Permit Application Status

B1000449


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000449
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
FULL TENANT FINISH IN UNOCCUPIED SPACE
05/05/2010
07/19/2010
03/22/2011
09/24/2010
Locations
Contacts
RETAIL CONSTRUCTION SERVICES INC, Address:11343 39TH ST NORTH  
THE BUCKLE, INC, Address:12915 JONES MALTSBERGER, SUITE 302  
MICHAEL R. BLACK, AIA, Address:3100 EAST RANDOL MILL ROAD  
BRIGHT PLUMBING, Address:220 NW COMMERCE CT  
DONALDSON MECHANICAL INC., Address:934 B SE 7TH TR  
RODINA COMPANY INC, Address:1721 N 69TH LN  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/10/2011 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff.
Correction

Codes Administration - I believethe location shown on the Area Map and Key Plan on Sheet T1 is incorrect. The star is located on a shell building which has not been constructed yet. This tenant space would back up to a corridor and your space runs the full depth of the building. I believe the actual location per the address provided and our most current copy of the landlords tenant layout is diagnolly across the intersection.
Correction

Codes Administration - 2005 NEC 210.62 - Show windows. At least one receptacle outlet shall be installed directly above a show window for each 3.7 linear m (12 linear ft) or major fraction thereof of show window area measured horizontally at its maximum width.
Correction

Codes Administration - Information on the shell building plans regarding the mechanical zone states "Area has been designed for 2000# maximum per unit weight (curb and rtu operating weight). Rtu's shall be arranged such that no more than one rtu shall load the same joist".
Correction

Codes Administration - A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Correction

Fire Department-2006 IFC 1005.2 Door encroachment. Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 7 inches (178 mm) into the required width. Exception: The restrictions on a door swing shall not apply to doors within individual dwelling units and sleeping units of Group R-2 and dwelling units of Group R-3.
Correction

Fire Department- 2006 IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Correction

Fire Department- The A drawings indicate the east wall is an exterior wall, however the overall site drawing shows the east as part of the of the shell building corridor. Please clarify.
Correction

Fire Department - All plans submitted for review on or after July 9, 2007 shall be designed to the requirements of the 2006 International Building Code, 2006 International Mechanical Code, 2006 International Plumbing Code, 2006 International Fuel Gas Code, 2006 International Fire Code, 2005 National Electric Code and the ANSI A117.1-2003 as amended and adopted by the City of Lee's Summit.
Correction

Codes Administration - 2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,055.04 $1,055.04 Paid 07/19/2010
89 Sewer Tap Fees $150.00 $150.00 Paid 07/19/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 07/23/2010
Correction
Resolved
07/23/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Underslab Electrical Inspection - Commercial Passed 07/23/2010
Correction
Resolved
07/23/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
Rated Assembly Inspection Partial 07/23/2010
Correction
Partial Correction
07/23/2010
GWB AT UL RATED WALL NOTE: UNPROTECTED OPENING NOT ALLOWABLE WHERE PVC ROOF DRAIN PIPING PENETRATES RATED WALL. NORTH DEMISING WALL OK TO TAPE/MUD/FIRE-SEAL
All Rough Inspection - Commercial Failed 07/30/2010
Correction
Corrective Action Required
07/30/2010
See Comment - OKAY TO ROCK ONE SIDE OF INTERIOR WALLS NO ELECTRICAL OR PLUMBING READY - DO NOT ROCK FINISH WALLS ON NORTH & SOUTH SIDE UNTIL ELECTICAL APPROVED. Interior Walls
Correction
Corrective Action Required
07/30/2010
Soffit - SOFFIT NOT FINISHED - DO NOT ROCK
Correction
Partial Correction
07/30/2010
See Comment - RETURN AIR - NOT STUBBED TO RTU. - THREE (3) MULTI SECTION LATERALS - INSTALL ADDITIONAL SUPPORT WIRES. OKAY TO WRAP
All Rough Inspection - Commercial Failed 08/04/2010
Correction
Resolved
08/04/2010
See Comment
Correction
Corrective Action Required
08/04/2010
Soffit
Correction
Resolved
08/04/2010
See Comment
Correction
Corrective Action Required
08/04/2010
INSTALLATION OF MC ELECTRICAL CABLE NEC 300-11 & 334-10 SECURELY FASTEN WITHIN 12" OF ENTRY TO BOXES
Correction
Corrective Action Required
08/04/2010
MOUNTING OF IN-WALL ELECTRICAL BOXES TO PREVENT MOVEMENT OF BOX WHEN USED SECURE AGAINST DEFLECTION USE STAND-OFFS OR EQUAL
Correction
Corrective Action Required
08/04/2010
FRAMING OF BULKHEADS AT PERIMETER SOFFITS SCREW ALL FLANGES AT CONNECTION POINTS HANGING STRUCTURES CONNECTIONS NOT COMPLETE
Correction
Corrective Action Required
08/04/2010
PROTECTION OF PVC PIPING FROM PENETRATION IPC 305.8: INSTALL SHIELD PLATES AT STUDS & PLATES/TRACKS. SHIELD PLATES SHALL COVER THE AREA OF THE PIPE PENETRATION AND SHALL EXTEND A MINIMUM OF 2" ABOVE BOTTOM PLATES & BELOW TOP PLATES. CHECK ALL. WHERE < 1-1/2" FROM FACE OF FRAMING TO RECEIVE GWB
All Rough Inspection - Commercial Partial 08/06/2010
Correction
Resolved
08/06/2010
Soffit
Correction
Resolved
08/06/2010
INSTALLATION OF MC ELECTRICAL CABLE
Correction
Resolved
08/06/2010
MOUNTING OF IN-WALL ELECTRICAL BOXES
Correction
Resolved
08/06/2010
FRAMING OF BULKHEADS AT PERIMETER SOFFITS
Correction
Resolved
08/06/2010
PROTECTION OF PVC PIPING FROM PENETRATION
Correction
Partial Correction
08/06/2010
WALL FRAMING + IN-WALL SYSTEMS EXTERIOR WALLS; INTERIOR WALLS/PARTITIONS; PERIMETER BULKHEADS/SOFFITS; OK TO COVER WHEN READY FRAMING LISTED BELOW:
Above Ceiling Inspection Partial 08/06/2010
Correction
Partial Correction
08/06/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO PLACE PLYWOOD DECK ABOVE SPACES: MEN'S RR, WOMEN'S RR, EXIT CORRIDOR, OFFICE; OK TO COVER WHEN READY ELEMENTS DESCRIBED BELOW:
Electrical Service Inspection Passed 08/11/2010
Correction
Resolved
08/11/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE 277/480V 3P 4W 75KVA XFMR > 120 208V 3P 4W 200A
Above Ceiling Inspection Partial 08/12/2010
Correction
Partial Correction
08/12/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS OK TO PLACE PLYWOOD DECK ABOVE SPACES: MEN'S RR, WOMEN'S RR, EXIT CORRIDOR, OFFICE. OK FOR GWB AT: OFFFICE; FITTING ROOMS; SOFFITS @ SE ENTRANCE, EAST & SOUTH SHOW WINDOWS, ARCH @ SALES AREA CENTER, CORRIDOR OK TO COVER WHEN READY ELEMENTS DESCRIBED BELOW:
Rated Assembly Inspection Partial 08/16/2010
Correction
Partial Correction
08/16/2010
GWB AT UL RATED WALL NOTE: UNPROTECTED OPENING NOT ALLOWABLE WHERE PVC ROOF DRAIN PIPING PENETRATES RATED WALL. *HOLES THROUGH DEMISING WALL WHERE SPRINKLER LINES WERE REMOVED MUST BE PATCHED. HAVE THIS DONE BEFORE ABOVE CEILING INSPECTION NORTH DEMISING WALL OK TO TAPE/MUD/FIRE-SEAL
Above Ceiling Inspection Failed 08/19/2010
Correction
Resolved
08/19/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS OK FOR GWB AT: OFFFICE; FITTING ROOMS; SOFFITS @ SE ENTRANCE, EAST & SOUTH SHOW WINDOWS, ARCH @ SALES AREA CENTER, CORRIDOR, RESTROOMS OK TO COVER WHEN READY ELEMENTS DESCRIBED BELOW:
Correction
Corrective Action Required
08/19/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS, CONT'D 1) WELD TRUSS GIRDER BOTTOM CHORD BRACES 2) COMPLETE HVAC DIFFUSSER CONNECTORS 3) SUPPORT OF CLOUDS NOT PER DRAWING -- CONSULT A/E AND PROVIDE WRITTEN A/E SPECIFIC ENDORSEMENT OF VARIATION. CLOUDS SEE ISSUES BELOW:
Above Ceiling Inspection Passed 08/23/2010
Correction
Resolved
08/23/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS, CONT'D 1) WELD TRUSS GIRDER BOTTOM CHORD BRACES 2) COMPLETE HVAC DIFFUSSER CONNECTORS 3) SUPPORT OF CLOUDS NOT PER DRAWING -- CONSULT A/E AND PROVIDE WRITTEN A/E SPECIFIC ENDORSEMENT OF VARIATION. CLOUDS + RESTROOMS ISSUES RESOLVED:
Above Ceiling Inspection Passed 09/16/2010
Correction
Resolved
09/16/2010
None OKAY TO HANG TILE
Rated Assembly Inspection Passed 09/20/2010
Correction
Resolved
09/20/2010
GWB AT UL RATED WALL NOTE: UNPROTECTED OPENING NOT ALLOWABLE WHERE PVC ROOF DRAIN PIPING PENETRATES RATED WALL. *HOLES THROUGH DEMISING WALL WHERE SPRINKLER LINES WERE REMOVED MUST BE PATCHED. HAVE THIS DONE BEFORE ABOVE CEILING INSPECTION INSPECTED DURING ABOVE CEILIN NORTH DEMISING WALL OK TO TAPE/MUD/FIRE-SEAL
All Rough Inspection - Commercial Passed 09/20/2010
Correction
Resolved
09/20/2010
WALL FRAMING + IN-WALL SYSTEMS EXTERIOR WALLS; INTERIOR WALLS/PARTITIONS; PERIMETER BULKHEADS/SOFFITS; OK TO COVER WHEN READY FRAMING LISTED BELOW:
Occupancy Inspection - Codes Commercial Failed 09/20/2010
Correction
Partial Correction
09/20/2010
Receive Fire Department approval - RECEIVE UNDER SEPARATE COVER
Correction
Corrective Action Required
09/20/2010
Service Panel Labels - BREAKERS 5 & 16 MISSING LABELED. Service Panel B
Occupancy Inspection - Codes Commercial Passed 09/23/2010
Correction
Resolved
09/23/2010
Receive Fire Department approval
Correction
Resolved
09/23/2010
Service Panel Labels
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home