Permit Application Status

B1000677


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000677
Building Permit - Commercial
Certificate of Occupancy
ADDITION COMMERCIAL
ADDITION TO EXISTING CHURCH
06/18/2010
08/19/2010
04/26/2011
10/05/2012
Locations
Contacts
STRICKLAND CONSTRUCTION CO., INC., Address:720 S. ROGERS RD STE B  
CENTURY PLUMBING, Address:14001 CENTURY LANE  
BART'S ELECTRIC COMPANY INC, Address:7103 N STEWART RD  
UNITED HEATING & COOLING, Address:301 DUCK RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 02/14/2011 10/29/2010
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- 2006 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1008.1.9 - Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds. Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Gourp A occupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equiped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.
Correction

Codes Administrations - 2006 IBC 1009.3 - Stair treads and risers. Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. Winder treads shall have a minimum tread depth of 11 inches measured at a right angle to the tread's leading edge at a point 12 inches from the side where the treads are narrower and a minimum tread depth of 10 inches.
Correction

Codes Administration - 2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Correction

Codes Administration - 2006 IBC 1109.2.1 - Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible unisex toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the unisex toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessilble unisex bathing room shall be provided. Fixtures located within unisex toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IBC 508.2.2 - Separation. Incidential use areas shall be separated or protected, or both, in accordance with Table 508.2. 508.2.2.1 Constrction. Where Table 508.2 requires a fire-resistance-rated separation, the incidental use area shall be separated from the remainder of the building by a fire barrier constructed in accordance with Section 706 or a horizontal assembly constructed in accordance with Section 711, or both. Where Table 508.2 permits an automatic fire-extinguishing system without a fire barrier, the incidental use area shall be separated from the remainder of the building by construction capable of resisting the passage of smoke. The partitions shall extend from the floor to the underside of the fir-resistance-rated floor/ceiling assembly of fire-resistance-rated roof/ceiling assembly above or the underside of the roof sheathing, or sub deck above. Doors shall be self- or automatic closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permited in accordance with NFPA 80.
Correction

Codes Administration - The design loads, including live loads, dead loads, snow loads, wind load and sesmic design, shall be provided.
Correction

Codes Administration - 2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Correction

Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Codes Administration - The electrical specs are not clear on the type of wire to be used and how it is to be installed.
Correction

Codes Administration - The plans do not provide any specifications for the mechanical installation.
Correction

Codes Administration - The fire-resistive assembly shown is intended for interior use. This application has it on both the interior and exterior of the structure.
Correction

Codes Administration - The electrical plans reference an HP-1 on the upper floor plans and the panel schedules but I am unable to locate it on other sheets.
Correction

Codes Administration - I am unable to locate any emergency lighting in the sanctuary at the stage area.
Correction

Codes Administration - The electrical plans show a door on the west side of the building from the stage area on the upper floor and only one exterior door from the lower level.
Correction

Codes Administration - Copies of the engineered truss and steel packages were not provided at the time of permit application.
Correction

Codes Administration - Each layer of fire-resistive assemblies shall be inspected and approved prior to the application of additional layers or finishes. All firestopping of penetrations and required dampers shall be inspected and approved prior to concealing.
Correction

Codes Administration - I am unable to locate detials for the interior and exterior wall construction.
Correction

Fire Department- 2006 IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 703.2.1 Signs. Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows: 1. For doors designed to be kept normally open: FIRE DOOR—DO NOT BLOCK. 2. For doors designed to be kept normally closed: FIRE DOOR—KEEP CLOSED. 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
Correction

Fire Department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

Fire Department. Provide exit signage over doors: 104-1, 104-2, 104-3, 100-5, 001-1, 001-2, and at the top of the stairs from the mezzanine.
Correction

Fire Department- The main drain from the sprinkler riser shall be routed to the exterior or suitably sized floor drain.
Correction

Fire Department- 2006 IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $3,249.64 $3,249.64 Paid 08/19/2010
89 Sewer Tap Fees $750.00 $750.00 Paid 08/19/2010
91 EFHB Maybrook Water Shed $1,065.25 $1,065.25 Paid 08/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rated Assembly Inspection Partial 10/11/2010
Correction
Partial Correction
10/11/2010
None -1" GYPSUM LAYER INSTALLED TO ROOFLINE PER PLAN
Rated Assembly Inspection Partial 10/13/2010
Correction
Partial Correction
10/13/2010
None -1" GYPSUM LAYER INSTALLED TO ROOFLINE PER PLAN, 1/2" BASE LAYER INSTALLED
Rated Assembly Inspection Partial 10/15/2010
Correction
Partial Correction
10/15/2010
None 2 HR RATED WALL TO ROOFLINE PER PLAN-1" GYPSUM LAYER , 1/2" BASE LAYER INSTALLED, FINAL 1/2" LAYER INSTALLED
Rated Assembly Inspection Partial 10/22/2010
Correction
Partial Correction
10/22/2010
None -2 HR RATED WALL TO ROOFLINE PER PLAN-1" GYPSUM LAYER , 1/2" BASE LAYER INSTALLED, FINAL 1/2" LAYER INSTALLED -EXTENSION OF PARAPET AND 2HR WALL-OK FOR BASE&FACE LAYER
All Rough Inspection - Commercial Partial 10/25/2010
Correction
Partial Correction
10/25/2010
None IN-WALL ALLROUGH OK BELOW: GWB WALL AT STAGE 106; *OK TO ROCK ONE SIDE ONLY AT 105&107
Rated Assembly Inspection Passed 10/26/2010
Correction
Resolved
10/26/2010
None -2 HR RATED WALL TO ROOFLINE PER PLAN-OK -PARAPET AND EXTENSION OF THE 2HR WALL-OK
Rough Electrical Inspection - Commercial Failed 10/28/2010
Correction
Corrective Action Required
10/28/2010
None INSPECTED BELOW: ELECTRICAL FROM MAIN SERVICE DISCONNECT TO PANEL IN BASEMENT-CONDUCTORS RUBS AGAINST EDGE OF CONDUIT. INSTALL BUSHINGS TO PROTECT CONDUCTORS, ID EQUIPMENT GROUNDING CONDUCTORS
Rough Electrical Inspection - Commercial Partial 10/29/2010
Correction
Partial Correction
10/29/2010
None INSPECTED BELOW: ELECTRICAL FROM MAIN SERVICE DISCONNECT TO PANEL IN BASEMENT-OK
All Rough Inspection - Commercial Failed 11/16/2010 at 12:00 AM 11/16/2010
Misc
Partial Correction
11/15/2010
IN-WALL ALLROUGH OK BELOW: -GWB WALL AT STAGE 106 (OK TO ROCK ONE SIDE ONLY AT 105&107)
Misc
Corrective Action Required
11/16/2010
*INSPECTED THE WOOD STRUCTURE. ONLY OK TO SPRAY EXTERIOR WALL AND ROOF *THE FOLLOWING DEFICIENCIES ARE FOR THE REST: -FIREBLOCK DEAD VERTICAL SPACE FROM ATTIC SPACE; FIREBLOCK WALL EVERY 10FT HORIZONTALLY AND AT CEILING INTERSECTION WITH ROOF SPACE; ALL FLOOR PENETRATIONS -PENETRATIONS OF THE 2HR RATED WALL SHALL BE PROTECTED PER LISTING -PROTECT PVC WHEN WITHIN 1.5" OF NAILING SURFACE; SECURE PVC (2" OR SMALLER) AT MIDHEIGHT -BLOCK WALL FOR 18" VERTICAL GRAP BAR IN RESTROOMS -WATER-HAMMER ARRESTORS SHALL CONFORM TO IPC 604.9 (NO FIELD MADE CHAMBERS ALLOWED)
All Rough Inspection - Commercial Failed 11/22/2010 at 12:00 AM 11/22/2010
Misc
Partial Correction
11/16/2010
IN-WALL ALLROUGH OK BELOW: -GWB WALL AT STAGE 106 (OK TO ROCK ONE SIDE ONLY AT 105&107)
Misc
Corrective Action Required
11/16/2010
*INSPECTED THE WOOD STRUCTURE. ONLY OK TO SPRAY EXTERIOR WALL AND ROOF *THE FOLLOWING DEFICIENCIES ARE FOR THE REST: -FIREBLOCK DEAD VERTICAL SPACE FROM ATTIC SPACE;
All Rough Inspection - Commercial Partial 11/29/2010 at 12:00 AM 11/29/2010
Misc
Partial Correction
11/22/2010
IN-WALL ALLROUGH OK BELOW: -GWB WALL AT STAGE 106/105/107 -RAMP (LEAVE STORAGE SIDE OPEN) -RESTROOMS/HALL/STAIRS&RAMP/COFFEE AREA
Misc
Partial Correction
11/29/2010
-OK TO ROCK CEILING AT :NARTHEX
All Rough Inspection - Commercial Partial 12/6/2010 at 12:00 AM 12/06/2010
Misc
Partial Correction
11/29/2010
IN-WALL ALLROUGH OK BELOW: -106/105/107/SANCTUARY -RAMP&STORAGE -RESTROOMS/HALL/STAIRS&RAMP@FIRE WALL/COFFEE AREA -STAIRS TO BASEMENT
Misc
Partial Correction
11/29/2010
-OK TO ROCK CEILING AT :NARTHEX, RESTROOMS&HALLWAY
Sprinkler - Hydrostatic Test Passed 12/6/2010 at 12:00 AM 12/06/2010
All Rough Inspection - Commercial Partial 12/28/2010 at 12:00 AM 12/28/2010
Misc
Partial Correction
12/06/2010
IN-WALL ALL-ROUGH OK BELOW: -106/105/107/SANCTUARY/PLATFORM -RAMP&STORAGE -RESTROOMS/HALL/STAIRS&RAMP@FIRE WALL/COFFEE AREA -STAIRS TO BASEMENT
Misc
Partial Correction
12/06/2010
-OK TO ROCK CEILING AT :NARTHEX, RESTROOMS&HALLWAY
All Rough Inspection - Commercial Partial 1/6/2011 at 12:00 AM 01/06/2011
Misc
Partial Correction
12/28/2010
ALL-ROUGH OK BELOW: -106/105/107/SANCTUARY -PLATFORM -RAMP&STORAGE -RESTROOMS/HALL/STAIRS&RAMP@FIRE WALL/COFFEE AREA -STAIRS TO BASEMENT -MEZZANINE PLATFORM IN SANCTUARY
Misc
Partial Correction
12/28/2010
-OK TO ROCK CEILING AT :NARTHEX, RESTROOMS&HALLWAY -FIRE PROTECTION SPRAY APPLIED TO VERTICAL SURFACE OF FOAM PLASTIC INSULATION IN NARTHEX PER ESR DOCUMENT
Rough Electrical Inspection - Commercial Partial 1/18/2011 at 12:00 AM 01/18/2011
Correction
Partial Correction
12/03/2010
INSPECTED&OK BELOW: ELECTRICAL FROM MAIN SERVICE DISCONNECT TO PANEL IN BASEMENT, DRIVEWAY DROP-OFF LIGHTING, SANCTUARY BALCONY WALL RECEPTACLES
Above Ceiling Inspection Passed 1/25/2011 at 12:00 AM 01/25/2011
Alarm Test Failed 2/9/2011 at 12:00 AM 02/09/2011
Corrective Action Required
02/09/2011
Sprinkler - Flow Test Passed 2/9/2011 at 12:00 AM 02/09/2011
All Rough Inspection - Commercial Passed 2/10/2011 at 12:00 AM 02/10/2011
Misc
Resolved
02/10/2011
ALL-ROUGH OK BELOW: -106/105/107/SANCTUARY -PLATFORM -RAMP&STORAGE -RESTROOMS/HALL/STAIRS&RAMP@FIRE WALL/COFFEE AREA -STAIRS TO BASEMENT -MEZZANINE PLATFORM IN SANCTUARY
Misc
Resolved
02/10/2011
-OK TO ROCK CEILING AT :NARTHEX, RESTROOMS&HALLWAY -FIRE PROTECTION SPRAY APPLIED TO VERTICAL SURFACE OF FOAM PLASTIC INSULATION IN NARTHEX PER ESR DOCUMENT
Rough Electrical Inspection - Commercial Passed 2/10/2011 at 12:00 AM 02/10/2011
Correction
Resolved
02/10/2011
INSPECTED&OK BELOW: ELECTRICAL FROM MAIN SERVICE DISCONNECT TO PANEL IN BASEMENT, DRIVEWAY DROP-OFF LIGHTING, SANCTUARY BALCONY WALL RECEPTACLES
Occupancy Inspection - Codes Commercial Temporary C of O 2/10/2011 at 12:00 AM 02/10/2011
Misc
Corrective Action Required
02/10/2011
-EXTERIOR NOT INSPECTED DUE TO WEATHER CONDITION. CHECK AT LATER DATE. -GRADE/SOD/SPLASHBLOCKS UNDER DOWNSPOUTS, ETC WILL BE CHECKED LATER -SEAL EXTERIOR WALL PENETRATION AT HEAT PUMP LINE -PROVIDE APPROVALS FROM FOLLOWING DEPARTMENTS: PLANNING&DEVELOPMENT, PUBLIC WORKS, FIRE -PROVIDE SPECIAL INSPECTION REPORT
Misc
Corrective Action Required
02/10/2011
-EXTERIOR GFCI RECEPTACLES EXPOSED TO WEATHER SHALL BE PROTECTED WITH WEATHER-PROOF COVERS
Misc
Corrective Action Required
02/10/2011
RESTROOM TACTILE SIGNAGE IS REQUIRED TO BE INSTALLED ON LATCHED SIDE OF DOOR PER ANSI 117.1 (703.3.11)
Misc
Corrective Action Required
02/10/2011
@ BAPTISING TUB -HANDRAIL REQUIRED AT STAIR TO BAPTISING TUB -INSTALL COVER PLATE FOR SHUT-OFF SWITCH -BOND MOTOR TO COPPER WATER PIPING WITH #8 SOLID COPPER -PROTECT HYDROMASSAGE TUB AND ALL ASSOCIATED EQUIPMENTS WITH GFCI AS REQUIRED
Misc
Corrective Action Required
02/10/2011
SEAL ELECTRICAL FEEDER CONDUIT TO BASEMENT PANEL (ON EITHER END)
Misc
Corrective Action Required
02/10/2011
OCCUPANT LOAD SIGNAGE SHALL BE PROVIDED AT ALL ASSEMBLY AREAS
Occupancy Inspection - Fire Temporary C of O 02/10/2011
Corrective Action Required
02/10/2011
(1) provide exit/emergency lighting in sanctuary for door 104-2 (2) provide emergency lighting for basement door exits. (3) remove tape from aa sprinkler heads in the sanctuary (4) install sprinkler eschutions in stairway to basement (5) post occupant load in sanctuary (979) (6) label the FDConnection "supplies sanctuary only"
Alarm Test Passed 2/10/2011 at 12:00 AM 02/10/2011
Occupancy Inspection - Planning Temporary C of O 2/10/2011 at 12:00 AM 02/10/2011
Corrective Action Required
02/10/2011
Lighting. Modifications to the lighting shown on the approved site plan were done, but staff found that the lighting was acceptable because there was less and wattages were lower than shown on the approved plan.
Corrective Action Required
02/10/2011
Landscaping. The site will have to be re-inspected for landscaping in the spring. All landscaping shall be installed as shown on the approved landscape plan by the end of March.
Occupancy Inspection - Fire Passed 02/17/2011
Occupancy Inspection - Codes Commercial Partial 2/17/2011 at 12:00 AM 02/17/2011
Misc
Corrective Action Required
02/10/2011
-GRADE/SOD/SPLASHBLOCKS UNDER DOWNSPOUTS -PROVIDE APPROVALS FROM FOLLOWING DEPARTMENTS: PLANNING&DEVELOPMENT, PUBLIC WORKS -PROVIDE SPECIAL INSPECTION REPORT
Misc
Resolved
02/17/2011
-EXTERIOR GFCI RECEPTACLES EXPOSED TO WEATHER SHALL BE PROTECTED WITH WEATHER-PROOF COVERS
Misc
Resolved
02/17/2011
RESTROOM TACTILE SIGNAGE IS REQUIRED TO BE INSTALLED ON LATCHED SIDE OF DOOR PER ANSI 117.1 (703.3.11)
Misc
Resolved
02/17/2011
@ BAPTISING TUB -HANDRAIL REQUIRED AT STAIR TO BAPTISING TUB -INSTALL COVER PLATE FOR SHUT-OFF SWITCH -BOND MOTOR TO COPPER WATER PIPING WITH #8 SOLID COPPER
Misc
Resolved
02/17/2011
SEAL ELECTRICAL FEEDER CONDUIT TO BASEMENT PANEL (ON EITHER END)
Misc
Resolved
02/17/2011
OCCUPANT LOAD SIGNAGE SHALL BE PROVIDED AT ALL ASSEMBLY AREAS
Occupancy Inspection - Planning Temporary C of O 3/24/2011 at 12:00 AM 03/24/2011
Occupancy Inspection - Planning Passed 10/05/2012
Occupancy Inspection - Codes Commercial Full C of O 10/05/2012
Misc
Corrective Action Required
02/17/2011
-GRADE/SOD/SPLASHBLOCKS UNDER DOWNSPOUTS -PROVIDE APPROVALS FROM FOLLOWING DEPARTMENTS: PLANNING&DEVELOPMENT, PUBLIC WORKS -PROVIDE SPECIAL INSPECTION REPORT
Documents & Images
Date Uploaded File Type Document Name
11/16/2010 Letter Inspection Summary
11/29/2010 Letter Inspection Summary
12/06/2010 Letter Inspection Summary
12/16/2010 Letter Fire Loss Reduction Form
12/28/2010 Letter Inspection Summary
01/06/2011 Letter Inspection Summary
01/18/2011 Letter Inspection Summary
01/25/2011 Letter Inspection Summary
02/04/2011 Letter CMR
02/09/2011 Letter Fire Loss Reduction Form
02/09/2011 Letter Fire (Alarm) Plan Review Notice.pdf
02/09/2011 Letter Fire (Alarm) Plan Review Notice0.pdf
02/10/2011 Letter Temporary Certificate of Occupancy
02/10/2011 Letter Fire Loss Reduction Form
02/17/2011 Letter Fire Loss Reduction Form
02/17/2011 Letter Inspection Summary
03/03/2011 PSI Report
05/03/2011 Letter 10-Day Notice of Violation
06/24/2011 Letter 20110624144805725.pdf
12/07/2011 Letter 20111207111647141.pdf
10/08/2012 Letter Final Certificate of Occupancy
06/14/2013 Letter DOC061413-005.pdf
06/21/2013 Letter Fire (Alarm) Plan Review Notice
06/21/2013 Letter Fire Loss Reduction Form3.pdf
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home