Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/20/2011 10/29/2010
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - ICC/ANSI A117.1-2003 604.5.2 - Rear wall grab bars. The rear wall grab bar shall be 36 inches minimum in length, and extend from the centerline of the water closet 12 inches minimum on the side closest to the wall, and 24 inches minimum on the transfer side.
Correction

Codes Administration - 2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the evenet of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building requried to have two or more exits. 3. Exterior egress componenets at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2006 IBC 1009.10 - Handrails. Stairways shall have handrails on each side and shall comply with Section 1012. Where glass is used to provide the handrail, the handrail shall also comply with Section 2047.
Correction

Codes Administration - 2006 IBC 1009.4 - Stairway landings. There shall be a floor or landing at the top and bottom of each stairway. The width of landings shall not be less than the width of stairways they serve. Every landing shall have a minimum dimension measured in the direction of travel equal to the width of the stairway. Such dimension need not exceed 48 inches where the stairway has a straight run.
Correction

Codes Administration - 2006 IBC 1013.3 - Opening limitations. Open guards shall have balusters or ornamental patterns such that a 4-inch-diameter sphere cannot pass through any opening up to a height or 34 inches. From a height of 34 inches to 42 inches above the adjacent walking surfaces, a sphere 8 inches in diameter shall not pass. (See exceptions provided in the code.)
Correction

Codes Administration - 2006 IBC 1017.1 - Construction. Corridors shall be fire-resistance rated in accordance with Table 1017.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partions.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - 2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Correction

Fire Department- Provide an exit sign at the top (north end) of the ramp.
Correction

Fire Department- 2006 IFC 1010.5 Minimum dimensions. The minimum dimensions of means of egress ramps shall comply with Sections 1010.5.1 through 1010.5.3. 1010.5.1 Width. The minimum width of a means of egress ramp shall not be less than that required for corridors by Section 1017.2. The clear width of a ramp and the clear width between handrails, if provided, shall be 36 inches (914 mm) minimum.
Correction

Fire Department- The doorway at the northeast corner of the building indicates "CLOS". What is the intended use of this space?
Correction

Codes Administration - The plan provided does not give specifications on the mechanical, electrical and plumbing alterations.
Correction

Codes Administration - It has been our experience that KCPL will not allow more than one service to a single tenant space.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $204.25 $204.25 Paid 08/25/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 09/07/2010
Correction
Corrective Action Required
09/07/2010
See Comment - MECHANICAL WORK IS UNDER B1001033.
Correction
Corrective Action Required
09/07/2010
Metal Boxes (grounding) (IRC) - NOT ALL J-BOXES ARE GROUNDED
Correction
Corrective Action Required
09/07/2010
Stair Treads and Risers (IRC) - STAIR RISERS CAN NOT VARY MORE THAN 3/8" BETWEEN RISERS. Interior
Correction
Resolved
09/07/2010
None - OKAY TO INSULATE, OKAY TO ROCK.
Rough Framing Inspection - Commercial Request Complete 9/3/2010 9/7/2010 09/07/2010
Above Ceiling Inspection Failed 09/29/2010
Correction
Corrective Action Required
09/29/2010
REMOVAL OF ABANDONED MATERIALS REMOVE ALL ABANDONED FOR SAFE/CLEAR WORK SPACE
Correction
Corrective Action Required
09/29/2010
HOLES/PENETRATIONS AT EXTERIOR WALLS SEAL ALL UNUSED OPENINGS EXAMPLE: NORTH EXT WALL
Correction
Corrective Action Required
09/29/2010
UNUSED OPENINGS AT JUNCTION BOXES CHECK ALL CLOSE ANY UNUSED OPNG'S
Correction
Corrective Action Required
09/29/2010
OPEN ELECTRICAL BOX(ES) CHECK ALL CLOSE ALL
Correction
Corrective Action Required
09/29/2010
SUPPORT/SECURING OF LOW VOLTAGE ELECTRICAL CABLE SECURE TO STRUCTURE
Correction
Corrective Action Required
09/29/2010
CONDITION OF ELECTRICAL BOX ABOVE JANITOR CLOSET DOOR OBSTRUCTED BY HVAC DUCT CONDUIT BENT @ FLEX DUCT
Correction
Corrective Action Required
09/29/2010
WATER PIPING ABOVE RAMP CORRIDOR NORTH END TWISTED LATERAL WIRE NOT LISTED FOR PURPOSE
Correction
Corrective Action Required
09/29/2010
SYSTEMS ABOVE CEILINGS WITH TILE IN PLACE LADDER REQUIRED FOR ACCESS SUBJECT TO APPROVAL SAFETY INSPECTION REQ'D
Above Ceiling Inspection Partial 10/04/2010
Correction
Resolved
10/04/2010
REMOVAL OF ABANDONED MATERIALS
Correction
Resolved
10/04/2010
HOLES/PENETRATIONS AT EXTERIOR WALLS
Correction
Resolved
10/04/2010
UNUSED OPENINGS AT JUNCTION BOXES SEE BELOW
Correction
Corrective Action Required
10/04/2010
OPEN ELECTRICAL BOX(ES) CLOSE ONE @ HVAC UNIT
Correction
Resolved
10/04/2010
SUPPORT/SECURING OF LOW VOLTAGE ELECTRICAL CABLE
Correction
Resolved
10/04/2010
CONDITION OF ELECTRICAL BOX ABOVE JANITOR CLOSET DOOR
Correction
Resolved
10/04/2010
WATER PIPING ABOVE RAMP CORRIDOR NORTH END
Correction
Corrective Action Required
10/04/2010
SYSTEMS ABOVE CEILINGS WITH TILE IN PLACE ENSURE ALL ELECT BOXES ARE SECURED TO STRUCTURE CLOSE ALL ELECT BOXES BLUNDER PLUGS AS NEEDED
Correction
Partial Correction
10/04/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS LEAVE OUT ONE TILE WHERE ELECTRICAL BOX @ HVAC UNIT REQUIRES COVER PLATE. OK TO COVER WHEN READY NEW CEILING AREAS EXCEPT:
Above Ceiling Inspection Passed 10/05/2010
Correction
Resolved
10/05/2010
UNUSED OPENINGS AT JUNCTION BOXES
Correction
Resolved
10/05/2010
OPEN ELECTRICAL BOX(ES)
Correction
Resolved
10/05/2010
SYSTEMS ABOVE CEILINGS WITH TILE IN PLACE
Correction
Resolved
10/05/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Occupancy Inspection - Fire Temporary C of O 11/5/2010 at 12:00 AM 11/05/2010
Corrective Action Required
11/05/2010
SIGNAGE ON EXTERIOR OF CLOSET DOOR. OUTSIDE OF DOOR NEEDS TO BE LABELED "STORAGE - BLOCKED DOOR"
Corrective Action Required
11/05/2010
AS SHOWN ON THE PLANS, THE EXIT DOOR DISCHARGES NEED TO BE ILLUMINATED WITH A REMOTE LIGHT HEAD
Corrective Action Required
11/05/2010
REMOVE EXIT SIGN FROM CLOSET
Corrective Action Required
11/05/2010
REMOVE SLIDE BOLT FROM STUDIO D REAR EXIT
Corrective Action Required
11/05/2010
FIRE EXTINGUISHERS NEED TO BE A MINIMUM OF 2A 10BC
Corrective Action Required
11/05/2010
NEED TO UPDATE THE LEGENDS TO THE BREAKER PANELS
Occupancy Inspection - Codes Commercial Failed 11/5/2010 at 12:00 AM 11/05/2010
B2406 SAFETY GLAZING
Corrective Action Required
11/05/2010
GLAZING AT HAZARDOUS LOCATIONS NOT FOUND TO BE ETCHED "TEMPERED": SEE SOME DOORS; GLAZING ADJACENT TO INTERIOR STAIR
Misc
Corrective Action Required
11/05/2010
ELECT RECEPT AT STUDIO B EAST WALL NOT HOT FOR TEST
Misc
Corrective Action Required
11/05/2010
HANDICAPPED ACCESSIBLE RESTROOMS: REAR GRAB BARS REQUIRED AT WATER CLOSETS; PADDING REQUIRED ON PIPING UNDER SINKS; MAXIMUM HEIGHT OF BOTTOM OF MIRRORS 40"
Misc
Corrective Action Required
11/05/2010
ELECTRICAL PANEL SCHEDULES NOT ACCURATE NOR COMPLETE
Misc
Corrective Action Required
11/05/2010
ADDRESS LABELING AT ELECTRICAL AND GAS SERVICES
Misc
Corrective Action Required
11/05/2010
"NO SMOKING" SIGNS REQUIRED AT ALL PUBLIC ENTRANCES
Misc
Corrective Action Required
11/05/2010
ELECTRICAL RECEPTACLE AT MEN'S RESTROOM NOT SOLID TO BOX
Misc
Corrective Action Required
11/05/2010
EXTERIOR STAIR PER A5/A1 NOT PER DRAWING: STEEL HANDRAIL NOT INSTALLED; BALLUSTER OPENINGS ARE NOT LESS THAN 4"
Misc
Corrective Action Required
11/05/2010
INTERIOR STAIR PER A4/A1 NOT PER DRAWING
Misc
Corrective Action Required
11/05/2010
EGRESS DOOR AT NORTHWEST: DECK BOARDS NOT FASTENED SECURELY
Occupancy Inspection - Fire Temporary C of O 11/11/2010 at 12:00 AM 11/11/2010
Occupancy Inspection - Codes Commercial Temporary C of O 11/11/2010 at 12:00 AM 11/11/2010
B2406 SAFETY GLAZING
Corrective Action Required
11/05/2010
GLAZING AT HAZARDOUS LOCATIONS NOT FOUND TO BE ETCHED "TEMPERED": SEE ONE DOOR; GLAZING ADJACENT TO INTERIOR STAIR
Misc
Resolved
11/11/2010
ELECT RECEPT AT STUDIO B EAST WALL NOT HOT FOR TEST
Misc
Corrective Action Required
11/05/2010
PADDING REQUIRED ON PIPING UNDER SINKS; MAXIMUM HEIGHT OF BOTTOM OF MIRRORS 40"
Misc
Resolved
11/11/2010
ELECTRICAL PANEL SCHEDULES NOT ACCURATE NOR COMPLETE
Misc
Resolved
11/11/2010
ADDRESS LABELING AT ELECTRICAL AND GAS SERVICES
Misc
Resolved
11/11/2010
"NO SMOKING" SIGNS REQUIRED AT ALL PUBLIC ENTRANCES
Misc
Resolved
11/11/2010
ELECTRICAL RECEPTACLE AT MEN'S RESTROOM NOT SOLID TO BOX
Misc
Corrective Action Required
11/05/2010
STEEL HANDRAIL NOT INSTALLED @ EXTERIOR STAIR
Misc
Resolved
11/11/2010
INTERIOR STAIR PER A4/A1 NOT PER DRAWING
Misc
Resolved
11/11/2010
EGRESS DOOR AT NORTHWEST: DECK BOARDS NOT FASTENED SECURELY
Occupancy Inspection - Fire Passed 11/18/2010 at 12:00 AM 11/18/2010
Occupancy Inspection - Codes Commercial Full C of O 11/18/2010 at 12:00 AM 11/18/2010
B2406 SAFETY GLAZING
Resolved
11/18/2010
GLAZING AT HAZARDOUS LOCATIONS NOT FOUND TO BE ETCHED "TEMPERED": SEE ONE DOOR; GLAZING ADJACENT TO INTERIOR STAIR
Misc
Resolved
11/18/2010
PADDING REQUIRED ON PIPING UNDER SINKS; MAXIMUM HEIGHT OF BOTTOM OF MIRRORS 40"
Misc
Resolved
11/18/2010
STEEL HANDRAIL NOT INSTALLED @ EXTERIOR STAIR
All Rough Inspection - Commercial Passed 11/22/2010 at 12:00 AM 11/22/2010
Correction
Resolved
11/22/2010
Stair Treads and Risers (IRC) - STAIR RISERS CAN NOT VARY MORE THAN 3/8" BETWEEN RISERS. Interior
Correction
Resolved
11/22/2010
Metal Boxes (grounding) (IRC) - NOT ALL J-BOXES ARE GROUNDED
Correction
Resolved
11/22/2010
See Comment - MECHANICAL WORK IS UNDER B1001033.
Documents & Images
Date Uploaded File Type Document Name
11/05/2010 Letter Fire Loss Reduction Form
11/05/2010 Letter Inspection Summary
11/11/2010 Letter Temporary Certificate of Occupancy
11/18/2010 Letter Fire Loss Reduction Form
11/18/2010 Letter Final Certificate of Occupancy
11/22/2010 Letter Inspection Summary
11/23/2010 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home