OF WALL
B717 CONCEALED SPACES
Resolved
01/25/2011
HARD LIDS- COMPLETE INSTALLATION OF CAN LIGHTS IN CEILINGS FOR INSPECTION
Gas Service Inspection - Commercial Passed 2/15/2011 at 12:00 AM 02/15/2011
Above Ceiling Inspection Partial 2/17/2011 at 12:00 AM 02/17/2011
Misc
Corrective Action Required
02/17/2011
APPROVED TO INSTALL CEILING TILE: FRONT LOBBY AREA MISSING 8CEILING FIXTURES. TILE IS TO BE REMOVED AT FINAL OR ABOVE CEILING INSPECTION FOR INSPECTION OF 8 REMAINING FIXTURES.
Alarm Test Passed 2/24/2011 at 12:00 AM 02/24/2011
Sprinkler - Flow Test Passed 02/24/2011
Occupancy Inspection - Fire Temporary C of O 2/25/2011 at 12:00 AM 02/25/2011
Corrective Action Required
02/25/2011
Corrective Action Required
02/25/2011
Corrective Action Required
02/25/2011
Occupancy Inspection - Codes Commercial Temporary C of O 2/25/2011 at 12:00 AM 02/28/2011
Misc
Corrective Action Required
02/28/2011
-FINAL APPROVAL SUBJECT TO OUTSTANDING DEFICIENCIES (IF THERE ARE ANY) ON OTHER INSPECTIONS
Misc
Corrective Action Required
02/28/2011
-BATHROOMS 1) INSTALL 6” WALL BASE 2) EPOXY PAINT REQUIRED AROUND WATER CLOSET PER IBC CH12 3) WRAP PLUMBING UNDER SINKS
Misc
Corrective Action Required
02/28/2011
-LOCK NOT ALLOWED ON EGRESS SIDE OF DOOR (BREAK ROOM)
Misc
Corrective Action Required
02/28/2011
-COMPLETE SECURITY PER CPTED REQUIREMENTS
Misc
Corrective Action Required
02/28/2011
-SECURE FLEXIBLE METAL CONDUIT ABOVE PANEL
Misc
Corrective Action Required
02/28/2011
-OBTAIN APPROVAL FROM FIRE DEPARTMENT **TEMPORARY OCCUPANCY APPROVED FOR 30 DAYS FROM THIS DATE
Occupancy Inspection - Fire Passed 3/7/2011 at 2:00 PM 03/07/2011
Occupancy Inspection - Codes Commercial Full C of O 3/7/2011 at 12:00 AM 03/07/2011
Misc
Resolved
03/07/2011
-FINAL APPROVAL SUBJECT TO OUTSTANDING DEFICIENCIES (IF THERE ARE ANY) ON OTHER INSPECTIONS
Misc
Resolved
03/07/2011
-BATHROOMS 1) INSTALL 6” WALL BASE 2) EPOXY PAINT REQUIRED AROUND WATER CLOSET PER IBC CH12 3) WRAP PLUMBING UNDER SINKS
Misc
Resolved
03/07/2011
-LOCK NOT ALLOWED ON EGRESS SIDE OF DOOR (BREAK ROOM)
Misc
Resolved
03/07/2011
-COMPLETE SECURITY PER CPTED REQUIREMENTS
Misc
Resolved
03/07/2011
-SECURE FLEXIBLE METAL CONDUIT ABOVE PANEL
Misc
Resolved
03/07/2011
-OBTAIN APPROVAL FROM FIRE DEPARTMENT **TEMPORARY OCCUPANCY APPROVED FOR 30 DAYS FROM THIS DATE
Above Ceiling Inspection Passed 03/07/2011
Misc
Resolved
03/07/2011
HARD CEILING- APPROVED TO ROCK SOFIT AND CEILING ON RESTROOMS NEED TO INSPECT BATHFANS AND DUCTS OVER RESTROOMS- PROVIDE LADDER OR LIFT FOR INSPECTION OR ACCES
Documents & Images
Date Uploaded File Type Document Name
01/07/2011 Letter Building Permit
01/13/2011 Letter Inspection Summary
01/14/2011 Letter Fire (Sprinkler) Plan Review
01/24/2011 Letter Inspection Summary
01/25/2011 Letter Inspection Summary
02/15/2011 Letter Inspection Summary
02/17/2011 Letter Inspection Summary
02/25/2011 Letter Fire Loss Reduction Form
02/28/2011 Letter Temporary Certificate of Occupancy
03/01/2011 Letter Fire (Alarm) Plan Review Notice
03/07/2011 Letter Fire Loss Reduction Form
03/07/2011 Letter Field Certificate of Occupancy
03/08/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/21/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home