Permit Application Status

B1000450


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000450
Building Permit - Commercial
Certificate of Occupancy
LBP IV LLC
NEW TENANT FINISH
INTERNAL REVENUE SERVICE TENANT FINISH
05/05/2010
08/19/2010
04/27/2011
12/29/2010
Locations
Contacts
UNITED HEATING & COOLING, Address:301 DUCK RD  
CLEARLINE PLUMBING, Address:14922 KNORPP RD  
CAPITAL CONSTRUCTION SERVICES, Address:2642 NE HAGAN RD  
BLUE SPRINGS ELECTRICAL, Address:3402 LAKESHORE DR  
LBP IV LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/21/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1003.3.3 - Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches over any walking surface between the heights of 27 inches and 80 inches above the walking surface.
Correction

Codes Administration - 2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.
Correction

Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Correction

Fire Department- The occupant load of the multi-purpose room exceeds 50, provide a second exit light from the space.
Correction

Fire Department- 2006 IFC 1008.1.3.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Correction

Codes Administration - 2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $5,890.64 $5,890.64 Paid 08/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 08/24/2010
Correction
Resolved
08/24/2010
None LOW VOLTAGE PHONE LINES OK
Underslab Plumbing Inspection - Commercial Passed 08/25/2010
Correction
Resolved
08/25/2010
None UNDERSLAB PLUMBING APPROVED
All Rough Inspection - Commercial Partial 09/20/2010
Correction
Partial Correction
09/20/2010
None ROOMS 107/110-118/124-129/170-176/150-151/182-184; CORRIDORS 144/149/159/167-169 IN-WALL APPROVED BELOW
All Rough Inspection - Commercial Partial 09/21/2010
Correction
Partial Correction
09/21/2010
None ROOMS 107/110-118/123-129/145-148/150-158/161-165/170-180/182-185; CORRIDORS 144/149/159/166-169 IN-WALL APPROVED BELOW
All Rough Inspection - Commercial Passed 09/24/2010
Correction
Resolved
09/24/2010
None IN-WALL ROUGHINS APPROVED TO COVER
Electrical Service Inspection Passed 09/30/2010
Correction
Resolved
09/30/2010
None 1000 AMP POWER DISCONNECT-SERVICE METER IS APPROVED FOR RELEASE
Rough Plumbing Inspection - Commercial Passed 10/07/2010
All Rough Inspection - Commercial Passed 10/07/2010
Correction
Resolved
10/07/2010
None ALL IN-WALL ROUGHINS-APPROVED TO COVER
Above Ceiling Inspection Failed 10/12/2010
Correction
Partial Correction
10/12/2010
None -NORTH VESTIBULE, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM OK BELOW
Rated Assembly Inspection Passed 10/14/2010
Correction
Resolved
10/14/2010
None RATED WALL/CEILING ASSY APPROVED PER PLAN-MDF/IDF ROOMS 122/139/173
Above Ceiling Inspection Partial 10/14/2010
Correction
Partial Correction
10/14/2010
None -VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS OK BELOW
Above Ceiling Inspection Partial 10/28/2010
Correction
Partial Correction
10/28/2010
None -VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS -RMS 121,123,126,138,145-147, 152-153, 156-157,170-185 OK BELOW
Above Ceiling Inspection Partial 11/1/2010 at 12:00 AM 11/01/2010
Correction
Partial Correction
10/31/2010
None -VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS -RMS114,115,116,118,120, 121,123,124,125,126,127,128,129,133,138,145-147, 152-153, 156-157,170-185 OK BELOW
Above Ceiling Inspection Not Ready 11/3/2010 at 12:00 AM 11/03/2010
Correction
Partial Correction
11/01/2010
None -VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS -RMS114,115,116,118,120, 121,123,124,125,126,127,128,129,133,138,145-147, 152-153, 156-157,170-185 OK BELOW
Misc
Corrective Action Required
11/03/2010
COMPLETE INSTALLATION OF ALL HVAC DIFFUSERS
Misc
Corrective Action Required
11/03/2010
CEILING GRID SUPPORT WIRES: 1) REFER TO MANUFACTURER'S INSTRUCTIONS FOR SPACING AND REQUIREMENTS 2) SUPPORT ONLY CEILING LOADS THEREFROM 3) ENSURE PATH OF WIRES IS STRAIGHT FROM ATTACHMENT @ GRID TO ATTACHMENT @ STRUCTURE -- NOT BENT AROUND DUCTS, PIPE, ETC
Misc
Corrective Action Required
11/03/2010
UNTERMINATED COILS OF MC ELECT CABLE LYING ABOVE GRID -- 2 LOCATIONS OR MORE
Misc
Corrective Action Required
11/03/2010
COMBUSTIBLE MATERIAL IN CEILING HVAC R.A. PLENUM SPACE NOT ALLOWED: SEE BOX BEAMS @ ACCORDIAN PARTITIONS
Misc
Corrective Action Required
11/03/2010
INSTALLATION OF CEILING GRID: NOT COMPLETED IN SOME SPACES REQUESTED FOR INSPECTION
Above Ceiling Inspection Partial 11/4/2010 at 12:00 AM 11/04/2010
Correction
Partial Correction
11/03/2010
OK BELOW: VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS -RMS114,115,116,118,120, 121,123,124,125,126,127,128,129,133,138,145-147, 152-153, 156-157,170-185; 159; 155; 154; 149; 144; 142; 141; 107; 106 (LEAVE OUT 2 TILES @ DISCONTINUOUS C.I. PIPE); 150; 150/161 (LEAVE OUT TILE @ BOX BEAM);
Misc
Resolved
11/04/2010
COMPLETE INSTALLATION OF ALL HVAC DIFFUSERS
Misc
Resolved
11/04/2010
CEILING GRID SUPPORT WIRES: 1) REFER TO MANUFACTURER'S INSTRUCTIONS FOR SPACING AND REQUIREMENTS 2) SUPPORT ONLY CEILING LOADS THEREFROM 3) ENSURE PATH OF WIRES IS STRAIGHT FROM ATTACHMENT @ GRID TO ATTACHMENT @ STRUCTURE -- NOT BENT AROUND DUCTS, PIPE, ETC
Misc
Resolved
11/04/2010
UNTERMINATED COILS OF MC ELECT CABLE LYING ABOVE GRID -- 2 LOCATIONS OR MORE
Misc
Corrective Action Required
11/03/2010
COMBUSTIBLE MATERIAL IN CEILING HVAC R.A. PLENUM SPACE NOT ALLOWED: SEE BOX BEAMS @ ACCORDIAN PARTITIONS
Misc
Resolved
11/04/2010
INSTALLATION OF CEILING GRID: NOT COMPLETED IN SOME SPACES REQUESTED FOR INSPECTION
Above Ceiling Inspection Not Ready 11/9/2010 at 12:00 AM 11/09/2010
Correction
Partial Correction
11/04/2010
OK BELOW: VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS -114-116,118,120, 121-129,133,138, 141-142, 144-147, 149-150, 152-157, 159, 161-162, 170-185; 107; 106 (LEAVE OUT 2 TILES @ DISCONTINUOUS C.I. PIPE)
Misc
Corrective Action Required
11/04/2010
COMBUSTIBLE MATERIAL IN CEILING HVAC R.A. PLENUM SPACE NOT ALLOWED: SEE BOX BEAMS @ ACCORDIAN PARTITIONS
Above Ceiling Inspection Partial 11/11/2010 at 12:00 AM 11/11/2010
Correction
Partial Correction
11/09/2010
OK BELOW: VESTIBULE RM 119, SOFFIT OUTSIDE RESTROOMS, EAST ENTRANCE RESTROOM, IDF/MDF RMS -110-129,133-138, 140-142, 144-147, 149-157, 159, 161-162, 170-185; 107; 106 (LEAVE OUT 2 TILES @ DISCONTINUOUS C.I. PIPE)
Misc
Corrective Action Required
11/09/2010
COMBUSTIBLE MATERIAL IN CEILING. SEE BOX BEAMS SUPPORTING STUDS @ ACCORDIAN PARTITIONS
Above Ceiling Inspection Passed 11/23/2010 at 12:00 AM 11/23/2010
Correction
Resolved
11/23/2010
Misc
Resolved
11/23/2010
Rough Electrical Inspection - Commercial Passed 11/23/2010
Correction
Resolved
11/23/2010
-ELECTRICAL EQUIPMENTS IN DISTRIBUTION RM-OK
Sprinkler - Hydrostatic Test Passed 11/24/2010 at 12:00 AM 11/29/2010
Sprinkler - Flow Test Passed 11/29/2010
Alarm Test Passed 11/29/2010
Occupancy Inspection - Fire Temporary C of O 11/29/2010
Occupancy Inspection - Codes Commercial Temporary C of O 11/29/2010 at 12:00 AM 11/29/2010
Misc
Corrective Action Required
11/29/2010
-FIRE OK FOR TCO
Misc
Resolved
12/07/2010
Misc
Resolved
12/07/2010
WALL AT FRONT DRINKING FOUNTAIN
Misc
Resolved
12/07/2010
OCCUPANCY LOAD SIGNS PER PLAN
Occupancy Inspection - Fire Passed 12/29/2010 at 12:00 AM 12/29/2010
Occupancy Inspection - Codes Commercial Full C of O 12/29/2010 at 12:00 AM 12/29/2010
Misc
Resolved
12/29/2010
Misc
Resolved
12/27/2010
Misc
Resolved
12/27/2010
Misc
Resolved
12/27/2010
Documents & Images
Date Uploaded File Type Document Name
11/01/2010 Letter Inspection Summary
11/03/2010 Letter Inspection Summary
11/04/2010 Letter Inspection Summary
11/09/2010 Letter Inspection Summary
11/09/2010 Letter Inspection Summary
11/11/2010 Letter Inspection Summary
11/23/2010 Letter Inspection Summary
11/29/2010 Letter Temporary Certificate of Occupancy
11/29/2010 Letter Fire Loss Reduction Form
12/29/2010 Letter Fire Loss Reduction Form
12/29/2010 Letter Field Certificate of Occupancy
12/30/2010 Letter Final Certificate of Occupancy
12/30/2010 Letter Final Certificate of Occupancy
12/30/2010 Letter Final Certificate of Occupancy
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home