Permit Application Status

B1000632


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000632
Building Permit - Commercial
Certificate of Occupancy
ADDITION COMMERCIAL
MULTIUSE BUILDING ADDITION
06/10/2010
08/04/2010
04/27/2011
08/04/2010
Locations
Contacts
MID-STATES HEATING AND COOLING, Address:4011 MAIN ST  
HOLLIS & MILLER GROUP INC, Address:220 NW EXECUTIVE WAY  
J E DUNN CONSTRUCTION, Address:1001 LOCUST  
NORTH KANSAS CITY ELECTRIC CO INC, Address:PO BOX 12442  
SALADINO PLUMBING & HEATING CO, Address:2210 TELEVISION PL  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/25/2011 10/29/2010
Correction

Fire Department- 2006 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45 720 mm) where: 1. The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies.
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117 2003 803.4 - Benches. A bench complying with Section 903 shall be provided within the room.
Correction

Codes Administration - 2006 IBC 1109.8.1 - Lockers. Where lockers are provided in accessible spaces, at least five percent, but not less than one, of each type shall be accessible.
Correction

Codes Administration - ICC/ANSI A117.1-2003 404.2.3.4 - Recessed Doors. Where any obstruction within 18 inches of the latch side of a doorway projects more than 8 inches beyond the face of the door, measured perpendicular to the face of the door, maneuvering clearances for a forward approach shall be provided.
Correction

Codes Administration - Copies of the engineered metal building package were not provided at the time of permit application.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $6,296.40 $6,296.40 Paid 08/04/2010
89 Sewer Tap Fees $450.00 $450.00 Paid 08/04/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 09/08/2010
Correction
Resolved
09/08/2010
None - FOOTING ALONG EXISTING BUILDING ONLY. - NOT ON APPROVED PLANS - COLUMN PIER INSTALLED AT CENTER OF FOOTING LINE. 4' X 4', DBL LAYER OF #4 REBAR 4 BARS EACH WAY. - PROVIDE ENGINEER'S REPORT ON PIER COLUMN. Line D
Correction
Resolved
09/08/2010
None LineS D & 3
Correction
Partial Correction
09/08/2010
None - APPROX. 20' FROM SE CORNER - APPROVED. Line A
Footing Inspection - Commercial Partial 09/10/2010
Correction
Partial Correction
09/10/2010
None - APPROX. 20' FROM SE CORNER - APPROVED. - LINE A COMPLETED TO SW CORNER Line A
Correction
Resolved
09/10/2010
None Column Line 2 Pads
Correction
Resolved
09/10/2010
None - FROM NW CORNER TO PAD ON LINE B Line 1
Footing Inspection - Commercial Passed 09/13/2010
Correction
Resolved
09/13/2010
None - APPROX. 20' FROM SE CORNER - APPROVED. - LINE A COMPLETED TO SW CORNER Line A
Correction
Resolved
09/13/2010
None NOT READY
Correction
Resolved
09/13/2010
None - FOOTING COMPLETE
Underslab Plumbing Inspection - Commercial Passed 09/23/2010
Correction
Resolved
09/23/2010
None
Underslab Electrical Inspection - Commercial Passed 09/28/2010
Correction
Resolved
09/28/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Underground Electrical Inspection - Commercial Request Complete 10/29/2010 11/1/2010 11/01/2010
Underground Electrical Inspection - Commercial Partial 11/1/2010 at 12:00 AM 11/02/2010
Misc
Partial Correction
11/02/2010
OK TO COVER WHEN READY THREE PVC BURIED CONDUITS TRENCHED & PLACED FROM TRANSFORMER POLE TO OUTSIDE ELECT RM 119-A104
Rough Plumbing Inspection - Commercial Partial 11/11/2010 at 12:00 AM 11/11/2010
Misc
Partial Correction
11/11/2010
OK TO COVER WHEN READY C.I. TOP ROUGH DWV PLUMBING PER (1) ON DRAWING SHEET P110;
Electrical Service Inspection Passed 11/24/2010 at 12:00 AM 11/24/2010
Gas Piping Inspection - Commercial Passed 12/1/2010 at 12:00 AM 12/01/2010
Underslab Plumbing Inspection - Commercial Passed 12/7/2010 at 12:00 AM 12/07/2010
Rough Plumbing Inspection - Commercial Partial 12/10/2010 at 12:00 AM 12/10/2010
Misc
Partial Correction
11/11/2010
OK TO COVER WHEN READY C.I. TOP ROUGH DWV PLUMBING PER (1) ON DRAWING SHEET P110; -IN-WALL PLUMBING FOR LAUNDRY RM-OK
Above Ceiling Inspection Partial 12/28/2010
Misc
Partial Correction
12/28/2010
OK TO COVER WHEN READY FRAMING & ABOVE-CEILING SYSTEMS @ GWB CEILINGS AT SPACES LISTED BELOW: A114; A119; A126
Underground Electrical Inspection - Commercial Passed 12/28/2010 at 12:00 AM 12/28/2010
Misc
Resolved
12/28/2010
OK TO COVER WHEN READY THREE PVC BURIED CONDUITS TRENCHED & PLACED FROM TRANSFORMER POLE TO OUTSIDE ELECT RM 119-A104
Rough Plumbing Inspection - Commercial Passed 12/28/2010 at 12:00 AM 12/28/2010
Misc
Resolved
12/28/2010
OK TO COVER WHEN READY C.I. TOP ROUGH DWV PLUMBING PER (1) ON DRAWING SHEET P110; -IN-WALL PLUMBING FOR LAUNDRY RM-OK
Sewer Service Inspection Partial 12/29/2010 at 12:00 AM 12/29/2010
Misc
Partial Correction
12/29/2010
OK TO COVER WHEN READY 4" SDR35 SANITARY SEWER SERVICE LINE FROM BUILDING ENTRY TO 60' W/SW. LAST 20' NOT IN PLACE; NOT APPROVED TO COVER
Misc
Corrective Action Required
12/29/2010
DRAWING SHOWS TWO BRANCHES ENTERING BUILDING, BUT ONE INSTALLED. JED TO OBTAIN WRITTEN CLARIFICATION FROM A/E.
Sewer Service Inspection Partial 1/4/2011 at 12:00 AM 01/04/2011
Misc
Resolved
01/04/2011
OK TO COVER WHEN READY 4" SDR35 SANITARY SEWER SERVICE LINE FROM BUILDING ENTRY TO 60' W/SW. LAST 20' NOT IN PLACE; NOT APPROVED TO COVER
Misc
Corrective Action Required
12/29/2010
DRAWING SHOWS TWO BRANCHES ENTERING BUILDING, BUT ONE INSTALLED. JED TO OBTAIN WRITTEN CLARIFICATION FROM A/E.
Sewer Service Inspection Partial 1/7/2011 at 12:00 AM 01/07/2011
Misc
Partial Correction
01/07/2011
CLEANOUT SHOWN ON DRAWING YET TO BE INSTALLED. CALL FOR INSPECTION WHEN INSTALLED BEFORE COVERING.
Above Ceiling Inspection Not Ready 1/12/2011 at 12:00 AM 01/12/2011
Misc
Partial Correction
12/28/2010
OK TO COVER WHEN READY FRAMING & ABOVE-CEILING SYSTEMS @ GWB CEILINGS AT SPACES LISTED BELOW: A114; A119; A126
Above Ceiling Inspection Partial 1/12/2011 at 12:00 AM 01/12/2011
Misc
Partial Correction
01/12/2011
OK TO COVER WHEN READY FRAMING & ABOVE-CEILING SYSTEMS @ GWB CEILINGS AT SPACES LISTED BELOW: A114; A119; A126
Misc
Partial Correction
01/12/2011
- NEW ADDITION ONLY - OKAY TO INSTALL CEILING TILE
Occupancy Inspection - Planning Temporary C of O 01/19/2011
Corrective Action Required
01/19/2011
Install sodding on the south side of the building per the approved plan.
Corrective Action Required
01/19/2011
Install asphalt pavement on west side of building per the approved plan.
Occupancy Inspection - Codes Commercial Partial 1/19/2011 at 12:00 AM 01/19/2011
B1008 DOORS, GATES AND TURNSTILES
Corrective Action Required
01/19/2011
1. CHECK HARDWARE ON INTERIOR DOOR WHEN INSTALLED AT LOCKER ROOMS. APPROVED TO OCCUPY SOUTH NEW ADDITION. PARTIAL INSPECTION ONLY(SOUTH PORTION OF NEW ADDITON.
Misc
Corrective Action Required
01/19/2011
TEMPORARY OCCUPANCY APPROVED TO SOUTH ADDITION ONLY.
Alarm Test Passed 01/19/2011
Occupancy Inspection - Fire Passed 01/19/2011
Corrective Action Required
01/19/2011
Underslab Plumbing Inspection - Commercial Passed 2/10/2011 at 12:00 AM 02/10/2011
Underslab Plumbing Inspection - Commercial Passed 2/11/2011 at 12:00 AM 02/11/2011
Rough Plumbing Inspection - Commercial Passed 2/22/2011 2/22/2011 at 12:00 AM 03/01/2011
In-wall Inspection Partial 3/3/2011 at 12:00 AM 03/03/2011
Misc
Partial Correction
03/03/2011
OK TO COVER WHEN READY FRAMING & IN-WALL SYSTEMS AT FOLLOWING WALLS/SPACES: 102 NORTH WALL;
Underslab Plumbing Inspection - Commercial Passed 3/10/2011 3/10/2011 at 12:00 AM 03/10/2011
Above Ceiling Inspection Not Ready 3/10/2011 at 12:00 AM 03/10/2011
Misc
Partial Correction
01/12/2011
OK TO COVER WHEN READY FRAMING & ABOVE-CEILING SYSTEMS @ GWB CEILINGS AT SPACES LISTED BELOW: A114; A119; A126
In-wall Inspection Partial 3/15/2011 at 12:00 AM 03/15/2011
Misc
Partial Correction
03/03/2011
OK TO COVER WHEN READY FRAMING & IN-WALL SYSTEMS AT FOLLOWING WALLS/SPACES: 102 NORTH WALL; WALL SEPARATING A129 & A128
Above Ceiling Inspection Partial 3/24/2011 at 12:00 AM 03/24/2011
Misc
Partial Correction
03/10/2011
OK TO COVER WHEN READY FRAMING & ABOVE-CEILING SYSTEMS @ GWB CEILINGS AT SPACES LISTED BELOW: A114; A119; A126
Misc
Partial Correction
03/24/2011
- OKAY TO INSTALL CEILING TILE - ROOMS 112 & 118
Alarm Test Passed 3/30/2011 at 12:00 AM 03/30/2011
Occupancy Inspection - Fire Passed 3/30/2011 at 12:00 AM 03/30/2011
Occupancy Inspection - Codes Commercial Temporary C of O 3/30/2011 3/30/2011 at 12:00 AM 03/30/2011
B1008 DOORS, GATES AND TURNSTILES
Corrective Action Required
01/19/2011
1. CHECK HARDWARE ON INTERIOR DOOR WHEN INSTALLED AT LOCKER ROOMS. APPROVED TO OCCUPY SOUTH NEW ADDITION. PARTIAL INSPECTION ONLY(SOUTH PORTION OF NEW ADDITON.
Misc
Resolved
03/30/2011
TEMPORARY OCCUPANCY APPROVED TO SOUTH ADDITION ONLY.
Misc
Corrective Action Required
03/30/2011
CIRCUIT BREAKER POSITIONS AT PANEL P-3 NOT NUMBERED
Misc
Corrective Action Required
03/30/2011
ELECT RECEPT BOXES AT COMBUSTIBLE WALL SURFACES NOT FLUSH WITH WALL FACE.
Misc
Corrective Action Required
03/30/2011
MAXIMUM HEIGHT OF BOTTOM OF MIRROR GLASS IN ACCESSIBLE RESTROOMS IS 40" AFF
Misc
Corrective Action Required
03/30/2011
RESTROOM FLOOR FINISH MUST BE NON-ABSORBENT
Misc
Corrective Action Required
03/30/2011
ENSURE ADA PADDING IS IN PLACE ON UNDER-SINK PIPING
Misc
Corrective Action Required
03/30/2011
UNIDENTIFIED GRILLE PARTIALLY COVERED BY WATER COOLER.
Misc
Corrective Action Required
03/30/2011
EXTERIOR OF BUILDING AND SITEWORK IS SUBJECT TO APPROVAL WHEN COMPLETED.
Above Ceiling Inspection Passed 3/30/2011 at 12:00 AM 03/30/2011
Misc
Resolved
03/30/2011
OK TO COVER WHEN READY FRAMING & ABOVE-CEILING SYSTEMS @ GWB CEILINGS AT SPACES LISTED BELOW: A114; A119; A126
Misc
Resolved
03/30/2011
- OKAY TO INSTALL CEILING TILE - ROOMS 112 & 118
In-wall Inspection Passed 3/30/2011 at 12:00 AM 03/30/2011
Misc
Partial Correction
03/15/2011
OK TO COVER WHEN READY FRAMING & IN-WALL SYSTEMS AT FOLLOWING WALLS/SPACES: 102 NORTH WALL; WALL SEPARATING A129 & A128
Sewer Service Inspection Passed 3/30/2011 at 12:00 AM 03/30/2011
Misc
Resolved
03/30/2011
CLEANOUT SHOWN ON DRAWING YET TO BE INSTALLED. CALL FOR INSPECTION WHEN INSTALLED BEFORE COVERING.
Occupancy Inspection - Codes Commercial Not Ready 3/31/2011 at 12:00 AM 03/31/2011
B1008 DOORS, GATES AND TURNSTILES
Corrective Action Required
03/30/2011
1. CHECK HARDWARE ON INTERIOR DOOR WHEN INSTALLED AT LOCKER ROOMS. APPROVED TO OCCUPY SOUTH NEW ADDITION. PARTIAL INSPECTION ONLY(SOUTH PORTION OF NEW ADDITON.
Misc
Corrective Action Required
03/30/2011
CIRCUIT BREAKER POSITIONS AT PANEL P-3 NOT NUMBERED
Misc
Corrective Action Required
03/30/2011
ELECT RECEPT BOXES AT COMBUSTIBLE WALL SURFACES NOT FLUSH WITH WALL FACE.
Misc
Corrective Action Required
03/30/2011
MAXIMUM HEIGHT OF BOTTOM OF MIRROR GLASS IN ACCESSIBLE RESTROOMS IS 40" AFF
Misc
Corrective Action Required
03/30/2011
RESTROOM FLOOR FINISH MUST BE NON-ABSORBENT
Misc
Corrective Action Required
03/30/2011
ENSURE ADA PADDING IS IN PLACE ON UNDER-SINK PIPING
Misc
Corrective Action Required
03/30/2011
UNIDENTIFIED GRILLE PARTIALLY COVERED BY WATER COOLER.
Misc
Corrective Action Required
03/30/2011
EXTERIOR OF BUILDING AND SITEWORK IS SUBJECT TO APPROVAL WHEN COMPLETED.
Occupancy Inspection - Codes Commercial Partial 4/1/2011 at 12:00 AM 04/01/2011
B1008 DOORS, GATES AND TURNSTILES
Corrective Action Required
03/31/2011
1. CHECK HARDWARE ON INTERIOR DOOR WHEN INSTALLED AT LOCKER ROOMS. APPROVED TO OCCUPY SOUTH NEW ADDITION. PARTIAL INSPECTION ONLY(SOUTH PORTION OF NEW ADDITON.
Misc
Corrective Action Required
03/31/2011
CIRCUIT BREAKER POSITIONS AT PANEL P-3 NOT NUMBERED
Misc
Corrective Action Required
03/31/2011
ELECT RECEPT BOXES AT COMBUSTIBLE WALL SURFACES NOT FLUSH WITH WALL FACE.
Misc
Corrective Action Required
03/31/2011
MAXIMUM HEIGHT OF BOTTOM OF MIRROR GLASS IN ACCESSIBLE RESTROOMS IS 40" AFF
Misc
Corrective Action Required
03/31/2011
RESTROOM FLOOR FINISH MUST BE NON-ABSORBENT
Misc
Corrective Action Required
03/31/2011
ENSURE ADA PADDING IS IN PLACE ON UNDER-SINK PIPING
Misc
Corrective Action Required
03/31/2011
UNIDENTIFIED GRILLE PARTIALLY COVERED BY WATER COOLER.
Misc
Corrective Action Required
03/31/2011
EXTERIOR OF BUILDING AND SITEWORK IS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
04/01/2011
SOUTH SIDEWALK TO BE CLEARED FOR USE IMMEDIATELY PER JB 4/1/2011 10:50 TELECON WITH CHERYL OF JED.
Occupancy Inspection - Planning Passed 8/4/2011 at 12:00 AM 08/04/2011
Occupancy Inspection - Engineering Passed 8/4/2011 at 12:00 AM 08/04/2011
Occupancy Inspection - Codes Commercial Full C of O 8/4/2011 8/4/2011 at 12:00 AM 08/04/2011
B1008 DOORS, GATES AND TURNSTILES
Resolved
08/04/2011
1. CHECK HARDWARE ON INTERIOR DOOR WHEN INSTALLED AT LOCKER ROOMS. APPROVED TO OCCUPY SOUTH NEW ADDITION. PARTIAL INSPECTION ONLY(SOUTH PORTION OF NEW ADDITON.
Misc
Resolved
08/04/2011
CIRCUIT BREAKER POSITIONS AT PANEL P-3 NOT NUMBERED
Misc
Resolved
08/04/2011
ELECT RECEPT BOXES AT COMBUSTIBLE WALL SURFACES NOT FLUSH WITH WALL FACE.
Misc
Resolved
08/04/2011
MAXIMUM HEIGHT OF BOTTOM OF MIRROR GLASS IN ACCESSIBLE RESTROOMS IS 40" AFF
Misc
Resolved
08/04/2011
RESTROOM FLOOR FINISH MUST BE NON-ABSORBENT
Misc
Resolved
08/04/2011
ENSURE ADA PADDING IS IN PLACE ON UNDER-SINK PIPING
Misc
Resolved
08/04/2011
UNIDENTIFIED GRILLE PARTIALLY COVERED BY WATER COOLER.
Misc
Resolved
08/04/2011
EXTERIOR OF BUILDING AND SITEWORK IS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
08/04/2011
SOUTH SIDEWALK TO BE CLEARED FOR USE IMMEDIATELY PER JB 4/1/2011 10:50 TELECON WITH CHERYL OF JED.
Documents & Images
Date Uploaded File Type Document Name
11/02/2010 Letter Inspection Summary
11/11/2010 Letter Inspection Summary
11/24/2010 Letter Inspection Summary
12/01/2010 Letter Inspection Summary
12/07/2010 Letter Inspection Summary
12/10/2010 Letter Inspection Summary
12/28/2010 Letter Inspection Summary
12/29/2010 Letter Inspection Summary
01/04/2011 Letter Inspection Summary
01/07/2011 Letter Inspection Summary
01/12/2011 Letter Inspection Summary
01/12/2011 Letter Inspection Summary
01/19/2011 Letter Inspection Summary
01/19/2011 Letter Inspection Summary
01/19/2011 Letter Fire Loss Reduction Form
02/10/2011 Letter Inspection Summary
02/11/2011 Letter Inspection Summary
03/03/2011 Letter Inspection Summary
03/10/2011 Letter Inspection Summary
03/10/2011 Letter Inspection Summary
03/15/2011 Letter Inspection Summary
03/15/2011 Letter Inspection Summary
03/24/2011 Letter Inspection Summary
03/30/2011 Letter Fire Loss Reduction Form
03/30/2011 Letter Temporary Certificate of Occupancy
08/04/2011 Letter Field Certificate of Occupancy
08/05/2011 Letter Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home