Permit Application Status

B1000368


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000368
Building Permit - Commercial
Final Completion
NEW TENANT FINISH
GREEN BEAUTY SALON TENANT FINISH
04/19/2010
04/28/2010
02/20/2011
05/14/2012
Locations
Contacts
CRAIG A LUEBBERT, ARCHITECT, LLC, Address:230 SW MAIN ST STE 203  
HYDRO-TECH PLUMBING INC, Address:622 NW HEADY AVE  
AMERICAN ELECTRIC INC, Address:27606 E PINK HILL RD  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD  
BARSTO CONSTRUCTION, INC, Address:1601 IRON ST NORTH  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 10/25/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - 2006 IBC 1010.8 - Handrails. Ramps with a rise greater than 6 inches shall have handrails on both sides. Handrails shall comply with Section 1012.
Correction

Codes Administration - 2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Correction

Codes Administration - The floor/ceiling above this space is fire-resistive occupancy separation.
Correction

Codes Administration - 2006 IBC 1003.5 - Elevation change. Where changes in elevations of less than 12 inches exist in the means of egress, sloped surfaces shall be used. Where the slope is greater than one unit vertical in 20 units horizontal, ramps complying with Section 1010 shall be used. Where the difference in elevations is 6 inches or less, the ramp shall be equipped with either handrails or floor finish materials that contrast with adjacent floor finish materials.
Correction

Codes Administration - 2006 IBC 1109.12.1 - Dressing, fitting and locker rooms. Where dressing rooms, fitting rooms or locker rooms are provided, at least 5 percent, but not less than one, of each type of use in each cluster provided shall be accessible.
Correction

Codes Administration - It has been my experience that KCPL will not allow two services for one tenant space.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $153.86 $153.86 Paid 04/28/2010
0120 Building INVEST. Fee $153.86 $153.86 Paid 04/28/2010
89 Sewer Tap Fees $360.00 $360.00 Paid 04/28/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Framing Inspection - Commercial Passed 05/03/2010
Correction
Resolved
05/03/2010
FRAMING OF SOUTH DEMISING WALL FRAMING ONLY; NO MEP OK TO COVER WHEN READY
All Rough Inspection - Commercial Failed 05/03/2010
Correction
Partial Correction
05/03/2010
READINESS FOR INSPECTION HVAC CONTRACTOR NOT LISTED ON PERMIT
Correction
Corrective Action Required
05/03/2010
PVC PIPING & PEX PLUMBING TUBING RUN THROUGH STUDS PROTECT WHERE EDGE OF BORE IS WITHIN 1 1/2" OF FACE OF STUDS & PLATES NOT PROTECTED WHERE WITHIN 1-1/2" FROM FACE
Correction
Corrective Action Required
05/03/2010
PEX PENETRATIONS THROUGH STUDS OR SUBSTITUTE SPRAY FOAM WHERE GROMMETS ARE INEFFECTIVE. ENSURE ALL GROMMETS IN PLACE & SOLID
Correction
Corrective Action Required
05/03/2010
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS SCREW ALL CONNECTIONS FULL HEIGHT OF WALL
All Rough Inspection - Commercial Partial 05/04/2010
Correction
Partial Correction
05/04/2010
READINESS FOR INSPECTION HVAC CONTRACTOR NOT LISTED ON PERMIT
Correction
Partial Correction
05/04/2010
PVC PIPING & PEX PLUMBING TUBING RUN THROUGH STUDS
Correction
Partial Correction
05/04/2010
PEX PENETRATIONS THROUGH STUDS
Correction
Partial Correction
05/04/2010
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS
Correction
Partial Correction
05/04/2010
WALL FRAMING + IN-WALL SYSTEMS 101; 101A; 102; 103; 104; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Occupancy Inspection - Codes Commercial Partial 05/07/2010
Correction
Partial Correction
05/07/2010
OCCUPANCY APPROVAL STATUS {101; 101A; 102; 103; 104} SUBJECT TO RE-INSPECTION WHEN EQUIPMENT IS INSTALLED, ANSI RESTROOM SIGN IS IN PLACE, ELECTRICAL PANEL SCHEDULE IS COMPLETED;.. SPACES LISTED BELOW OK FOR USE/OCCUPANCY
Correction
Partial Correction
05/07/2010
Receive Fire Department approval 101; 101A; 102; 103; 104 PER CH BRYAN AUSTERMAN FOLLOWING SPACES OK
All Rough Inspection - Commercial Partial 05/07/2010
Correction
Partial Correction
05/07/2010
WALL FRAMING + IN-WALL SYSTEMS 101; 101A; 102; 103; 104; 105; 106; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
All Rough Inspection - Commercial Partial 05/11/2010
Correction
Resolved
05/11/2010
PVC PIPING & PEX PLUMBING TUBING RUN THROUGH STUDS
Correction
Resolved
05/11/2010
PEX PENETRATIONS THROUGH STUDS
Correction
Resolved
05/11/2010
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS
Correction
Partial Correction
05/11/2010
WALL FRAMING + IN-WALL SYSTEMS 101; 101A; 102; 103; 104; 105; 106; 107; 107A; 108; 109; 110; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Rated Assembly Inspection Passed 05/12/2010
Correction
Resolved
05/12/2010
GWB AT UL RATED WALL BOTH FACES SOUTH DEMISING WALL OK TO COVER WHEN READY
Occupancy Inspection - Codes Commercial Failed 05/14/2010
Correction
Partial Correction
05/14/2010
OCCUPANCY APPROVAL STATUS SUBJECT TO RE-INSPECTION WHEN EQUIPMENT INSTALLED SEE TEMPORARY OCCUPANCY
Correction
Partial Correction
05/14/2010
Receive Fire Department approval FULL COMPLIANCE REQUIRED PRESENTLY SEE F.D. REPORT PROVIDED
Correction
Corrective Action Required
05/14/2010
ANSI RESTROOM SIGN WHEN EQUIPMENT IS INSTALLED ELECTRICAL PANEL SCHEDULE IS COMPLETED;.. TO BE AFFIXED ACCESSIBLE RESTROOM DOOR
Correction
Corrective Action Required
05/14/2010
HVAC SYSTEM SUBJECT TO APPROVAL WHEN INSTALLED
Correction
Corrective Action Required
05/14/2010
SOUTH RESTROOM IF REVISED CONFIGURATION IS APPROVED, ENSURE WALL FINISHES ARE NON-ABSORBENT (E.G. EPOXY PAINT) NOT BUILT PER PLAN NOT APPROVED FOR USE
Correction
Corrective Action Required
05/14/2010
INSTALLATION OF ELECTRICAL RECEPTACLES/SWITCHES NEC 380-10; 410-56(f) CHECK ALL SOME NOT TIGHT TO BOX MAKE ALL SOLID TO BOX
Occupancy Inspection - Codes Commercial Failed 06/09/2010
Correction
Corrective Action Required
06/09/2010
SOUTH RESTROOM NOT APPROVED FOR USE. ENSURE WALL AND FLOOR FINISHES ARE NON-ABSORBENT (E.G. EPOXY PAINT). MEN'S 111 NOT BUILT PER PLAN
Occupancy Inspection - Codes Commercial Failed 06/11/2010
Correction
Corrective Action Required
06/11/2010
ACCESSIBILITY RAMP TO BE CONSTRUCTED SUBJECT TO APPROVAL
Correction
Resolved
06/11/2010
Receive Water Utilities Approval NO ISSUES PER BEN HASKAMP 6/11/2010
Correction
Corrective Action Required
06/11/2010
FINAL INSPECTION OF RATED WALL TYPE "A" SUBJECT TO APPROVAL
Above Ceiling Inspection Not Ready 06/11/2010
Correction
Corrective Action Required
06/11/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ RESTROOMS SUBJECT TO APPROVAL WHEN READY
Occupancy Inspection - Codes Commercial Failed 06/23/2010
Correction
Partial Correction
06/23/2010
OCCUPANCY APPROVAL STATUS SEE TEMPORARY OCCUPANCY
Correction
Resolved
06/23/2010
Receive Fire Department approval PER CPT JOE DIR 6/23/2010
Correction
Resolved
06/23/2010
HVAC SYSTEM
Correction
Partial Correction
06/23/2010
SOUTH RESTROOM WALL AND FLOOR FINISHES IN PROGRESS. CEILING STRUCTURE AND ABOVE-CEILING SYSTEMS SUBJECT TO APPROVAL BEFORE ANY CEILING TILE IS PLACED. MEN'S 111 PARTIALLY-COMPLETED
Correction
Resolved
06/23/2010
INSTALLATION OF ELECTRICAL RECEPTACLES/SWITCHES MADE SOLID TO BOX
Correction
Corrective Action Required
06/23/2010
FINAL INSPECTION OF RATED WALL TYPE "A" SUBJECT TO APPROVAL WHEN ALL ELSE COMPLETED
Above Ceiling Inspection Failed 08/12/2010
Correction
Corrective Action Required
08/12/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ RESTROOMS TWO RESTROOMS + SOUTH MASSAGE ROOM
Correction
Corrective Action Required
08/12/2010
SUSPENSION OF CEILING GRID MUST BE HUNG FROM STRUCTURE -- NOT FROM M/E/P SYSTEMS SUCH AS WATER PIPE WIRE GUAGE NOT PER MFGR + SPACING NOT 4' C/C +
Correction
Corrective Action Required
08/12/2010
INSTALLATION OF MC ELECTRICAL CABLE NEC 300-11 & 334-10 [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG] MUST BE SECURELY FASTENED WITHIN 12" OF BOXES
Above Ceiling Inspection Passed 08/25/2010
Correction
Resolved
08/25/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ RESTROOMS TWO RESTROOMS + SOUTH MASSAGE ROOM
Correction
Resolved
08/25/2010
SUSPENSION OF CEILING GRID
Correction
Resolved
08/25/2010
INSTALLATION OF MC ELECTRICAL CABLE
Final Inspection - Commercial Passed 5/11/2012 at 12:00 AM 05/11/2012
All Rough Inspection - Commercial Passed 5/14/2012 at 12:00 AM 05/14/2012
Correction
Resolved
05/14/2012
WALL FRAMING + IN-WALL SYSTEMS 101; 101A; 102; 103; 104; OK TO COVER WHEN READY WALLS@SPACES LISTED BELOW
Correction
Resolved
05/14/2012
READINESS FOR INSPECTION HVAC CONTRACTOR NOT LISTED ON PERMIT
Correction
Resolved
05/14/2012
PVC PIPING & PEX PLUMBING TUBING RUN THROUGH STUDS
Correction
Resolved
05/14/2012
PEX PENETRATIONS THROUGH STUDS
Correction
Resolved
05/14/2012
CONNECTIONS OF LIGHT GUAGE FRAMING WITHIN WIDTH OF WALL OPENINGS
Documents & Images
Date Uploaded File Type Document Name
05/11/2012 Letter Inspection Summary
05/11/2012 Letter Inspection Summary
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home