Permit Application Status

B1000585


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000585
Building Permit - Commercial
Final Completion
RED SUMMIT FAIR LLC
ALTERATION COMMERCIAL
WHITE BOX INCLUDES 2 RESTROOMS, RTU'S, SOME INTERIOR PARTITIONS AND ELECTRICAL.
06/02/2010
07/09/2010
01/05/2011
08/20/2010
Locations
Contacts
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
REDLINE ELECTRIC LLC, Address:11918 A HWY  
BC ENGINEERS INC, Address:5720 REEDER  
MEYER COMPLETE, Address:200 NE MISSOURI RD, STE 100  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
L B A AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6226 MERRIAM DR  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 12/19/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway.
Correction

Codes Administration - 2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the evenet of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building requried to have two or more exits. 3. Exterior egress componenets at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Correction

Codes Administration - 2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbant surface that extends upward onto the walls at least 6 inches.
Correction

Codes Administration - 2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
Correction

Fire Department- The door from the display floor to the Egress corridor shall not be provided with a privacy lock set.
Correction

Codes Administration - 2005 NEC 210.62 - Show windows. At least one receptacle outlet shall be installed directly above a show window for each 3.7 linear m (12 linear ft) or major fraction thereof of show window area measured horizontally at its maximum width.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $824.75 $824.75 Paid 07/09/2010
89 Sewer Tap Fees $180.00 $180.00 Paid 07/09/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 07/13/2010
Correction
Partial Correction
07/13/2010
WALL FRAMING + IN-WALL SYSTEMS SEE MC SECURING ISSUE OK TO ONE-SIDE NORTH & SO DEMISING WALLS
Correction
Corrective Action Required
07/13/2010
INSTALLATION OF MC ELECTRICAL CABLE SECURELY FASTEN WITHIN 12" OF ENTRY TO ALL BOXES
Underslab Plumbing Inspection - Commercial Passed 07/13/2010
Correction
Resolved
07/13/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY OK TO COVER WHEN READY FOLLOWING SEGMENTS:
All Rough Inspection - Commercial Partial 07/16/2010
Correction
Partial Correction
07/16/2010
WALL FRAMING + IN-WALL SYSTEMS OK TO ONE-SIDE NORTH & SO DEMISING WALLS + N-S WALL @ J3.9; OK TO APPLY GWB TO EXISTING FRAMING @ JD.4/J3.9 TO JD.4/J5.5 TO JE.4/J5.5;
Correction
Resolved
07/16/2010
INSTALLATION OF MC ELECTRICAL CABLE
Rated Assembly Inspection Partial 07/16/2010
Correction
Partial Correction
07/16/2010
OK TO ONE-SIDE JE/J1 TO JE/J3.9; JG/J1 TO JG/J5.2; OK TO TAPE/MUD/FIRE-SEAL FOLLOWING WALL SEGMENTS:
All Rough Inspection - Commercial Partial 07/23/2010
Correction
Partial Correction
07/23/2010
WALL FRAMING + IN-WALL SYSTEMS NORTH & SOUTH DEMISING WALLS; N-S WALL @ J3.9; EXISTING FRAMING @ JD.4/J3.9 TO JD.4/J5.5 TO JE.4/J5.5; MEN'S RR; WOMEN'S RR; EXTERIOR WALL J5.5/JE.3 TO J5.5/JF; BULKHEAD ON J.1 FROM JE TO JG;
Rated Assembly Inspection Passed 07/23/2010
Correction
Resolved
07/23/2010
OK TO ONE-SIDE INCLUDING JE/J3.9 TO JE.6/J3.9 OK TO TAPE/MUD/FIRE-SEAL ALL NEW RATED WALLS
Correction
Resolved
07/23/2010
FIRE-SEALING OF INSIDE FACE OF NEW RATED WALLS APPROVED
Correction
Resolved
07/23/2010
LIMITATION OF RATED WALL CONSTRUCTION UNDER THIS PERMIT SCOPE COMPLETE INSIDE FACE ONLY
All Rough Inspection - Commercial Partial 07/27/2010
Correction
Partial Correction
07/27/2010
WALL FRAMING + IN-WALL SYSTEMS NORTH & SOUTH DEMISING WALLS; N-S WALL @ J3.9; EXISTING FRAMING @ JD.4/J3.9 TO JD.4/J5.5 TO JE.4/J5.5; MEN'S RR; WOMEN'S RR; EXTERIOR WALL J5.5/JE.3 TO J5.5/JF; BULKHEAD ON J.1 FROM JE TO JG;REAR WEST WALL(2 BOXS OUT OF ROOF DRAINS)FRAMING ELECT,APPROVED
All Rough Inspection - Commercial Partial 07/30/2010
Correction
Resolved
07/30/2010
None - WALLS & ELECTRICAL AT WEST OF WHITE BOX - APPROVED Walls & Electrical
Miscellaneous Inspection Failed 07/30/2010
Correction
Corrective Action Required
07/30/2010
Premises Identification (IRC) - NO FURTHER INSPECTIONS WILL BE DONE UNTIL ADDRESS IS POSTED ON WEST DOOR
All Rough Inspection - Commercial Passed 08/02/2010
Correction
Resolved
08/02/2010
WALL FRAMING + IN-WALL SYSTEMS N & S DEMISING WALLS; N-S WALL @ J3.9; EXSTG FRAM'G @ JD.4/J3.9 TO JD.4/J5.5 TO JE.4/J5.5; MEN'S RR; WOMEN'S RR; EXT WALL J5.5/JE.3 TO J5.5/JF; BULKHEAD ON J.1 FROM JE TO JG; W WALL(BOX-OUT OF ROOF DRAINS); INT PARTITIONS @ SALES; COLUMN BOX-OUT @ S.E. OK TO COVER WHEN READY WALLS LISTED BELOW:
Correction
Resolved
08/02/2010
None
Miscellaneous Inspection Passed 08/04/2010
Correction
Resolved
08/04/2010
Premises Identification (IRC)
Electrical Service Inspection Passed 08/04/2010
Correction
Resolved
08/04/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE BY FINAL INSPECTION AFFIX PERMANENT ADDRESS LABEL AT SERVICE METER 277/480V 3P 4W 48KVA XFMR PANEL P 120/208V 125A MCB
Above Ceiling Inspection Passed 08/09/2010
Correction
Resolved
08/09/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS SOFFIT AT EAST END; RESTROOMS OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Above Ceiling Inspection Passed 08/13/2010
Correction
Resolved
08/13/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS ABOVE-CEILING APPROVED
Gas Service Inspection - Commercial Passed 08/16/2010
Correction
Resolved
08/16/2010
GAS PIPING PRESSURE TEST RELEASE GAS SERVICE. NOTE: PERMANENT LABEL TO BE APPLIED TO GAS SERVICE; P.H. ADVISED. PRESSURE HELD STEADY AT >= 10 PSI FOR >=10 MIN
Gas Piping Inspection - Commercial Failed 08/16/2010
Correction
Corrective Action Required
08/16/2010
PROTECTION OF METALLIC PIPE AGAINST CORROSION IFGC 404.8 EXPOSED ROOFTOP PIPING PAINT OR OTHER APPROVED
Correction
Corrective Action Required
08/16/2010
PADDING UNDER ROOFTOP GAS PIPING SUPPORTS NOT CAREY TREAD PER DRWG
Final Inspection - Commercial Passed 08/19/2010
Correction
Resolved
08/19/2010
Receive Fire Department approval PER CPT JOE DIR 8/19/2010
Correction
Resolved
08/19/2010
CODES ADMINISTRATION FINAL INSPECTION NO ISSUES FOUND CLOSE PERMIT
Gas Piping Inspection - Commercial Passed 08/19/2010
Correction
Resolved
08/19/2010
PROTECTION OF METALLIC PIPE AGAINST CORROSION
Correction
Resolved
08/19/2010
PADDING UNDER ROOFTOP GAS PIPING SUPPORTS NOT CAREY TREAD PER DRWG APPROVED BY A/E
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home