Permit Application Status

B1000791


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000791
Building Permit - Commercial
Final Completion
RED SUMMIT FAIR LLC
NEW TENANT FINISH
TOYS R US EXPRESS TENANT FINISH
07/13/2010
07/26/2010
01/22/2011
08/25/2010
Locations
Contacts
CAMM CONSTRUCTION INC, Address:7216 MAPEL  
STEVE THE PLUMBER, Address:601 S STELLA  
PALMER ELECTRIC, INC., Address:6600 ROYAL ST BLDG B  
J D TOWNSEND CONSTRUCTION LLC, Address:12651 HEMLOCK ST  
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/22/2011 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction

Codes Administration - Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Permits shall be obtained prior to any performing any work which requires permits.
Correction

Codes Administration - I am unable to locate the framing details for the ceiling above the restrooms.
Correction

Fire Department- 2006 IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $538.51 $538.51 Paid 07/26/2010
89 Sewer Tap Fees $150.00 $150.00 Paid 07/26/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/27/2010
Correction
Resolved
07/27/2010
None
All Rough Inspection - Commercial Failed 08/03/2010
Correction
Corrective Action Required
08/03/2010
PROTECTION OF PVC PIPE FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS & TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES AND SHALL EXTEND A MINIMUM OF 2" ABOVE BASE TRACKS & BELOW TOP TRACKS. CHECK ALL. WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
Correction
Corrective Action Required
08/03/2010
INSTALLATION OF MC ELECTRICAL CABLE NEC 300-11 & 334-10: SPACE 103 EAST WALL NOT SECURELY FASTENED WITHIN 12" OF BOX
Correction
Corrective Action Required
08/03/2010
FRAMING OF BULKHEAD/SOFFIT @ EAST END CHECK ALL, INCLUDING AT TOP TRACK FRAMING CONNECTIONS NOT FULLY SCREWED
All Rough Inspection - Commercial Passed 08/04/2010
Correction
Resolved
08/04/2010
PROTECTION OF PVC PIPE FROM PENETRATION
Correction
Resolved
08/04/2010
INSTALLATION OF MC ELECTRICAL CABLE
Correction
Resolved
08/04/2010
FRAMING OF BULKHEAD/SOFFIT @ EAST END IN PROGRESS A FEW CONNECTIONS YET TO BE SCREWED
Correction
Resolved
08/04/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO COVER WHEN READY SEE FRAMING CONNECTIONS SCREWS TO BE COMPLETED
Gas Service Inspection - Commercial Passed 08/11/2010
Correction
Resolved
08/11/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE BY FINAL INSPECTION APPLY PERMANENT ADDRESS (840 J) TAG TO LOAD SIDE ENTRY PIPE (NOT ON METER). PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Gas Piping Inspection - Commercial Failed 08/11/2010
Correction
Corrective Action Required
08/11/2010
SUPPORT OF RIGID STEEL PIPING 18" x 18" x 3/4" ROOF WALKWAY MATERIAL ADHERED TO BOTTOM OF BLOCKS. BLOCK PADS NOT PER DRAW'G CAREY-TRED OR EQUAL
Correction
Corrective Action Required
08/11/2010
SPACING OF ROOFTOP GAS PIPING BLOCKS SUPPORT W/I 2' OF JOINTS
Correction
Corrective Action Required
08/11/2010
PAINTING OF ROOFTOP GAS PIPING INCOMPLETE SEE PARTIAL COVERAGE
Electrical Service Inspection Passed 08/18/2010
Correction
Resolved
08/18/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE. ENSURE PANEL FRONT IS IN PLACE BEFORE SERVICE ACTIVATION. 480V 3P / 120/208V 4W 100A MCB
Above Ceiling Inspection Passed 08/19/2010
Correction
Resolved
08/19/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO COVER WHEN READY
Gas Piping Inspection - Commercial Passed 08/20/2010
Correction
Resolved
08/20/2010
SUPPORT OF RIGID STEEL PIPING
Correction
Resolved
08/20/2010
SPACING OF ROOFTOP GAS PIPING BLOCKS
Correction
Resolved
08/20/2010
PAINTING OF ROOFTOP GAS PIPING
Final Inspection - Commercial Passed 08/24/2010
Correction
Resolved
08/24/2010
Receive Fire Department approval PER CPT JOE DIR
Correction
Resolved
08/24/2010
CODES ADMINISTRATION FINAL INSPECTION NO ISSUES FOUND CLOSE PERMIT
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home