Permit Application Status

B1000962


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000962
Building Permit - Commercial
Certificate of Occupancy
CHANGE OF TENANT
NEW TENANT IN PREVIOUSLY OCCUPIED SPACE.
08/10/2010
09/15/2010
03/27/2011
12/16/2010
Locations
Contacts
DAVIDSON DESIGN GROUP, Address:11301 STRANG LINE ROAD  
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
BRIGHT PLUMBING, Address:220 NW COMMERCE CT  
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/06/2011 10/29/2010
Correction

Fire Department- 2006 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Fire Department- 2006 IFC 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. Exception: Doors, when fully opened, and handrails, shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) on each side.
Correction

Codes Administration - The drinking fountains referenced by construction note 10 on Sheet A-1 are not shown on the plumbing plans.
Correction

Codes Administration - Per footnote b of Table 403.3 of the 2006 IMC, the recirculation of air in nail salons is prohibited and all supply air must be exhausted.
Correction

Codes Administration - Per footnote i of Table 403.3 of the 2006 IMC, the required exhaust system shall capture the contaminants and odors at their source.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $183.83 $183.83 Paid 09/15/2010
89 Sewer Tap Fees $510.00 $510.00 Paid 09/15/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 09/20/2010
Correction
Resolved
09/20/2010
None
All Rough Inspection - Commercial Passed 09/29/2010
Correction
Resolved
09/29/2010
FASTENING OF CONNECTIONS OF LIGHT-GUAGE STEEL FRAMING
Correction
Resolved
09/29/2010
SECURING OF MC ELECTRICAL CABLE
Correction
Resolved
09/29/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY
Above Ceiling Inspection Passed 11/1/2010 at 12:00 AM 11/01/2010
Occupancy Inspection - Fire Passed 11/17/2010
Alarm Test Passed 11/17/2010 at 12:00 AM 11/17/2010
Occupancy Inspection - Codes Commercial Temporary C of O 11/17/2010 at 12:00 AM 11/17/2010
Misc
Corrective Action Required
11/17/2010
EXHAUST FAN #2 FOR NAIL STATION LOCAL CAPTURE EXHAUST SUBJECT TO APPROVAL WHEN INSTALLATION LOCATION IS ACCESSIBLE.
Misc
Corrective Action Required
11/17/2010
LABEL RTU TO DESIGNATE SUITE #1190
Misc
Corrective Action Required
11/17/2010
REPLACE MISSING ROOFTOP GAS PIPE SUPPORT BLOCK AT DOGLEG
Misc
Corrective Action Required
11/17/2010
HANG 1190 ADDRESS TAG ON LOAD SIDE PIPE AT GAS SERVICE ENTRY
Occupancy Inspection - Codes Commercial Temporary C of O 11/17/2010 11/17/2010 at 12:00 AM 11/17/2010
Misc
Corrective Action Required
11/17/2010
EXHAUST FAN #2 FOR NAIL STATION LOCAL CAPTURE EXHAUST SUBJECT TO APPROVAL WHEN INSTALLATION LOCATION IS ACCESSIBLE.
Misc
Corrective Action Required
11/17/2010
LABEL RTU TO DESIGNATE SUITE #1190
Misc
Corrective Action Required
11/17/2010
REPLACE MISSING ROOFTOP GAS PIPE SUPPORT BLOCK AT DOGLEG
Misc
Corrective Action Required
11/17/2010
HANG 1190 ADDRESS TAG ON LOAD SIDE PIPE AT GAS SERVICE ENTRY
Occupancy Inspection - Codes Commercial Full C of O 12/16/2010 at 12:00 AM 12/16/2010
Misc
Corrective Action Required
11/17/2010
EXHAUST FAN #2 FOR NAIL STATION LOCAL CAPTURE EXHAUST SUBJECT TO APPROVAL WHEN INSTALLATION LOCATION IS ACCESSIBLE.
Misc
Corrective Action Required
11/17/2010
LABEL RTU TO DESIGNATE SUITE #1190
Misc
Corrective Action Required
11/17/2010
REPLACE MISSING ROOFTOP GAS PIPE SUPPORT BLOCK AT DOGLEG
Misc
Corrective Action Required
11/17/2010
HANG 1190 ADDRESS TAG ON LOAD SIDE PIPE AT GAS SERVICE ENTRY
Occupancy Inspection - Codes Commercial Full C of O 12/16/2010 at 12:00 AM 12/16/2010
Misc
Resolved
12/16/2010
EXHAUST FAN #2 FOR NAIL STATION LOCAL CAPTURE EXHAUST SUBJECT TO APPROVAL WHEN INSTALLATION LOCATION IS ACCESSIBLE.
Misc
Resolved
12/16/2010
LABEL RTU TO DESIGNATE SUITE #1190
Misc
Resolved
12/16/2010
REPLACE MISSING ROOFTOP GAS PIPE SUPPORT BLOCK AT DOGLEG
Misc
Resolved
12/16/2010
HANG 1190 ADDRESS TAG ON LOAD SIDE PIPE AT GAS SERVICE ENTRY
Documents & Images
Date Uploaded File Type Document Name
11/01/2010 Letter Inspection Summary
11/17/2010 Letter Fire Loss Reduction Form
12/02/2010 Letter Temporary Certificate of Occupancy
12/16/2010 Letter Final Certificate of Occupancy
12/17/2010 Letter Final Certificate of Occupancy
08/27/2013 Letter Temporary Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home