Permit Application Status

B1000770


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000770
Building Permit - Commercial
Final Completion
LBP III LLC
PARTIAL COMMERCIAL
UNDERSLAB PLUMBING ONLY.
07/08/2010
07/08/2010
01/04/2011
07/28/2010
Locations
Contacts
DAVIDSON BROWN, Address:11301 STRANG LINE ROAD  
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
LBP III LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/04/2011 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1006.2 - Illumination level. The means of egress illumination level shall not be less than 1 foot-candle at the walking surface level.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Codes Administration - Details for the installation of the unit heaters have not been provided.
Correction

Codes Administration - Specifications for the mechanical installation are not provided.
Correction

Codes Administration - 2006 IMC 501.2 - Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.2.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted inot an attic or crawl space.
Correction

Codes Administration - The mechanical plans do not indicate any return air from office 102, break room 105 and office 108.
Correction

Codes Administration - 2006 IBC 1103.2.3 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.9.1.2, 1007 and 1104.3.1 and shall be designed and constructed so that individuals with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, that are less than 150 square fee in area and elevated 7 inches or more above the ground or finish floor where the elevation is essential to the function of the space shall be exempt from all requirements.
Correction

Codes Administration - The plans do not indicate the intended use of the casework identified in construction note 10. If the casework is to be used for sales or service purposes, a section meeting the requirements for accessibliltiy will be required.
Correction

Fire Department - Indicate type of commodity and method of storage in the the warehouse. Provide a storage plan. If high rack storage is utilized, storage shall be in compliance with IFC Chapter 23 , High Piled Combustible Storage.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $30.00 $30.00 Paid 07/08/2010
89 Sewer Tap Fees $180.00 $180.00 Paid 07/08/2010
91 EFHB Maybrook Water Shed $255.66 $255.66 Paid 07/08/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/09/2010
Correction
Resolved
07/09/2010
None UNDERSLAB PLUMBING APPROVED
Final Plumbing Inspection - Commercial Passed 07/27/2010
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home