Permit Application Status

B1000609


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000609
Building Permit - Commercial
Certificate of Occupancy
NEW COMMERCIAL
FIRE STATION NO 2
06/07/2010
08/20/2010
04/05/2011
09/26/2013
Locations
Contacts
BLUE RIVER PLUMBING INC, Address:152 NW 361ST RD  
KC ONE SERVICE COMPANY, Address:9923 W 65TH DR  
STRAUB CONSTRUCTION, Address:7775 MEADOW VIEW DR  
WSKF ARCHITECTS, INC, Address:110 ARMOUR RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/10/2011 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Correction

Codes Administration - Copies of the engineered truss package were not provided at the time of permit application.
Correction

Codes Administration - The project cost, which is used to establish the permit fee, has not been provided.
Correction

Codes Administration - 2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Correction

Fire Department- 2006 IFC 907.14 Fire-extinguishing systems. Automatic fire-extinguishing systems shall be connected to the building fire alarm system where a fire alarm system is required by another section of this code or is otherwise installed.
Correction

Fire Department- 2006 IFC 604.1.1 Stationary generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200.
Correction

Fire Department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

Codes Administration - Some of the detail identifiers on Sheet A1.02 refer to Sheet A1.03 which is not part of the package. The details are actually located on Sheet A1.02.
Correction

Codes Administration - Per Table 715.4 openings in one-hour fire barriers providing a separation between occupancy types are required to be protected by 45 minute assemblies. The door schedule indicates that door 108A is to be rated for 20 minutes.
Correction

Codes Administration - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

CA - The Final Development Plan must be approved prior to issuing full building permits.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $5,451.10 $5,451.10 Paid 08/20/2010
84 Water Meters $1,471.53 $1,471.53 Paid 08/20/2010
85 Water Taps $9,690.00 $9,690.00 Paid 08/20/2010
89 Sewer Tap Fees $510.00 $510.00 Paid 08/20/2010
Right of Way Permit $60.00 $60.00 Paid 08/20/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 08/25/2010
Correction
Partial Correction
08/25/2010
None GARAGE EXT. GRADE BEAM-SW TO SE CORNERS OK TO POUR BELOW:
Footing Inspection - Commercial Partial 08/26/2010
Correction
Partial Correction
08/26/2010
None -GARAGE EXT. GRADE BEAM CONTINUE C.C. AROUND LIVING AREAS OK TO POUR BELOW:
Footing Inspection - Commercial Partial 08/27/2010
Correction
Partial Correction
08/27/2010
None -EXT. GRADE BEAM FROM GARAGE CONTINUE C.C. AROUND LIVING AREAS -ALL INTERIOR FOOTING OK TO POUR BELOW:
Footing Inspection - Commercial Partial 08/30/2010
Correction
Partial Correction
08/30/2010
None -EXT. GRADE BEAM&COLUMN PADS FROM GARAGE CONTINUE COUNTER CLOCKWISE TO SE CORNER OF RM 102 -MID INTERIOR FOOTING FROM EAST-WEST OK TO POUR BELOW:
Footing Inspection - Commercial Partial 08/31/2010
Correction
Partial Correction
08/31/2010
None OK TO POUR BELOW: -EXT. GRADE BEAM&COLUMN PADS FROM GARAGE CONTINUE COUNTER CLOCKWISE AND COMPLETE TO GARAGE -MID INTERIOR FOOTING FROM EAST-WEST OK TO POUR BELOW:
Correction
Resolved
08/31/2010
None *2 INTERIOR AND ONE EXT. SE PADS AND SOUTH GRADE BEAM NOT ATTACHED TO BUILDING GRADE BEAM WERE NOT INSPECTED. THESE ALREADY POURED. TERRACON INSPECTOR SAID SHE ALREADY LOOKED AT THESE
Underslab Plumbing Inspection - Commercial Partial 09/13/2010
Correction
Partial Correction
09/13/2010
None UNDERSLAB PLUMBING OK BELOW: -RESTROOMS PER ALT DETAIL P1.03; UNISEX RESTRM 102&103; RM 134,135,136 -SOUTH BUILDING DRAIN
Underslab Electrical Inspection - Commercial Passed 09/21/2010
Underslab Plumbing Inspection - Commercial Passed 09/21/2010
Correction
Resolved
09/21/2010
None
Footing Inspection - Commercial Passed 09/21/2010
Correction
Resolved
09/21/2010
None OK TO POUR BELOW: -EXT. GRADE BEAM&COLUMN PADS FROM GARAGE CONTINUE COUNTER CLOCKWISE AND COMPLETE TO GARAGE -MID INTERIOR FOOTING FROM EAST-WEST -GARAGE DRAIN TRENCH OK TO POUR BELOW:
Water Service Inspection Passed 09/22/2010
Water Service Inspection - Commercial Request Complete 9/22/2010 9/22/2010 09/22/2010
Water Service Inspection - Commercial Request Complete 9/22/2010 9/22/2010 09/22/2010
Footing Inspection - Commercial Passed 11/10/2010 at 12:00 AM 11/10/2010
Misc
Resolved
11/10/2010
BUILDING AND TRASH ENCLOSURE FOOTING APPROVED
Underground Plumbing Inspection - Commercial Partial 11/30/2010 at 12:00 AM 11/30/2010
Misc
Partial Correction
11/30/2010
-APPROVED TO COVER BELOW: -UNDERGROUND SEWER FROM GARAGE TO OIL INTERCEPTOR
Underground Plumbing Inspection - Commercial Passed 12/1/2010 at 12:00 AM 12/01/2010
Misc
Resolved
12/01/2010
-UNDERGROUND PLUMBING FROM BUILDING TO RIGHT-OF-WAY IS APPROVED
Electrical Service Inspection Partial 12/1/2010 at 12:00 AM 12/01/2010
Misc
Partial Correction
12/01/2010
TEMPORARY ELECTRICAL SERVICE IS APPROVED FOR RELEASE
All Rough Inspection - Commercial Failed 12/15/2010 at 12:00 AM 12/15/2010
Misc
Corrective Action Required
12/15/2010
PROTECT PVC WHERE WITHIN 1.5" OF SURFACE OF BOTTOM TRACKS
All Rough Inspection - Commercial Partial 12/16/2010 at 12:00 AM 12/16/2010
Misc
Partial Correction
12/16/2010
-IN-WALL ALLROUGH-APPROVED FOR GYPSUM COVER
Gas Service Inspection - Commercial Failed 12/22/2010 at 12:00 AM 12/22/2010
Misc
Corrective Action Required
12/22/2010
INSTALL 2" SHUT-OFF VALVE NEAR ENTRY INTO MEZZANINE AND RE-PRESSURIZE FOR TEST
All Rough Inspection - Commercial Partial 12/22/2010 at 12:00 AM 12/22/2010
Misc
Partial Correction
12/16/2010
-IN-WALL ALL-ROUGH: ALL WALLS OK FOR GYPSUM COVER -ABOVE-CEILING ALL-ROUGH: BATHROOMS CEILING OK FOR COVER
Rough Framing Inspection - Commercial Passed 11/3/2010 at 12:00 AM 12/22/2010
Rated Assembly Inspection Passed 12/27/2010 at 12:00 AM 12/27/2010
Gas Service Inspection - Commercial Passed 12/27/2010 at 12:00 AM 12/27/2010
Above Ceiling Inspection Partial 1/12/2011 at 12:00 AM 01/12/2011
Misc
Partial Correction
01/12/2011
ABOVE CEILING APPROVED TO COVER BELOW: -CEILING LID IN RM 134,135,137,138
Above Ceiling Inspection Partial 2/4/2011 at 12:00 AM 02/04/2011
Misc
Partial Correction
01/12/2011
ABOVE CEILING APPROVED TO COVER BELOW: -CEILING LID IN RM 134,135,137,138, GARAGE AREA
Sprinkler - Hydrostatic Test Passed 2/9/2011 at 12:00 AM 02/09/2011
Above Ceiling Inspection Passed 2/10/2011 at 12:00 AM 02/10/2011
Misc
Resolved
02/10/2011
ABOVE CEILING APPROVED
Above Ceiling Inspection Passed 3/2/2011 at 12:00 AM 03/02/2011
Electrical Service Inspection Failed 3/8/2011 3/8/2011 at 12:00 AM 03/08/2011
E250.50 Grounding Electrode System
Corrective Action Required
03/08/2011
GROUND THE SERVICE TO ROD AND TO BUILDING STRUCTURAL STEEL PER PLAN. NOTE: CODE DOES NOT REQUIRE GROUNDING TO ROD SINCE THERE IS ALREADY A UFER GROUNDING AS SUPPLEMENTARY GROUNDING TO WATER. BUILDING STRUCTURAL STEEL GROUNDING IS STILL REQUIRED.
Misc
Corrective Action Required
03/08/2011
-INSTALL 4/0 COPPER TAP CONDUCTORS TO EACH 225 AMP PANEL. CURRENTLY HAS 3/0 COPPER CONDUCTORS -GENERATOR INSTALLATION NOT COMPLETED
Electrical Service Inspection Passed 3/9/2011 at 12:00 AM 03/09/2011
E250.50 Grounding Electrode System
Resolved
03/09/2011
GROUND THE SERVICE TO ROD AND TO BUILDING STRUCTURAL STEEL PER PLAN. NOTE: CODE DOES NOT REQUIRE GROUNDING TO ROD SINCE THERE IS ALREADY A UFER GROUNDING AS SUPPLEMENTARY GROUNDING TO WATER. BUILDING STRUCTURAL STEEL GROUNDING IS STILL REQUIRED.
Misc
Resolved
03/09/2011
-GENERATOR INSTALLATION NOT COMPLETED
Underground Electrical Inspection - Commercial Partial 3/11/2011 3/11/2011 at 12:00 AM 03/11/2011
Misc
Corrective Action Required
03/11/2011
UNDERGROUND ELECTRICAL AND 6 LIGHT POLES PIERS-OK
Underground Electrical Inspection - Commercial Passed 04/15/2011
Misc
Resolved
04/15/2011
UNDERGROUND ELECTRICAL AND 6 LIGHT POLES PIERS-OK
All Rough Inspection - Commercial Passed 04/15/2011
Misc
Resolved
04/15/2011
-IN-WALL ALL-ROUGH: ALL WALLS OK FOR GYPSUM COVER -ABOVE-CEILING ALL-ROUGH: BATHROOMS CEILING OK FOR COVER
Sprinkler - Flow Test Not Ready 4/15/2011 at 12:00 AM 04/15/2011
Alarm Test Not Ready 4/15/2011 at 12:00 AM 04/15/2011
Occupancy Inspection - Fire Not Ready 4/15/2011 at 12:00 AM 04/15/2011
Misc
Corrective Action Required
04/15/2011
Exterior egress lighting off kitchen not illuminating on DC power
Misc
Corrective Action Required
04/15/2011
electrical room, a sprinkler head blocked by a light fixture, needs 4' minimum clearance.
Misc
Corrective Action Required
04/15/2011
label the generator fuel tank, flammable, deisel ,and a NFPA 704 placard with the MSDS listins for diesel fuel
Misc
Corrective Action Required
04/15/2011
uncover all the smoke detectors, test the alarm system and the ansul system
Occupancy Inspection - Codes Commercial Failed 4/15/2011 at 12:00 AM 04/15/2011
Misc
Corrective Action Required
04/15/2011
-OBTAIN APPROVAL FROM THE FOLLOWING DEPARTMENTS: FIRE, PUBLIC WORKS, PLANNING AND DEVELOPMENT, WATER -PROVIDE SPECIAL INSPECTION REPORT
Misc
Corrective Action Required
04/15/2011
EXTERIOR RECEPTACLE NEAR TRANSFER SWITCH NOT TRIPPING
Misc
Corrective Action Required
04/15/2011
GENERATOR FRAME SHALL BE GROUNDED WITH 3/0 CONDUCTOR PER PLAN
Misc
Corrective Action Required
04/15/2011
BOXES SHALL NOT BE RECESSED MORE THAN 1/4" BEHIND NON-COMBUSTIBLE SURFACES; BOXES SHALL FLUSH OR EXTEND BEYOND COMBUSTIBLE SURFACES *CHECK ALL RECEPTACLES
Misc
Corrective Action Required
04/15/2011
ONE KITCHEN RECEPTACLE NOT TRIPPING
Misc
Corrective Action Required
04/15/2011
INSTALL LOCK DEVICES FOR HOOD AND WATER HEATER BREAKERS
Misc
Corrective Action Required
04/15/2011
PROVIDE AIR GAP AT WATER HEATER P/T DISCHARGE
Occupancy Inspection - Planning Temporary C of O 4/21/2011 at 12:00 AM 04/15/2011
Corrective Action Required
05/16/2011
Paint the vent louvers near the front door to match the surrounding EFIS/Stucco.
Corrective Action Required
05/16/2011
Add 4 shrubs, 2 on the east and 2 on the west, on the sides of the area of ground mounted mechanical units on the north side of the building. These are needed to meet the screening of mechanical units requirement in the UDO.
Sprinkler - Flow Test Passed 4/15/2011 at 12:00 AM 04/19/2011
Alarm Test Passed 4/19/2011 at 12:00 AM 04/19/2011
Occupancy Inspection - Fire Temporary C of O 4/19/2011 at 12:00 AM 04/19/2011
Misc
Corrective Action Required
04/19/2011
EXTERIOR EGRESS LIGHT OVER MAN DOOR OFF KITCHEN NOT ILLUMINATING ON DC POWER
Misc
Corrective Action Required
04/19/2011
Main electrical room: a sprinkler head is obstructed by a light fixture. 4" minimum clearance needed
Misc
Corrective Action Required
04/19/2011
label the emergency generators fuel tank with signage: FLAMMABLE, NO SMOKING, DIESEL, and a NFPA placard (sticker) with the MSDS hazard ratings for diesel fuel
Misc
Corrective Action Required
04/19/2011
Reprogram the outside horn/strobe notification device to activate only on a waterflow activation alarm. Reprogram the sprinkler riser tamper switches to be a supervisory siganl only, NO activation of interior notification devices.
Occupancy Inspection - Codes Commercial Temporary C of O 4/21/2011 4/21/2011 at 12:00 AM 04/21/2011
Misc
Corrective Action Required
04/15/2011
-OBTAIN APPROVAL FROM THE FOLLOWING DEPARTMENTS: FIRE (OK FOR TCO), PUBLIC WORKS, PLANNING AND DEVELOPMENT, WATER -PROVIDE SPECIAL INSPECTION REPORT
Misc
Resolved
04/21/2011
EXTERIOR RECEPTACLE NEAR TRANSFER SWITCH NOT TRIPPING
Misc
Resolved
04/21/2011
GENERATOR FRAME SHALL BE GROUNDED WITH 3/0 CONDUCTOR PER PLAN
Misc
Resolved
04/21/2011
BOXES SHALL NOT BE RECESSED MORE THAN 1/4" BEHIND NON-COMBUSTIBLE SURFACES; BOXES SHALL FLUSH OR EXTEND BEYOND COMBUSTIBLE SURFACES *CHECK ALL RECEPTACLES
Misc
Corrective Action Required
04/15/2011
ONE KITCHEN RECEPTACLE NOT TRIPPING
Misc
Corrective Action Required
04/15/2011
INSTALL LOCK DEVICES FOR WATER HEATER BREAKER OR INSTALL SWITCH WITHIN SIGHT OF WATER HEATER
Misc
Resolved
04/21/2011
PROVIDE AIR GAP AT WATER HEATER P/T DISCHARGE
Occupancy Inspection - Fire Temporary C of O 4/21/2011 at 12:00 AM 04/21/2011
Misc
Corrective Action Required
04/20/2011
EXTERIOR EGRESS LIGHT OVER MAN DOOR OFF KITCHEN NOT ILLUMINATING ON DC POWER
Misc
Corrective Action Required
04/20/2011
Main electrical room: a sprinkler head is obstructed by a light fixture. 4" minimum clearance needed
Misc
Corrective Action Required
04/20/2011
label the emergency generators fuel tank with signage: FLAMMABLE, NO SMOKING, DIESEL, and a NFPA placard (sticker) with the MSDS hazard ratings for diesel fuel
Misc
Corrective Action Required
04/20/2011
Reprogram the outside horn/strobe notification device to activate only on a waterflow activation alarm. Reprogram the sprinkler riser tamper switches to be a supervisory siganl only, NO activation of interior notification devices.
Occupancy Inspection - Fire Passed 04/27/2011
Misc
Corrective Action Required
04/27/2011
EXTERIOR EGRESS LIGHT OVER MAN DOOR OFF KITCHEN NOT ILLUMINATING ON DC POWER
Misc
Corrective Action Required
04/27/2011
Main electrical room: a sprinkler head is obstructed by a light fixture. 4" minimum clearance needed
Misc
Corrective Action Required
04/27/2011
label the emergency generators fuel tank with signage: FLAMMABLE, NO SMOKING, DIESEL, and a NFPA placard (sticker) with the MSDS hazard ratings for diesel fuel
Misc
Corrective Action Required
04/27/2011
Reprogram the outside horn/strobe notification device to activate only on a waterflow activation alarm. Reprogram the sprinkler riser tamper switches to be a supervisory siganl only, NO activation of interior notification devices.
Occupancy Inspection - Codes Commercial Temporary C of O 5/3/2011 at 12:00 AM 05/03/2011
Misc
Corrective Action Required
04/21/2011
-OBTAIN APPROVAL FROM THE FOLLOWING DEPARTMENTS: PUBLIC WORKS, PLANNING AND DEVELOPMENT, WATER
Misc
Resolved
05/03/2011
ONE KITCHEN RECEPTACLE NOT TRIPPING
Misc
Resolved
05/03/2011
INSTALL LOCK DEVICES FOR WATER HEATER BREAKER OR INSTALL SWITCH WITHIN SIGHT OF WATER HEATER
Occupancy Inspection - Planning Passed 05/16/2011
Occupancy Inspection - Engineering Passed 04/12/2013
Occupancy Inspection - Codes Commercial Full C of O 09/26/2013
Misc
Resolved
09/26/2013
-OBTAIN APPROVAL FROM THE FOLLOWING DEPARTMENTS: PUBLIC WORKS
Documents & Images
Date Uploaded File Type Document Name
11/10/2010 Letter Inspection Summary
11/10/2010 Letter Inspection Summary
11/30/2010 Letter Inspection Summary
12/01/2010 Letter Inspection Summary
12/15/2010 Letter Inspection Summary
12/15/2010 Letter Inspection Summary
12/16/2010 Letter Inspection Summary
12/22/2010 Letter Inspection Summary
12/27/2010 Letter Inspection Summary
01/12/2011 Letter Inspection Summary
02/04/2011 Letter Inspection Summary
02/09/2011 Letter Fire Loss Reduction Form
03/08/2011 Letter Inspection Summary
03/09/2011 Letter Inspection Summary
03/11/2011 Letter Inspection Summary
04/15/2011 Letter Fire Loss Reduction Form
04/15/2011 Letter Inspection Summary
04/15/2011 Letter Planning Inspection Summary
04/19/2011 Letter Fire Loss Reduction Form
04/21/2011 Letter Temporary Certificate of Occupancy
04/21/2011 Letter Fire Loss Reduction Form
04/27/2011 Letter Fire Loss Reduction Form
05/16/2011 Letter Planning Inspection Summary
08/21/2013 Letter Inspection Summary
08/21/2013 Letter Inspection Summary
09/26/2013 Letter Field Certificate of Occupancy
09/27/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home