Permit Application Status

B1000353


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
B1000353
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
CHARMING CHARLIE TENANT FINISH
04/15/2010
05/12/2010
11/08/2010
07/07/2010
Locations
Contacts
TEMP CON INC, Address:15670 S. KEELER  
ROZIER ELECTRIC, INC., Address:1608 SW JEFFERSON  
MENEMSHA CONSTRUCTION, Address:4950 W 145TH ST  
TRITON PLUMBING, Address:1016 KAYCEE DR  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 11/06/2010 10/29/2010
Correction

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenat commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Correction

Fire Department- 2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Correction

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Correction

Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Correction

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
Correction

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Correction

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Correction

Codes Administration - ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Correction

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Correction

Codes Administration - 2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.
Correction

Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Correction

Fire Department- Exterior emergency lighting is required per IFC 1006.3 .
Correction

Codes Administration - Notes on Detail 5 on Sheet A4.01 are overlapped.
Correction

Codes Administration - Note 9 on Sheet EIJK1.01 of the shell building plans indicates that exit signage and exterior emergency lighting at the storefront doors is to be installed on the tenant finish. To my knowledge these items have not been installed as they had no idea where the doors would be.
Fees
Paid Fees Amount Paid Owing Date Paid
0120 Building Permit Fee $1,428.70 $1,428.70 Paid 05/12/2010
89 Sewer Tap Fees $180.00 $180.00 Paid 05/12/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 05/21/2010
Correction
Resolved
05/21/2010
UNDER-SLAB SANITARY WASTE, SOIL, VENT PIPING OK TO COVER WHEN READY
Underslab Electrical Inspection - Commercial Passed 05/21/2010
Correction
Resolved
05/21/2010
UNDER-SLAB ELECTRICAL CONDUIT OK TO COVER WHEN READY MATERIAL & WORKMANSHIP NO ISSUES FOUND
All Rough Inspection - Commercial Partial 05/27/2010
Correction
Corrective Action Required
05/27/2010
WALL FRAMING + IN-WALL SYSTEMS ALL EXCEPT EAST EXT WALL AND NORTH EXT WALL EAST OF C/L J3.8 AND WEST (PLUMBING) WALL OF RR 105; INCLUD'G ENCLOSED SOFFITS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 05/28/2010
Correction
Partial Correction
05/28/2010
WALL FRAMING + IN-WALL SYSTEMS ALL EXCEPT EAST EXT WALL AND NORTH EXT WALL EAST OF C/L J3.8; INCLUD'G ENCLOSED SOFFITS OK TO COVER WHEN READY
All Rough Inspection - Commercial Partial 05/28/2010
All Rough Inspection - Commercial Partial 06/02/2010
Correction
Resolved
06/02/2010
None - 2' SOFFIT - FROM J4.5 TO J1 - ON NORTH WALL. - SOFFIT FROM J1 TO JL5 ON EAST WALL
All Rough Inspection - Commercial Passed 06/08/2010
Correction
Resolved
06/08/2010
WALL FRAMING + IN-WALL SYSTEMS ALL EXCEPT EAST EXT WALL AND NORTH EXT WALL EAST OF C/L J3.8; VERTICAL FRAMING & ROUGH ELECT @ S WALL + WEST CASH WRAP INCLUD'G ENCLOSED SOFFITS OK TO COVER WHEN READY
Above Ceiling Inspection Not Ready 06/09/2010
Correction
Corrective Action Required
06/09/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS
Above Ceiling Inspection Partial 06/10/2010
Correction
Partial Correction
06/10/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS EAST N-S BAY; CENTER N-S BAY; EAST PERIMETER SOFFIT; NORTH PERIMETER SOFFIT; INCL SUSPENDED "CLOUDS" OK TO COVER WHEN READY:
Above Ceiling Inspection Partial 06/11/2010
Correction
Partial Correction
06/11/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS EAST N-S BAY; CENTER N-S BAY; EAST PERIMETER SOFFIT; NORTH PERIM SOFFIT; WEST N-S BAY; NW CORNER; CORRIDORS ENSURE TEMP ELECT WIRING & FIXTURES ARE REMOVED. NOTE: TRUSS JOIST BOTTOM CHORD BRACES YET TO BE WELDED @ UPPER ENDS AFTER RTU'S ARE INSTALLED. INCL SUSPENDED "CLOUDS" OK TO COVER WHEN READY:
Electrical Service Inspection Passed 06/15/2010
Correction
Resolved
06/15/2010
ELECTRICAL SERVICE INSTALLATION RELEASE SERVICE 277/480V 3P 4W 400A MCB 75 KVA XMFR
Rough Electrical Inspection - Commercial Passed 06/17/2010
Correction
Resolved
06/17/2010
WIRING OF LUMINAIRES @ RECESSED CABINETS JUNCTION BOXES WILL BE ACCESSIBLE WHEN CABINETS ARE REMOVED FROM RECESSES. OK TO PROCEED WITH TERMINATION IN 1900 BOXES
Occupancy Inspection - Codes Commercial Not Ready 06/28/2010
Correction
Resolved
06/28/2010
Receive Fire Department approval PER CPT JOE DIR 6/28/2010
Correction
Resolved
06/28/2010
Receive Water Utilities Approval PER BEN HASKAMP 6/28/2010
Correction
Corrective Action Required
06/28/2010
INSTALLATION OF LIGHTED SIGN PER NEC 600-3: SUBJECT TO NATIONAL 2005 ELECTRICAL CODE. IF INTERNALLY LIGHTED > 12V MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN. SUBJECT TO APPROVAL. WHEN INSTALLED
Occupancy Inspection - Codes Commercial Not Ready 06/29/2010
Correction
Partial Correction
06/29/2010
INSTALLATION OF LIGHTED SIGN UL LABELS AFFIXED NO ISSUES FOUND
Above Ceiling Inspection Partial 06/29/2010
Correction
Partial Correction
06/29/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS EAST N-S BAY; CENTER N-S BAY; EAST PERIMETER SOFFIT; NORTH PERIM SOFFIT; WEST N-S BAY; NW CORNER; CORRIDORS ENSURE TEMP ELECT WIRING & FIXTURES ARE REMOVED. NOTE: TRUSS JOIST BOTTOM CHORD BRACES YET TO BE WELDED @ UPPER ENDS AFTER RTU'S ARE INSTALLED. INCL SUSPENDED "CLOUDS" OK TO COVER WHEN READY:
Correction
Resolved
06/29/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 103; 104; 105; 106; 107; 108 OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Occupancy Inspection - Codes Commercial Failed 06/30/2010
Correction
Resolved
06/30/2010
INSTALLATION OF LIGHTED SIGN UL LABELS AFFIXED NO ISSUES FOUND
Correction
Corrective Action Required
06/30/2010
TRUSS JOIST BOTTOM CHORD BRACES SUBJECT TO APPROVAL WELD TOP END AT BAR JOIST ENSURE BOLT TIGHT @BOTTOM
Correction
Corrective Action Required
06/30/2010
ELECTRICAL RECEPTACLE @ S.E. HVAC RTU NOT HOT FOR TEST
Correction
Corrective Action Required
06/30/2010
DESIGNATION OF ROOFTOP HVAC UNITS AFFIX PERMANENT LABEL(S) DESIGNATE SUITE & UNIT #
Correction
Corrective Action Required
06/30/2010
DISPLAY OF "NO SMOKING" SIGN(S) LS CODE OF ORDINANCES 17-309: SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY NOT FOUND AFFIXED AT PUBLIC ENTRY(IES)
Correction
Corrective Action Required
06/30/2010
IDENTIFICATION OF ELECTRICAL SERVICE PANELS PER DRAWINGS OR OCCUPANT PREFERENCE AFFIX PERMANENT LABELS FACE OF PANEL FRONT
Correction
Corrective Action Required
06/30/2010
ELECTRICAL PANEL SCHEDULES NEC 110-22; 384-13: EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE" NOT COMPLETED SERVICE PANELS
Correction
Corrective Action Required
06/30/2010
GLAZING OF PUBLIC ENTRY DOORS LSCO 7-905; IBC 2406 SUBJECT TO APPROVAL WHEN COMPLETED
Correction
Partial Correction
06/30/2010
USE / OCCUPANCY APPROVAL STATUS UNTIL APPROVED OK TO SET UP FOR BUSINESS NO PUBLIC ENTRY
Occupancy Inspection - Codes Commercial Passed 07/02/2010
Correction
Resolved
07/02/2010
TRUSS JOIST BOTTOM CHORD BRACES WELDED TO BAR JOISTS
Correction
Resolved
07/02/2010
ELECTRICAL RECEPTACLE @ S.E. HVAC RTU TESTED
Correction
Resolved
07/02/2010
DESIGNATION OF ROOFTOP HVAC UNITS PERMANENT LABELS AFFIXED
Correction
Resolved
07/02/2010
DISPLAY OF "NO SMOKING" SIGN(S) AT PUBLIC ENTRIES IN PROGRESS
Correction
Resolved
07/02/2010
IDENTIFICATION OF ELECTRICAL SERVICE PANELS
Correction
Resolved
07/02/2010
ELECTRICAL PANEL SCHEDULES SERVICE PANELS
Correction
Resolved
07/02/2010
GLAZING OF PUBLIC ENTRY DOORS ETCHED "TEMPERED"
Correction
Resolved
07/02/2010
USE / OCCUPANCY APPROVAL STATUS
Above Ceiling Inspection Passed 07/06/2010
Correction
Resolved
07/06/2010
GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS EAST N-S BAY; CENTER N-S BAY; EAST PERIMETER SOFFIT; NORTH PERIM SOFFIT; WEST N-S BAY; NW CORNER; CORRIDORS ENSURE TEMP ELECT WIRING & FIXTURES ARE REMOVED. INCL SUSPENDED "CLOUDS" OK TO COVER WHEN READY:
Correction
Resolved
07/06/2010
ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS 103; 104; 105; 106; 107; 108 OK TO COVER WHEN READY CEILINGS @ SPACES BELOW:
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home